1 / 31

The Role of Controls for Indoor Air Quality

The Role of Controls for Indoor Air Quality. Kent W. Peterson, PE, Fellow ASHRAE P2S Engineering, Inc. kent.peterson@p2seng.com. Mid Columbia ASHRAE Chapter. Introduction. Proper operating controls are fundamental to providing acceptable indoor air quality

gen
Download Presentation

The Role of Controls for Indoor Air Quality

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. The Role of Controls for Indoor Air Quality • Kent W. Peterson, PE, Fellow ASHRAE • P2S Engineering, Inc. • kent.peterson@p2seng.com Mid Columbia ASHRAE Chapter

  2. Introduction • Proper operating controls are fundamental to providing acceptable indoor air quality • Many control factors must be considered to be effective in maintaining air quality

  3. Topics of Discussion • Control fundamentals • Relative humidity control • Building pressurization control • Ventilation control • ASHRAE Standard 62.1-2004 • Ventilation Rate Procedure • Demand Controlled Ventilation

  4. ASHRAEStandard 62.1-2004 • 5.4 Ventilation System Controls. Mechanical ventilation systems shall include controls, manual or automatic, that enable the fan system to operate whenever the spaces served are occupied. The system shall be designed to maintain the minimum outdoor airflow as required by Section 6 under any load condition.

  5. IMC Section 403.3Mechanical Ventilation • The ventilation system shall be designed to supply the required rate of ventilation air continuously during the period the space is occupied, except as otherwise stated in other provisions of the code.

  6. Control System Goals • Provide required amount of ventilation air throughout the complete range of operating conditions without wasting energy • Must function reliably over a long time • Must be usable by the building operating staff Control Fundamentals

  7. Control Reliability • Accuracy and inaccuracy • Measure controlled parameter • Capable controls • Commissioning Control Fundamentals

  8. Control Accuracy • Describes the total of all deviations between the true value and the measured value • Typically expressed as the percent of full-scale range • Inaccuracy refers to the departure from the actual value to which all causes of error contribute • Total Error = SQRT [ (error1)2 + (error2)2 + … + (errorn)2 ] Control Fundamentals Accuracy

  9. Ventilation Control Strategies for VAV • Common OSA Control Methods • Fan tracking • Use of commissioning data • Plenum pressure differential • Flow monitoring Control Fundamentals

  10. Outside Air Control • A fixed minimum outside air damper position with no control is not a valid control strategy for a VAV system under any condition Not Recommended Control Fundamentals

  11. 100,000 cfm SA 85,000 cfm RA 15,000 cfm OSA 3% sensing accuracy 3,000 cfm SA error 2,550 cfm RA error 37% Error on OSA Fan Tracking • Assumption: The difference between the measured supply airflow and return airflow is the amount of outside air. Not Recommended Control Fundamentals OSA Control Methods

  12. Use Commissioning Data • Assumption: • That for any given airflow in a system, there is some OSA damper position that provides the required OSA quantity Not Recommended Control Fundamentals OSA Control Methods

  13. Plenum Pressure Control • Maintain a fixed MA plenum pressure differential by modulating the RA damper Control Fundamentals OSA Control Methods

  14. Flow Monitoring • Measure the amount of ventilation air to control • Flow measurement • Velocity must be high enough • Typically need minimum 2D before & 1D after the flow element (will increase if turning vanes are not used) • Flow sensing built into dampers Control Fundamentals OSA Control Methods

  15. Measuring Airflow • Different sensing means advantages can depend on the application • <1000 fpm Thermal anemometry • >1000 fpm Pitot tube • Understand how accuracy can impact the control method selected • Caution when controlling differential Control Fundamentals Accuracy

  16. Flow Monitoring (continued) • Combination damper-flow station PV = PT - PS Control Fundamentals OSA Control Methods

  17. Relative HumidityControl • Humidity control is required for good IAQ • ASHRAE Standard 62.1 Section 5 recommends that RH be maintained below 65% Controls for Good IAQ

  18. Building Pressurization Control • Negative building pressure causes infiltration • Infiltration in hot and humid climates can cause IAQ problems Controls for Good IAQ

  19. Standard 62.1-2004Ventilation Control • Classifications • Ventilation Rate Procedure • Indoor Air Quality Procedure • Variable Supply Air • Operations and Maintenance • Demand Controlled Ventilation Ventilation Control

  20. Standard 62.1-2004Ventilation Rate Procedure • New procedure for calculating outside air flow rates • Default values for ventilation system efficiency and multiple spaces effects for simplicity • Reduced rates in most occupancies Ventilation Control Standard 62.1

  21. Standard 62.1-2004Ventilation Rate Procedure People Component Building Component Breathing Zone Outdoor Airflow CFM Vbz = Rp Pz + Ra Az Minimum CFM/Person Ventilation Control Zone Floor Area Standard 62.1 Zone Population Minimum CFM/ft2

  22. Minimum Ventilation Rate In Breathing Zone Application cfm/person cfm/ft2 Offices Office space 5 0.06 Reception areas 5 0.06 Conference rooms 5 0.06 Public Spaces Corridors and utilities 0.06 Public Restrooms note note Excerpt from Table 6.1 of Standard 62.1-2004

  23. Standard 62.1-2004Ventilation Rate Procedure • Terms • Vbz Breathing Zone Outdoor Air • Ez Zone Air Distribution Effectiveness • Voz Zone Outdoor Airflow • Vpz Zone Primary Airflow • Zp Primary Outdoor Air Fraction • Vot Uncorrected Outdoor Air Intake • Ev System Ventilation Efficiency • Vot Outdoor Air Intake Ventilation Control Standard 62.1

  24. Standard 62.1-2004 Reset • 6.2.7 Dynamic Reset. The system may be designed to reset the design outdoor air intake flow (Vot) and/or space or zone airflow as operating conditions change. • Variations on occupancy • Variations in the efficiency with which the outside air is distributed • Higher fraction of OSA due to free cooling or exhaust air makeup

  25. Demand Controlled Ventilation (DCV) • It is “any” method used to control ventilation that modifies intake rates based on changing “demand” • “Demand” is usually measured as a change in the occupancy • CO2 sensing is typically used as an occupancy indicator Ventilation Control

  26. Understanding CO2 • CO2 is not an indicator of IAQ • If ventilation rate is 15 cfm per person (1.2 met units) the resulting steady-state CO2 concentration relative to outdoor is 700 ppm differential • Standard 62.1 Appendix C Ventilation Control DCV Using CO2

  27. Demand Controlled Ventilation • Avoid CO2 sensors in RA ducts • Zone sensors in breathing zone • Outdoor ventilation control • Minimum 0.15 cfm/ft2 OSA • Modulate airflow rate to space first • Modulate OSA rate to maintain the CO2 setpoint of 1000-1100 ppm Ventilation Control DCV Using CO2

  28. Demand Controlled Ventilation • Good candidates • Unpredictable variations in occupancy • Climate where cooling and heating is required most of year • Low pollutant emissions from non-occupant sources • DCV guidance is available • Centralized CO2 monitoring Ventilation Control DCV Using CO2

  29. IAQ Control System … • Must understand system relationships and accuracy • Requires careful selection • Should be commissioned • Must be usable by the building operating staff • Must function reliably over a long time Controls for IAQ

  30. For Further Information • ASHRAE Publications • Standard 62.1-2004 • ASHRAE Guideline 16-2003 • Research Project RP-980 • Techniques for Measuring and Controlling Outside Air Intake Rates in Variable Air Volume Systems • ASHRAE Journal Articles • Transactions • Humidity Control Design Guide • Trade journals Controls for IAQ

More Related