SECTION 5 COMMERCIAL REFRIGERATION UNIT 24 EXPANSION DEVICES. UNIT OBJECTIVES. List and describe the three most popular expansion devices Explain the operating characteristics of various expansion valves Explain how various expansion devices respond to load changes

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about 'SECTION 5 COMMERCIAL REFRIGERATION UNIT 24 EXPANSION DEVICES' - emery-mccall


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
slide1

SECTION 5

COMMERCIAL REFRIGERATION

UNIT 24

EXPANSION DEVICES

unit objectives
UNIT OBJECTIVES
  • List and describe the three most popular expansion devices
  • Explain the operating characteristics of various expansion valves
  • Explain how various expansion devices respond to load changes
  • Describe the operation of balanced port, dual port and electronic
  • expansion valves
  • Explain how electronic controllers are used to control expansion
  • valves

After studying this unit, the reader should be able to

expansion metering devices
EXPANSION (METERING) DEVICES
  • Meters the correct amount of refrigerant to the evaporator
  • Installed in the liquid line at the inlet of the evaporator
  • Common devices: Automatic expansion valve, thermostatic expansion valve, fixed bore (capillary tube)
  • Less common devices: High-side float, low-side float
slide4

Compressor

Condenser

Direction of Refrigerant Flow

Evaporator

Metering device

thermostatic expansion valve txv
THERMOSTATIC EXPANSION VALVE (TXV)
  • Maintains a constant evaporator superheat
  • If the evaporator superheat is high, the valve will open
  • Superheat ensures that no liquid refrigerant leaves the evaporator
  • Low superheat increases the net refrigerant effect
slide6

Transmission Line

Evaporator

Thermal Bulb

Thermostatic Expansion Valve

Liquid Line

Direction of Refrigerant Flow

txv components
TXV COMPONENTS
  • Valve body
  • Diaphragm
  • Needle and seat
  • Spring
  • Adjustment and packing gland
  • Sensing bulb and transmission tube
the valve body
THE VALVE BODY
  • Machined brass or stainless steel
  • Holds components together
  • Provides means to connect valve to the piping circuit
  • Fastened by flare, solder, or flange
  • Has an inlet screen to stop any small particulate matter from entering valve
the diaphragm
THE DIAPHRAGM
  • Moves the needle in and out of the seat in response to system load changes
  • Flexes downward to open the valve
  • Flexes upward to close the valve
  • Made of thin, flexible stainless steel
  • Located at the top of the valve
slide10

Bulb pressure pushes down to open the valve

Diaphragm

Evaporator pressure pushes up to close the valve

Spring pressure pushes up to close the valve

needle and seat
NEEDLE AND SEAT
  • Control refrigerant flow through the valve
  • Needle is pushed into the seat to reduce refrigerant flow to the evaporator
  • Made of stainless steel
  • The greater the pressure difference across the needle and seat, the greater the amount of flow through the valve
slide12

Diaphragm

Seat

Push Rods

Needle

slide13

Diaphragm pushed up

Needle pushed into the seat, closing the valve

slide14

Diaphragm pushed down

Needle pushed out of the seat, opening the valve

the spring
THE SPRING
  • One of the valve’s closing forces
  • Acts to push the needle into the seat, causing the valve to close
  • Spring pressure determines the evaporator superheat
  • Spring tension can be field adjusted
  • Only EXPERIENCED field technicians should do adjustments on the valve
the sensing bulb and transmission line
THE SENSING BULB AND TRANSMISSION LINE
  • Senses temperature at the outlet of the evaporator
  • This temperature is converted to a pressure and is transmitted to the top of the diaphragm
  • The fluid in the bulb responds to a pressure / temperature relationship
  • When the suction line temperature goes up, the bulb pressure goes up
  • The bulb pressure is the only opening pressure that controls the valve
slide18

