Class C Cargo Compartment ULD Suppression Agent Penetration Test. Second IMLBTCM Audience >. Harry Webster, FAA Fire Safety Br. September 9, 2014. Purpose. To determine the infiltration rate of Halon 1301 into a standard LD3 ULD. “Quick Look”, more rigorous tests to follow. Background.

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about 'Class C Cargo Compartment ULD Suppression Agent Penetration Test' - illana-lindsay


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
class c cargo compartment uld suppression agent penetration test

Class C Cargo Compartment ULD Suppression Agent Penetration Test

Second IMLBTCMAudience>

Harry Webster, FAA Fire Safety Br.

September 9, 2014

purpose
Purpose

To determine the infiltration rate of Halon1301 into a standard LD3 ULD.

“Quick Look”, more rigorous tests to follow

background
Background

Halon 1301 has been shown to be effective in suppressing the electrolyte fire associated with lithium-ion cells in thermal runaway.

Halon 1301 has been shown to be an effective explosion suppressant.

The effectiveness of the agent is predicated on the agent concentration and proximity to the fire.

why this is an issue
Why this is an issue

Lithium-ion battery fires originating in ULD’s may not be exposed to the full concentration of Halon 1301.

Potential for the explosive build up of unburned electrolyte gases.

test setup
Test Setup
  • Measure Halon concentration
    • Inside the environmental chamber
    • Inside the closed LD3
    • 20” above the floor
  • Volumes
    • Chamber volume: 284 cubic feet
    • LD3 volume: 160 cubic feet
results
Results
  • Test 1
    • Initial chamber concentration: 12.33%
    • Time to 5% concentration in LD3: 7:11 minutes
  • Test 2
    • Initial chamber concentration: 8.93%
    • Time to 5% concentration in LD3: 11:04 minutes
additional tests
Additional Tests
  • Tests will be conducted to measure the ability of Class C cargo compartment fire suppression agent to penetrate into standard AKE cargo containers.
additional tests1
Additional Tests
  • Aluminum AKE containers with flexible door coverings have been ordered. These types of containers are typical of what is used in many Class C cargo compartments.
  • FE25 (HFC-125) will be used as a surrogate gas for Halon 1301. Gas concentrations will be measured in the compartment outside of the containers and within the containers
additional tests2
Additional Tests
  • Variables include
    • Container loading
    • Simulated battery fire
      • Pressure pulse
      • Temperature