Training Package TP 05/05. Prevention of Over - Pressurization. Asia Industrial Gases Association 298 Tiong Bahru Road, #20-01 Central Plaza, Singapore 168730 Internet: http//www.asiaiga.org. 1. Prevention of Over - Pressurization. Disclaimer

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about '' - duff


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
Slide1 l.jpg

Training Package

TP 05/05

Prevention of Over - Pressurization

Asia Industrial Gases Association

298 Tiong Bahru Road, #20-01 Central Plaza, Singapore 168730

Internet: http//www.asiaiga.org

1


Prevention of over pressurization l.jpg
Prevention of Over - Pressurization

Disclaimer

All publications of AIGA or bearing AIGA’s name contain information, including Codes of Practice, safety procedures and other technical information that were obtained from sources believed by AIGA to be reliable and/ or based on technical information and experience currently available from members of AIGA and others at the date of the publication. As such, we do not make any representation or warranty nor accept any liability as to the accuracy, completeness or correctness of the information contained in these publications.

While AIGA recommends that its members refer to or use its publications, such reference to or use thereof by its members or third parties is purely voluntary and not binding.

AIGA or its members make no guarantee of the results and assume no liability or responsibility in connection with the reference to or use of information or suggestions contained in AIGA’s publications.

AIGA has no control whatsoever as regards, performance or non performance, misinterpretation, proper or improper use of any information or suggestions contained in AIGA’s publications by any person or entity (including AIGA members) and AIGA expressly disclaims any liability in connection thereto.

AIGA’s publications are subject to periodic review and users are cautioned to obtain the latest edition.

 AIGA 2005 - AIGA grants permission to reproduce this publication provided the Association is acknowledged as the source

Asia Industrial Gases Association 298 Tiong Bahru Road, #20-01 Central Plaza, Singapore 168730

Internet: http//www.asiaiga.org


What is over pressurization l.jpg
What is Over-Pressurization?

  • The increase of pressure inside a piece of equipment beyond its ability to hold that pressure.

    • Vessels and tanks

    • Cylinders and bottles

    • Compressors and pumps

    • Piping and tubing

    • Hoses and flex joints

    • Instruments and valves


Imagine blowing up a balloon l.jpg
Imagine - Blowing Up a Balloon

This could hurt. Now imagine if you were near a vessel, pipe or cylinder when it ruptured!


Over pressurization hazards l.jpg
Over-Pressurization Hazards

  • Ruptured process vessels, cylinders, piping

  • Whipping hoses

  • Flying debris and shrapnel

  • Serious injury

  • Death


Hazardous result l.jpg
Hazardous result

An ammonia cylinder that failed due to overfilling & hydraulic-king


Over pressurization kills l.jpg
Over-Pressurization Kills

  • Incident 1: Liquid trapped in the ball of a ball valve expanded, causing the valve to come apart. Worker dies when contents of CO2 storage tank released in his direction.

  • Incident 2: A chlorine cylinder ruptures during fill procedure, killing worker in the same room.


Over pressurization kills8 l.jpg
Over-Pressurization Kills

  • Over-pressurization can occur at your location too!


Causes of over pressurization l.jpg
Causes of Over-Pressurization

  • Faulty process control

  • Process upsets

  • Trapped liquefied gases

    • In a pipe or hose between two closed valves

    • In a ball or gate valve not designed to relieve internal pressure


Causes of over pressurization10 l.jpg
Causes of Over-Pressurization

  • Poor equipment and process design

  • Uncontrolled modifications

  • Human ignorance

  • Human error


Faulty process control l.jpg
Faulty Process Control

  • Improperly calibrated control devices (temperature, pressure, flow, level…)

  • Malfunctioning control sensing device such as:

    • Isolation valves closed

    • Inlet ports blocked

    • Devices damaged


Faulty process control cont d l.jpg
Faulty Process Control (cont’d)

  • Malfunctioning control valves

    • Sticking control valves, solenoids

    • Closed or throttled isolation or bypass valves


Process upsets l.jpg
Process Upsets

  • Sudden flow rate, temperature or pressure changes

  • Process operation outside of established operating limits


Trapped liquefied gases l.jpg
Trapped Liquefied Gases

  • Expand as they warm and vaporize

  • Pressure rises can exceed most process valves, piping and hoses pressure ratings

  • If no vapour in the trapped space, hydraulic loading can occur - leads to extremely high pressures in a very short time


Liquefied gases l.jpg
Liquefied Gases

  • If allowed to reach ambient (room) temperatures:

  • Liquid carbon dioxide could reach 1,100 psi!*

  • Liquid gases like helium, hydrogen, nitrogen, oxygen and argon could reach 22,000 to 50,000 psi!*

    * If the container could hold the pressure.


Liquefied gases cont d l.jpg
Liquefied Gases (cont’d)

  • Do not over-fill a cylinder or tank

    • Maintain proper vapour space

  • Do not trap liquid gases

    • Must be able to relieve pressure


Liquefied gas cont d l.jpg
Liquefied Gas (cont’d)

  • Expand 700 to 800 times in volume as they suddenly change (“flash”) from a liquid state into a gas.

  • Results in a tremendous force similar to that released in an explosion.


Trapped liquid with vapour l.jpg
Trapped Liquid With vapour

As temperature rises, a given mass of liquid can require more room (its density changes)...

Vapour can be compressed. So it makes room for the expanding liquid. Pressure rises gradually with temperature. Eventually, most liquefied gases will develop pressures that will rupture the container.


Trapped liquid without vapour l.jpg
Trapped Liquid Without vapour

As temperature rises, a given mass of liquid can require more room (its density changes)...

