台電大樓主樓阻尼器 耐震補強案例

運用創新材料、技術、工法. 台電大樓主樓阻尼器 耐震補強案例. 台灣電力公司 營建處 中華民國 101 年 7 月 31 日. 台電大樓主樓耐震補強概述. 台電大樓主樓興建於民國 68 年、完工於民國 71 年屋齡已近 30 年,由於本大樓之功能特殊重要性高,台電公司參照最新版「建築物耐震設計規範及解說」中比本大樓設計年代較為嚴格之現行法規要求,委託中興工程顧問公司辦理大樓耐震能力評估及補強設計之規劃設計技術服務工作,其工作成果並經「中華民國結構工程學會」審查通過。台電公司於民國 98 年 12 月間辦理公開招標進行耐震補強工程以期提高其耐震能力並延長大樓使用年限。

deshawn
Download Presentation

台電大樓主樓阻尼器 耐震補強案例

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 運用創新材料、技術、工法 台電大樓主樓阻尼器耐震補強案例 台灣電力公司 營建處 中華民國101年7月31日

  2. 台電大樓主樓耐震補強概述 • 台電大樓主樓興建於民國68年、完工於民國71年屋齡已近30年,由於本大樓之功能特殊重要性高,台電公司參照最新版「建築物耐震設計規範及解說」中比本大樓設計年代較為嚴格之現行法規要求,委託中興工程顧問公司辦理大樓耐震能力評估及補強設計之規劃設計技術服務工作,其工作成果並經「中華民國結構工程學會」審查通過。台電公司於民國98年12月間辦理公開招標進行耐震補強工程以期提高其耐震能力並延長大樓使用年限。 • 台電大樓主樓為使用中之鋼構造辦公大樓,傳統耐震補強工法如增設鋼構斜撐、貼覆鋼鈑增大鋼構件斷面等施工方式,將嚴重影響大樓正常運作。本案採用增設黏滯液流阻尼器(Fluid Viscous Damper, FVD)減震補強工法(非專利品),使需要耐震補強之鋼構件及接頭大幅減少。本案為國內首次〝超高層建築〞進行耐震補強之案例。

  3. 台電大樓主樓耐震能力詳細評估(非線性側推分析)台電大樓主樓耐震能力詳細評估(非線性側推分析)

  4. 台電大樓主樓耐震能力詳細評估結果

  5. 台電大樓主樓結構系統耐震補強方案比較

  6. 建築物減震消能元件—黏滯液流阻尼器

  7. 台電大樓主樓採用74組黏滯液流阻尼器耐震補強台電大樓主樓採用74組黏滯液流阻尼器耐震補強

  8. 黏滯液流阻尼器減震消能原理

  9. FVD 減震消能元件主樓L(X)方向屋頂加速度減震效果

  10. FVD 減震消能元件主樓T(Y)方向屋頂加速度減震效果

  11. 國家地震工程研究中心阻尼器性能測試

  12. 國家地震工程研究中心阻尼器性能測試

  13. 黏滯液流阻尼器地震非線性歷時分析

  14. 黏滯液流阻尼器高阻尼比減震效果顯著

  15. 鋼構造傳統梁柱接頭 V.S.改良式梁柱接頭 傳統鋼構梁接頭 塑性轉角θp =0.92%~1.5%

  16. 鋼構造傳統梁柱接頭 V.S.改良式梁柱接頭 切削式改良接頭 改良式鋼構梁接頭 塑性轉角θp > 3%

  17. 敬請指教