Panasonic Advanced Ventilation Fans
Download
1 / 19

Panasonic Advanced Ventilation Fans - PowerPoint PPT Presentation


  • 349 Views
  • Updated On :

Panasonic Advanced Ventilation Fans. Panasonic Advanced Ventilation Fans. 40/20 CFM Spot Energy Recovery Ventilator. Dual speed settings for 40/20 or 20/10 CFM - 0.8 Sone at 40 CFM / <0.3 Sone at 20 CFM. FV-04VE1. Panasonic Advanced Ventilation Fans. Operation. 2-speed settings.

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about 'Panasonic Advanced Ventilation Fans' - daniel_millan


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript

Slide2 l.jpg

Panasonic Advanced Ventilation Fans

40/20 CFM Spot Energy Recovery Ventilator

  • Dual speed settings for 40/20 or 20/10 CFM- 0.8 Sone at 40 CFM / <0.3 Sone at 20 CFM

FV-04VE1


Slide3 l.jpg

Panasonic Advanced Ventilation Fans

Operation

2-speed settings


Slide4 l.jpg

Panasonic Advanced Ventilation Fans

Features:

Balanced VentilationExhaust & Supply Air

Exchange Core

Temper Air


Slide5 l.jpg

Panasonic Advanced Ventilation Fans

58℉

46℉

32℉

72℉



Slide7 l.jpg

Panasonic Advanced Ventilation Fans

Features:

Spot ERV – Home Office / Game Room / Family Rooms / Bedrooms

Whole-House ERV – Housing Authority Properties / Hotels / Studio Apts.


Slide8 l.jpg

Panasonic Advanced Ventilation Fans

Features:

Motor Technology – totally enclosed AC condenser motor, one motor operates two fan wheels

Filters – for supply and exhaust side to keep exchange core clean

Grille – contemporary design

No drain necessary!


Slide9 l.jpg

Panasonic Advanced Ventilation Fans

Operation

Switches

On = Hi or Lo speed

Off = shutdown

On

Off

40/20 CFM (factory preset)

20/10 CFM

Hi

Lo

Switch not supplied

Switch labels are provided for optional use


Slide10 l.jpg

White

A.C.

120V

Black

Ground

Orange

Yellow

On/Off

Blue

Hi/Low


Slide11 l.jpg

Panasonic Advanced Ventilation Fans

Operation

Frost Prevention Mode

Above 32 degree F

Both exhaust and supply fully function

From 32 – 20 degree F

Supply closes 30 minutes then opens 1 hour

Below 20 degree F

Supply closes 1 hour then opens 10 minutes


Slide12 l.jpg

Panasonic Advanced Ventilation Fans

37°F (3 ℃)

32°F (0 ℃)

temperature

19°F (-7 ℃)

Exhaust only

-13°F (-25 ℃)

30m

10m

10m

30m

1h

1h

1h

1h

1h

Damper Open

Damper Close

40 cfm

20 cfm

Defrost Operation (40 CFM)



Slide14 l.jpg

Panasonic Advanced Ventilation Fans

Installation

Mounting – Unit 14 inches wide. Fits between 16” on center joist

Wiring – 120/60 V/Hz 2 switches for on/off and high/low

Duct – 4” insulated duct (recommended) for exhaust and supply.

Terminations (exterior hoods) – separate by 3 feet or point 45 degrees opposite directions


Slide15 l.jpg

Panasonic Advanced Ventilation Fans

Installation

3 ft min.


Slide16 l.jpg

Panasonic Advanced Ventilation Fans

Maintenance:

Grille – light dish soap

Filters – vacuum with soft brush attachment

Exchange Core - vacuum with soft brush attachment


Slide17 l.jpg

Panasonic Advanced Ventilation Fans

Example 1:

Two bedrooms

1600 square feet

Master bedroom (7.5 CFM x 2) = 15 CFM

Second bedroom = 7.5 CFM

1600 sq ft x .01 = 16 CFM

Total 38.5 CFM

Use WhisperComfort set at 40 CFM

Sizing – Based on ASHRAE 62.2

Example 2:

Four bedrooms

2200 square feet

Master bedroom (7.5 CFM x 2) = 15 CFM

Other 3 bedrooms 7.5 each = 22.5 CFM

2200 sq ft x .01 = 22 CFM

Total 59.5 CFM

Use 2 WhisperComfort

Or

1 WhisperComfort and 1 WhisperGreen


Slide18 l.jpg

Panasonic Advanced Ventilation Fans

Ventilation Capacity Requirements (CSA-F326)

10CFM

Single Bed room

Living room

Family room

20CFM

Master Bed room

Large Basement room

ASHRAE62.2 2004

ASHRAE62 2001

(0.35 ACH)

1 Bed room

2 Bed room

3 Bed room

20CFM

500Ft2

N/A

N/A

429 Ft2

40CFM

2500 Ft2

1750 Ft2

1000 Ft2

857 Ft2

Spot Ventilation

Need to be chosen 10/20 CFM mode when it’s installed.

Whole House Ventilation (IAQ)

Need to be chosen 20/40 CFM mode when it’s installed.