1 / 86

Energy Efficient Compressed Air Systems

Energy Efficient Compressed Air Systems. Compressed Air Fundamentals. dW elec = ∫V dP / [ Eff compressor Eff motor Eff control ]. V = volume flow rate D P = pressure rise Eff = efficiencies of compressor, motor, and control. Internal cooling decreases electrical power.

clover
Download Presentation

Energy Efficient Compressed Air Systems

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Energy EfficientCompressed Air Systems

  2. Compressed Air Fundamentals dWelec= ∫V dP/ [EffcompressorEffmotorEffcontrol] • V = volume flow rate • DP = pressure rise • Eff = efficiencies of compressor, motor, and control Internal cooling decreases electrical power

  3. Compressed Air Savings Opportunities dWelec = ∫V dP / [EffcompressorEffmotorEffcontrol] • Reduce volume flow rate • Reduce pressure rise • Increase cooling during compression • Increase compressor efficiency • Increase motor efficiency • Increase control efficiency

  4. Compressed Air System

  5. Screw Compressor Operation

  6. Compressed Air System Savings Opportunities • End use • Eliminate inefficient uses of compressed air • Eliminate air pumps, agitation, cooling and suction • Use blower for low-pressure applications • Install solenoid valves to shut off air • Install air saver nozzles • Install differential pressure switches on bag houses • Distribution • Fix leaks • Decrease pressure drop in distribution system • Compressor System • Compress outside air • Use refrigerated dryer • Direct warm air into building during winter • Use load/unload control with auto shutoff or VSD for lag compressor • Stage compressors with pressure settings or controller • Add compressed air storage to increase auto shutoff

  7. Plant and Compressor Data For Calculating Example Savings • Plant operates 6,000 hours per year • Electricity cost including demand = $0.10 /kWh • Air compressor produces 4.2 scfm/hp • Air compressor motor is 90% efficient • Air compressor runs in load/unload control with FP0 = 0.50

  8. Eliminate Inefficient Uses of Compressed Air

  9. Replace Air Pump with Electric Pump • Air motors use 7x more electricity than electrical motors • Example • Replace 10 x 1-hp air pumps with electric pumps • Cost Savings = 10 hp / 0.90 x 6/7 x 0.75 kW/hp x 6,000 hr/yr x $0.10 /kWh = $4,300 /yr

  10. Replace Compressed Air with Mechanical Agitation • Compressed air agitation uses ~10x more electricity than mechanical agitation • Example • Replace air agitation from 0.5-in pipe at 50 psig with mechanical agitator. • Flow Savings = 11.6 (scfm/lbf) x [1 (in)]2 x 55 psia= 150 scfm • Power Savings = 150 scfm / (4.2 scfm/hp x 0.90) x 0.75 kW/hp x (1-0.50) = 15 kW • Cost Savings = 15 kW x 6,000 hr/yr x $0.10 /kWh = $9,000 /yr

  11. Replace Compressed Air Cooling with Chiller • ‘Vortex’ coolers use 4x more electricity than electric chillers • Example • Replace 10,200 Btu/hr cooler using 150 scfmwith chilled water • Cost Savings = 150 scfm / (4.2 scfm/hp x 90%) x 75% x 0.75 kW/hp x (1-0.50) x 6,000 hr/yr x $0.10 /kWh = $6,700 /year

  12. Replace Air With Heat Pipe Cabinet Coolers • Air coolers use 8x more electricity than (heat pipe + small fan) coolers • Example • Replace 2,400 Btu/hr compressed air cooler with heat pipe cooler • Cost comp air = 2,400 Btu/hr / 80 (Btu/hr)/cfm / (4.2 cfm/hp x 90%) x 0.75 kW/hpx (1-0.50) x 8,760 hr/yr x $0.10 /kWh = $2,607/year • Cost heat pipe = 0.6 A x 120 V / 1,000 VA/kW x 8,760 hr/yr x $0.10 /kWh = $ 63 /year • Implementation Cost = $1,000 Source: www.airtxinternational.com and www.system-directions.com