Thermal Bulb

Transmission Line

Valve body

Saturated refrigerant to the evaporator

Liquid refrigerant from condenser or receiver

Superheat spring adjusting screw

types of bulb charge
TYPES OF BULB CHARGE
  • Bulb charge is the type and amount of refrigerant contained in the thermal bulb transmission line and the space above the diaphragm
    • Liquid charge
    • Vapor charge
    • Cross liquid charge
    • Cross vapor charge
the liquid charge bulb
THE LIQUID CHARGE BULB
  • Bulb contains the same refrigerant as the refrigeration system
  • Under all conditions, the bulb will ALWAYS contain some liquid
  • The refrigerant in the bulb will always follow the pressure/temperature relationship of the system
the cross liquid charge bulb
THE CROSS LIQUID CHARGE BULB
  • Bulb contains a different refrigerant than the system
  • Under all conditions, the bulb will ALWAYS contain some liquid
  • The bulb does not follow the pressure/ temperature relationship of the system
  • Valve closes during the compressor off cycle
the vapor charge bulb
THE VAPOR CHARGE BULB
  • Bulb contains the same refrigerant as the system
  • Bulb only contains a small amount of liquid
  • Also called a critical charge bulb
  • At some predetermined temperature, all of the liquid in the bulb will boil until only vapor remains
  • Any further increases in bulb temperature will have no effect on the bulb pressure
the cross vapor charge bulb
THE CROSS VAPOR CHARGE BULB
  • Bulb contains a different refrigerant than the system
  • Bulb only contains a small amount of liquid
  • Also called a critical charge bulb
  • At some predetermined temperature, all of the liquid in the bulb will boil until only vapor remains
  • Any further increases in bulb temperature will have no effect on the bulb pressure
example of a txv with internal equalizer liquid filled bulb
EXAMPLE OF A TXV WITH INTERNAL EQUALIZER – LIQUID-FILLED BULB
  • Normal load conditions – medium temperature application, R-134a, valve is in equilibrium
  • Suction pressure 18.4 psig
  • Suction line temperature 30°F, PBULB= 26.1 psig
  • PSPRING + PEVAPORATOR = PBULB
  • Spring pressure + 18.4 psig = 26.1 psig
  • Spring pressure = 7.7 psig
slide25

30°F

26.1 psig

Spring pressure = ?

Evaporator pressure 18.4 psig

26.1 psig = Ps + 18.4 psig

Ps = 7.7 psig

R-134a

load changes with food added to cooler
LOAD CHANGES WITH FOOD ADDED TO COOLER
  • Addition of warm food increases evaporator load
  • Refrigerant boils faster and suction pressure rises
  • Evaporator superheat rises
  • Valve opens to feed more refrigerant to the evaporator
  • Increased evaporator superheat causes temperature of remote bulb to rise
load changes with food removed from the cooler
LOAD CHANGES WITH FOOD REMOVED FROM THE COOLER
  • Removal of food reduces load on the evaporator
  • Refrigerant boils slower and suction pressure drops
  • Evaporator superheat drops
  • Valve closes to feed less refrigerant to the evaporator
txv with external equalizer
TXV WITH EXTERNAL EQUALIZER
  • Used if an evaporator has more than a 2.5 psig drop from inlet to outlet
  • The evaporator pressure is sensed at the outlet of the coil instead of the inlet
  • Used to prevent the coil from starving
  • Connected to the evaporator outlet after the thermal bulb
  • Used to compensate for pressure drop in the evaporator
slide29

External equalizer line connected to the outlet of the evaporator coil

Diaphragm

Solid brass divider

Evaporator pressure pushing up on the diaphragm

Saturated refrigerant to the evaporator

Liquid refrigerant to the expansion valve

txv responses to load changes
TXV RESPONSES TO LOAD CHANGES
  • When load increases
    • Refrigerant boils faster and the suction line temperature increases
    • Valve opens to feed more refrigerant to the evaporator
  • When load decreases
    • Refrigerant takes longer to boil
    • Valve closes to feed less refrigerant to the evaporator
balanced port txv
BALANCED PORT TXV
  • Designed to operate in low ambient conditions
  • Used if any of the following conditions exist

- Large varying head pressures

- Large varying pressure drops across the TXV

- Widely varying evaporator loads

- Very low liquid line temperatures

  • Have larger-than-normal orifices
dual port txv
DUAL PORT TXV
  • Used when systems need a larger TXV for short periods of time
  • Dual-port valves have two independent capacities

- Larger port for periods of high load

- Smaller port for periods of normal load

- TXV capacity is doubled when larger port is open all the way

pressure limiting txv
PRESSURE LIMITING TXV
  • Allows evaporator pressure to only reach a predetermined pressure
  • If the evaporator pressure exceeds this pressure, the valve will close
  • Desirable on low-temperature applications
sensing element bulb installation
SENSING ELEMENT (BULB) INSTALLATION
  • Bulb should be mounted on the suction line as close to the evaporator as possible
  • Suction line should be clean and straight
  • Bulb should be mounted securely
  • Follow manufacturer’s instructions
  • For small suction lines, the bulb is usually secured to the top of the line
slide35

