1 / 11

Earthing System

Earthing System. Earthing System for : - Electrical Network - General Building - Communication Tower - Industrial Building. Earthing System for Network. Two Letter Codes T N, T T, I T The First letter indicates connection between earth and power supply

garibay
Download Presentation

Earthing System

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Earthing System Earthing System for : - Electrical Network - General Building - Communication Tower - Industrial Building

  2. Earthing System for Network Two Letter Codes T N, T T, I T The First letter indicates connection between earth and power supply T : direct connection of a point with earth I :no point is connected with earth (Isolation) The Second Letter indicate connection between earth &electrical device T :direct connection with earth N :connection to earth via the supply network

  3. T N network TN Transformer star point is connected with earth PE protective earth

  4. TT network TT earthing system, the protective earth connection of the consumer is provided by a local connection to earth, independent of any earth connection at the generator

  5. IT network IT network, the distribution system has no connection to earth at all, or it has only a high impedance connection. In such systems an insulation monitoring device used to monitor the impedance.

  6. Earthing Design Consideration A correctly designed and installed earthing system will safeguard both lives and equipment. A good earth connection should have: -Low electrical resistance to earth -Good corrosion resistance -Ability to carry the required current repeatedly -A reliable life of at least 30 years The crucial factors that determine the resistance to earth of an electrode are: - Soil resistivity - Electrode dimensions - Area available - Earth electrode materials

  7. Soil Resistivity Effect of soil type on resistivity Soil type Typical resistivity Ohm-m Marshy ground 2.7 Loam and clay 150 Chalk 400 Sand 8,000 Peat 200 upwards Sandy gravel 500 Rock 1,000 upwards

  8. Earthing System for TowerRadial System

  9. Electrodes

  10. Ring System12 meter between loops

  11. Earthing Testing Resistance must be less than 5 ohm in general building Resistance must be less than 2 ohm in hospitals & clinic building Resistance must be less than 0.5 ohm in electronic equipments