  13. Replace Pneumatic Suction Cups with Magnets • Suction cups use 6.0 scfmwhile holding while magnets use average of 0.3 scfm • Example • Replace cups with magnets if holding 3,000 hours per year. • Power Savings = 5.7 scfm / (4.2 scfm/hp x 0.90) x 0.75 kW/hpx (1-0.50) = 0.57 kW • Cost Savings = 0.57kW x 3,000 hr/yr x $0.10 /kWh = $167 /yr

  14. Use Blowers for Low-Pressure Applications • Blowers generate 7.2 scfm /hp at 20 psig while compressors generate 4.2 scfm/hp at 100 psig • Example • Install low-pressure blower for application needing 140 scfm of 20 psig air • Power Savings = 140 scfmx (1/4.2 – 1/7.2) hp/scfm / 0.90 x .75 kW/hpx (1-0.50) = 5.8 kW • Cost Savings = 5.8kW x 6,000 hr/yr x $0.10 /kWh = $3,472/yr

  15. Reduce End Use Compressed Air Demand

  16. Reduce Blow-off with Solenoid Valves • Flow from open tube (scfm) = 11.6 (scfm/lbf) x [Diameter (in)] 2 x Pressure (psia) • Example • Install solenoid to shut-off blowoff from 3/8-in pipe at 100 psig 80% of time • Flow Savings = 11.6 (scfm/lbf)x [3/8 (in)]2 x 115 psiax 80% = 150 scfm • Power Savings = 150 scfm/ (4.2 scfm/hp x 0.90) x 0.75 kW/hp x (1-0.50) = 15 kW • Cost Savings = 15 kW x 6,000 hr/yr x $0.10 /kWh = $8,933/yr • Cost of 3/8-inch solenoid valve = $100

  17. Reduce Blow off with Air-Saver Nozzles • Nozzles maximize entrained air and generate same flow and force with ~50% less compressed air • Example • Add nozzle to 1/8-in tube at 100 psig • Flow Savings = 11.6(scfm/lbf)x [1/8 (in)]2 x 115 psiax 50% = 10.4 scfm • Power Savings = 10.4 scfm / (4.2 scfm/hp x 0.90) x 0.75 kW/hp x (1-0.50) = 1.0kW • Cost Savings = 1.0 kW x 6,000 hr/yr x $0.10 /kWh = $620 /yr • Nozzles cost about $10 each

  18. Activate Bag House Air Pulses Using Pressure Differential Instead of Timer • Timers are designed for peak conditions, where demand-based control matches actual conditions • Example • Install differential pressure control to reduce timed pulse from 34 cfm by 60% • Flow Savings = 34 cfm x 60% = 20.4 cfm • Power Savings = 20.4 cfm/ (4.2 scfm/hp x 0.90) x 0.75 kW/hp x (1-0.50) = 2.0kW • Cost Savings = 2.0 kW x 6,000 hr/yr x $0.10 /kWh = $1,214/yr

  19. Fix Leaks

  20. Fix Leaks • Leaks continuously drain power • Leakage rate increases exponentially with leak diameter • Example • Fix one 1/64” leak • Power Savings = .25 cfm / (4.2 scfm/hp x 0.90) x 0.75 kW/hp x (1-0.50) = 0.025 kW • Cost Savings = 0.025 kW x 6,000 hr/yr x $0.10 /kWh = $15 /yr

  21. Fix Leaks • Many plants lose ~20% of compressed air to leaks • Example • Fix leaks in plant with fully loaded 100-hp compressor and 20% leakage • Power Savings = 100 hp / 0.90 x 0.20 x 0.75 kW/hp x (1-0.50) = 8.3kW • Cost Savings = 8.3 kW x 6,000 hr/yr x $0.10 /kWh = $5,000 /yr

  22. Identify Leaks Using Ultrasonic Sensor

  23. Quantify Leakage By Logging Flow or Compressor Power

  24. Fix Leaks Frequently • Leak Loss = Rate x Time • Repairing leaks frequently cuts leak load at same implementation cost • Example • Fix leaks every 2 weeks instead of every 4 weeks ifone new 1-cfm leak per week • Reduces leakage by 40%

  25. Starve Leaks by Shutting off Branch Headers • Valve on branch header can starve all downstream leaks when area is not in use • Example • Install valve to shut off header with 200 cfm leak load for 4,000 hr/yr • Power Savings = 200 scfm x 50% / (4.2 scfm/hp x 0.90) x 0.75 kW/hp x (1-0.50) = 9.9 kW • Cost Savings = 9.9 kW x 4,000 hr/yr x $0.10 /kWh = $3,969/yr

  26. Use Rubber In Place of Braded Hose Braided hoses dry-rot and develop leaks that can’t be detected with ultrasonic sensors.