Thermal bulb mounted on top of the line

Use strapping material supplied with the valve to hold bulb securely to the suction line

Thermal bulb located 45° below horizontal

Suction line smaller than 3/4”

Suction line larger than 3/4”

the solid state controlled expansion valve
THE SOLID-STATE CONTROLLED EXPANSION VALVE
  • Uses a thermistor as a sensing element
  • Electrically controlled
  • When coil is energized, the valve opens
  • Responds very quickly to temperature changes
  • Suitable for heat pump applications
step motor expansion valves
STEP MOTOR EXPANSION VALVES
  • Uses a small motor to control the valve port
  • Valve port controls evaporator superheat
  • Temperature sensor sends a signal to the controller
  • The controller sends a signal to the motor
  • The motor turns a fraction of a rotation for each controller signal
algorithms and pid controllers
ALGORITHMS AND PID CONTROLLERS
  • Proportional Controllers

- Generate an analog output signal

- Difference between actual superheat and superheat set point is the “offset” or “error”

  • Integral Controller Modes

- Helps reduce the “error” or “offset”

- Calculates error size and the length of time the error exists

  • Derivative Controller Modes

- Estimate rate of change of temperature/time curve

automatic expansion valve
AUTOMATIC EXPANSION VALVE
  • Maintains constant pressure in the evaporator
  • When the evaporator pressure drops, the valve opens
  • The spring pressure pushes to open the valve
  • The evaporator pressure pushes to close the valve
  • Turning the adjustment screw into the valve increases the spring pressure
slide40

Spring pressure pushes down to open the valve

Diaphragm

Two pressures control the automatic expansion valve

Evaporator pressure pushes up to close the valve

slide41

Diaphragm pushed up

Needle pushed into the seat, closing the valve

Caused by an increase in evaporator pressure

slide42

Diaphragm pushed down

Needle pushed out of the seat, opening the valve

Caused by a decrease in evaporator pressure

slide43

Spring pressure

Spring

Diaphragm

Needle and Seat

Saturated refrigerant to the evaporator

Liquid refrigerant from condenser or receiver

Evaporator pressure

automatic expansion valve response to load changes
AUTOMATIC EXPANSION VALVE RESPONSE TO LOAD CHANGES
  • Responds in reverse to load changes
  • If the load increases
    • Refrigerant boils faster in the evaporator
    • The evaporator pressure increases
    • The valve closes
  • Used where the load is fairly constant
the capillary tube metering device
THE CAPILLARY TUBE METERING DEVICE
  • Controls refrigerant flow by the pressure drop across it
  • Diameter and length of the tube determine flow at a given pressure
  • Does not maintain evaporator pressure or superheat
  • Used when the load is relatively constant
  • No moving parts to wear out
operating charge for the capillary tube system
OPERATING CHARGE FOR THE CAPILLARY TUBE SYSTEM
  • Capillary tube systems are critically charged
  • All refrigerant in the system circulates at all times when the system is running
  • Capillary tube sometimes fastened to the suction line for heat exchange
  • Responds very slowly to system load changes
unit summary 1
UNIT SUMMARY - 1
  • Expansion devices meter the correct amount of refrigerant to the evaporator according to system operating conditions
  • Common expansion valves include the capillary tube, automatic expansion valve and the thermostatic expansion valve
  • The thermostatic expansion valve is designed to maintain constant superheat in the evaporator
unit summary 2
UNIT SUMMARY - 2
  • Three pressures control the operation of the TXV: the bulb pressure, the spring pressure and the evaporator pressure
  • Thermal bulb can be liquid-charged, vapor-charged, cross liquid-charged, or cross vapor-charged
  • Internally equalized TXVs get the evaporator pressure from the inlet of the coil, while externally equalized TXVs get the evaporator pressure from the outlet of the coil
unit summary 3
UNIT SUMMARY - 3
  • Special TXVs include the balanced port TXV, the dual port TXV and the electronic TXV
  • The automatic expansion valve maintains a constant evaporator pressure
  • Two pressure control the AXV: the spring pressure and the evaporator pressure
  • The capillary tube is a fixed bore metering device
  • The capillary tube meters refrigerant depending on the pressure drop across the tube