Liquid cannot be compressed, so as it gets bigger, it has to go somewhere! It quickly develops extremely high pressure.


With and without vapour l.jpg
With and Without vapour

The pressure of liquid without vapour rises quickly.

Liquid and vapour pressure rises gradually, but still reaches higher pressures than what typical equipment can contain.

Pressure (psig)

Heat Input


Ball valve hazard potential l.jpg
Ball Valve Hazard Potential

(Side View)

Stem

Valve Body

Upstream

(Higher Pressure)

Downstream

(Lower Pressure)

Seal

Trapped Liquid


Hazardous result22 l.jpg
Hazardous Result

(Side View)


Valve design for internal relief l.jpg
Valve Design for Internal Relief

Alternatively, ball valves have special self-relieving seats

Ball valves have

1/8” hole in ball

Upstream

(Higher Pressure)

Downstream

(Lower Pressure)


Gate valve l.jpg
Gate Valve

Notch cut in gate


Faulty system design l.jpg
Faulty System Design

  • Equipment not designed for pressure or temperature extremes

  • Missing or isolated pressure relief devices

  • Relief devices that are too small


Faulty system design cont d l.jpg
Faulty System Design (cont’d)

  • Relief devices not set properly

  • Unanticipated modes of operation

  • Stressed piping, tubing, connectors

  • Relying solely on humans to control pressure


Case study faulty system design l.jpg
Case Study: Faulty System Design

  • A gas heater vessel ruptured at a CO2 plant in 1998

    • A dryer switching valve failed in open position.

    • High pressure process gas (800 psig) then entered the lower-pressure regeneration gas system.

    • The regeneration gas heater safety relief valve was not big enough to handle process gas flow rates.

    • The heater vessel ruptured.


Human ignorance error l.jpg
Human Ignorance & Error

  • Filling a low pressure cylinder on a high pressure filling manifold

  • Replacing relief devices with devices of a different design or pressure setting

  • Replacing a section of pipe, a valve or other process component with one that has a lower pressure rating than the original


Human ignorance error cont d l.jpg
Human Ignorance & Error(cont’d)

  • Compromising the integrity of a process component (dents, crimping, unchecked corrosion)

  • Not following established procedures


Case study human ignorance error l.jpg
Case Study: Human Ignorance & Error

  • Whipping hose during leak test:

    • Employee connected a 250 psig rated air hose to a high pressure nitrogen source.

    • He pressurized hose and manifold to 350 psig.

    • He discovered manifold leak, vented pressure and repaired leak.

    • Blow gun was attached to hose and employee claims that pressure was set to 200 psig.

    • Hose fitting failed, hose whipped and shredded a portion of employee’s coveralls.


Protecting ourselves l.jpg
Protecting Ourselves

  • Knowledgeable Employees

    • Proper training

  • Properly Designed Processes

    • Equipment that is good for the pressure

    • Control system designs that consider all scenarios

    • Valves with internal relief capability (for liquefied gases)


Protecting ourselves cont d l.jpg
Protecting Ourselves (cont’d)

  • Pressure Relief Devices

    • Relief valves, rupture disks

    • Dual relief valves with diverter valves

  • Proper Operating Procedures

  • Proper Maintenance Procedures


Proper maintenance l.jpg
Proper Maintenance

  • Relief Valves Calibration

    • Bench tested and reset every 5 years

    • Relief devices missing their wire seal must be removed from service and tested

    • Recalibration must be by a qualified person

  • Malfunctioning Relief Devices

    • Plugged or restricted inlets or outlets

    • Rust and dirt or ice in spring mechanism


Proper maintenance cont d l.jpg
Proper Maintenance (cont’d)

  • Process Controls and Sensing Devices Calibration

    • Gauges and thermometers

    • Metering devices

    • Solenoids

    • Temperature and pressure limit controls

    • Mercoids


Proper maintenance cont d35 l.jpg
Proper Maintenance (cont’d)

  • Ensure Replacement Parts are “Replacement-In-Kind”

    • Pipe, fittings and components with same pressure rating

    • Valves with same pressure relief capabilities


Management of change l.jpg
Management of Change

  • Follow established review procedures

  • Consider all modes of operations

  • For each process, ask “How can we have high pressure?”

  • Ensure proper pressure relief strategy for every process component


High pressure valve l.jpg
High Pressure Valve

Pressure Relief Device


Portable liquid container l.jpg
Portable Liquid Container

Rupture Disk

Pressure Relief Device


Forklift l.jpg
Forklift

Pressure Relief Device


Dual storage tank safety valves l.jpg
Dual Storage Tank Safety Valves

Pressure Relief Device


High pressure line safety l.jpg
High Pressure Line Safety

Pressure Relief

Device


Solenoid shut off valve l.jpg
Solenoid Shut-off Valve

Pressure Relief Device


Pressure temperature switch l.jpg
Pressure / Temperature Switch

Temperature Sensor

Pressure Inlet to Sensor


Mercoid switch l.jpg
Mercoid Switch

Mercoid Switch


High pressure shut off switches l.jpg
High Pressure Shut-Off Switches

Pressure Shut-off Switches


Review questions l.jpg
Review Questions

  • Give examples of processes or pieces of equipment at your location which can present an over-pressurization hazard?

  • What are the causes of over-pressurization?

  • Liquefied gases can expand up to __________ times in volume from liquid to gas.


Review questions47 l.jpg
Review Questions

  • Which is the most dangerous hazard, trapped liquid with or without vapour? Why?

  • What kinds of things can we do to protect from over-pressurization hazards?


ad