  27. Reduce Distribution System Pressure Drop

  28. Use Looped Piping System • If DP < 10 psi at farthest end use, use looped rather than linear design • Design Guidelines • Main line: size from average cfm to get DP = 3 psi • Branch line: size from cfm peak to get DP = 3 psi • Feed lines: size from peak cfm to get DP = 1 psi • Select hose with DP < 1 psi

  29. Avoid ‘Collision’ Connections

  30. Maintain Filters • Place filter upstream of dryer to protect dryer • DP filter < 1 psi

  31. Size Dryer for DP< 5 psi Low Flow: DP = 1 psi High Flow: DP = 6 psi

  32. Then, Reduce Compressed Air Pressure • Work = V DP, thus compressor requires less work to produce air at lower outlet pressure • Fraction savings from reducing pressure = • Fraction savings from reducing pressure = 1% per 2 psi pressure reduction • Example • Reduce pressure setting of fully-loaded 100-hp compressor from 110 to 100 psig • (P2high/P1)0.286 = [(110 psig +14.7 psia) / 14.7 psia]0.286 = 1.84 • (P2low/P1)0.286 = [(100 psig +14.7 psia) / 14.7 psia]0.286 = 1.80 • Fraction savings = (1.84 – 1.80) / (1.84 – 1) = 5.2 % • Cost Savings = 100 hpx 5.2% / 90% x 0.75 kW/hp x 6,000 hr/yr x $0.10 /kWh = $2,582 /yr

  33. Reduce Pressure To Maximum End Use Plus Friction Loss

  34. Dry Air Efficiently

  35. Refrigerated and Desiccant Dryers • Refrigerated dryer: • Dries air by cooling • Cools to Tdew-point = 35 F • Uses 6 W/scfm • Desiccant dryer: • Dries air by passing through desiccant, then purging desiccant of water • Cools air to Tdew-point = -40 F to -100 F • Uses 16 to 30 W/scfm Desiccant dryers “should one be applied to portions of compressed air systems that require dew points below 35 F. Because desiccant dryers require a higher initial investment and higher operating costs, Kaeser strongly recommends using refrigerated dryers whenever practical.” Kaeser Regenerative Desiccan Dryers

  36. Desiccant Dryer Purging • Three types of purge • Compressed air purge • Uses 15% of compressed air for purging • Total is about 30 W/scfm • Heated compressed air purge • Uses 7% of compressed air for purging • Plus 7 W/scfm for heating • Total is about 22 W/scfm • Heater blower air purge • Uses 3 W/scfm for blower • Plus 13 W/scfm for heating • Total is about 16 W/scfm • Purge cycle can be timed or demand-controlled Source: www.aircompressors.com

  37. Use Refrigerated Rather than Desiccant Dryer • Example: • Replace desiccant dryer using compressed air purge with refrigerated dryer for 200 hp(840 scfm) compressor • Desiccant Power = 840 scfm x 15% / (4.2 scfm/hp x 90%) x 0.75 kW/hp x (1-0.50) = 12.5kW • Refrigerated Power = (840 scfm x 85% x 0.006 kW/scfm x (1-0.50) = 2.1kW • Cost Savings = (12.5 kW – 2.1kW) x 6,000 hr/yr x $0.10 /kWh = $6,215/yr

  38. Use Demand-Control Rather than Timed Purge • Summer air 4x wetter than winter air. • Timed purge set for peak (summer) conditions • Example • Switch from timed to demand-control purge and reduce purge by 50% on dryer for 200 hp (840 scfm) compressor • Timed-Purge Power = 840 scfm x 15% / (4.2 scfm/hp x 90%) x 0.75 kW/hp x (1-0.50) = 12.5 kW • Cost Saving = 12.5 kW x 50% x 6,000 hr/yr x $0.10 /kWh = $3,250 /yr .016 lbw/lba .004 lbw/lba

  39. Replace Timed-solenoid with No-loss Drains • Winter air holds 50% less water than summer air • Timers designed for peak conditions, where demand-based control matches actual conditions • Example • Replace 3/8-inch timed-solenoid drain that opens 3 seconds every 30 seconds with no-loss drain that eliminates <90% of air losses. • Flow Savings = 11.6 (scfm/lbf) x [3/8 (in)]2 x 115 (psia) x 10% x 90% = 16.9 scfm • Power Savings = 16.9 scfm/ (4.2 scfm/hp x 0.90) x 0.75 kW/hp x (1-0.50) = 1.68kW • Cost Savings = 1.68kW x 6,000 hr/yr x $0.10 /kWh = $1,005 /yr • 3/8-inch no-loss drains costs $600

  40. Optimize Compressor Cooling

  41. Compress Outdoor Air • Compressing cool dense air reduces compressor work: • Fraction Savings = (Thi - Tlow) / Thi • Fraction Savings = ~ 2% per 10 F • Example • Install PVC piping to duct outside air at 50 F to compressor rather than inside air at 80 F. • Fraction Savings = [(80 + 460) - (50 + 460)] / (80 + 460) = 5.9% • Cost Savings = 20 kW x 5.9% x 6,000 hr/yr x $0.10 /kWh = $706 /yr

  42. Direct Warm Air Into Plant During Winter • 75% of compressor input power lost as heat • Example • Add duct work to direct warm air into plant during winter for compressors drawing 105 kW if heating system operates 2,000 hours per year and is 80% efficient • Heat Load Savings = 105 kW x 75% x 3,413 Btu/kWh x 2,000 hours/year = 537 mmBtu/yr • Cost Savings = 537 mmBtu/year / 80% x $10 /mmBtu = $6,719/year

  43. Employ Efficient Compressor Control FP = FP0 + (1-FP0) FC and P = Prated FP

  44. Power Signatures fromModulation and Load/unload Control

  45. Savings From Switching To Efficient Control • FP = FP0 + (1-FP0) FC • Typical Intercepts • FP0bypass = 1.00 • FP0modulation = 0.70 • FP0load/unload = 0.50 • FP0 variable-speed = 0.10 • FP0on/off = 0.00 • Example • Switch 100-hp compressor at 50% capacity from modulation to variable-speed control. • FP (modulation) = 0.70 + (1 - 0.70) .50 = .85 • FP (variable-speed) = 0.10 + (1 - 0.10) .50 = .55 • Savings = 100 hp x (.85 - .55) / .90 x 0.75 kW/hp x 6,000 hr/yr x $0.10 /kWh = $15,000 /yr

  46. Savings Penalty for Inefficient Control • Consider savings from reducing fraction capacity (FC) • P1 = Prated x FP1 = Prated x [FP0+ (1-FP0) FC1] • P2= Prated x FP2 = Prated x [FP0 + (1-FP0) FC2] • Psave = P1 – P2 • Psave = Prated x [FP0 + (1-FP0) FC1] - Prated x [FP0 + (1-FP0) FC2] • Psave= Prated x (FC1 - FC2) x (1-FP0) • Psave= Unadjusted savings x (1-FP0) • Actual Savings = Unadjusted Savings x (1 – FP0) • Example • Calculate actual savings for reducing leaks by 100 scfm if compressor operates in modulation control. • Unadjusted savings = 100 scfm / (4.2 scfm/hp x 0.90) x 0.75 kW/hp x 6,000 hr/yr x $0.10 /kWh = $11,905 • Actual savings = $11,905 /yr x (1 – 0.70) = $3,571 /yr

  47. Modulation to Load/Unload with Auto-shutoff Reduced power 35% and saved $17,000 /yr

  48. Centrifugal Compressor Control

  49. Energy-Efficient Centrifugal Compressor Control • Minimize/eliminate by-pass using effective multi-compressor control • Operate compressor with throttling/unload control if available • Adjust throttling/surge pressure points to widen throttling range

  50. Throttling/Surge Pressure Set Points Narrow or Widen Throttling Band

More Related