An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 6300

  2. 6300 System Features • Interactive Digital Addressable Fire Detection and Alarm System. • Designed for Small and Medium Sized Installations such as Nursing Homes Hotels and Offices • Fully Conformant to EN54 Requirements • Recessed Option • Range of Finishes. • Networkable (Up to 32 Panels) • 1 , 2 and 4 Loop options. • 191 Devices Per Loop

  3. 6300 System Features • Controls and Displays. • Silence/Sound Alarms/Reset/Accept • 80 Character LCD Display • Twin Fire LEDs • 32 Zonal Fire LEDs • Full Fault Monitoring LEDs • Optional Low Noise Printer

  4. 6300 System Features

  5. 6300 Front display LCD display General fire LEDS Fire ZONE display Status LEDs Control buttons Thermal printer

  6. 6300 Status LEDs Fault - illuminates with a general fault. System fault - illuminated when the processor has failed. Alarm fault - problem with the internal alarm circuits. Fire link fault - problem with the fire station link Power-supply status - illuminated in a healthy condition (GREEN) Test - illuminates when the system is in engineers test mode. Pre-alarm - illuminates when a devices is approaching a fire condition Alarms disabled -sounders are isolated Fire link active -signal to the fire brigade active (if link fitted) Disablement - illuminates when a devices has been isolated. Fire link disabled - fire station link isolated

  7. System Features LCD in a quiescent condition Lower line User Message Upper line Current time & date System Normal 20/1/09 15:35:31 ASM - HUNGARY Liquid Crystal Display - The 80, large character liquid crystal display will under normal quiescent conditions display the current time and date with the option to also display a 40-character user’s message such as the site name or installation company. In an alarm or fault condition the LCD will display the device Loop, address and Zone number and up to 40 characters of user definable location text, programmable on site using Protec 6300/WinTEXT windows based software. LCD in a fire condition Upper line Zone, Loop and address number Lower line User definable Location text Fire 01 of 01 Zone 32 Loop 1 address 191 Building 2, Ground Flr, East Wing Rm 12

  8. 6300 System Features • Thermal Printer • 40 Character • On Demand Real Time Data for Fire and Fault Condition • Prints Device Number and Location Text • Prints Event Reports • Prints Device Configuration • Prints Programming Matrix • Prints List of Devices becoming contaminated. Thermal Printer Fire in Zone 32 31/7/00 22:50:20 Loop 1 Address 191 Building 2, Ground Flr, East Wing Rm 12 Typical fire print-out

  9. 6300 Fire LEDs General fire LEDs 32 Fire ZONE LEDs

  10. 6300 Control buttons Accept - the fault buzzer to be muted (not all events) Previous -allows previous events or menu options to be selected. Next -allows the next event or menu options to be selected. Menu - allows access to the menu options. Sound alarms - activates all sounders on the system Silence - Allows all sounders to be silenced following either a fire or sound alarms event. Reset - allows the system to be fully reset following a fire event.

  11. 6300 Standalone Maximum of 4 repeater / mimics from a Master 6300 6300 Master 6300 Repeater 6300 Mimic 6300 Repeater 6300 Repeater

  12. 6300 Network 2 Core network Max 32 x 6300 per Network 1 Km Max between Nodes Max Network distance NOT to exceed 8Km(5 miles)

  13. 6300 Network break Network break 3 & 4

  14. X300 Software X300 WIN TEXT - Free software to allow client to write their own device text files (PC Only). X300 Engineer - software charged, to allow engineer to write their own program and download to control panel DONGLE PROTECTED.

  15. Device Text Editor Device Text can be edited to suit the site layout A print out of the device text is available

  16. Matrix X300 Matrix - The system cause and effects can be configured using the X300 WINPROG matrix editor. Outputs can be configured as alarm or control O/Ps Selectable Sound settings Overview shows the cause and effect for the whole system. C&E program Matrix delay setting set via ‘Timeouts’ editor Misc settings - refer to next slide Group text to detail C&E areas X300 setting refer to slide

  17. Miscellaneous 24 non Latching Fire Devices and 24 latching non fire devices Pulse times for output groups Miscellaneous Keyswitch Inputs The walk test function allows access in User Menu

  18. X300 Button Fire Link Delay allows delays on all individual devices or groups of devices The Fire Link output can be programmed for all of the options listed Different languages are supported Network Input Filtering allows a panel to display all events from chosen network panels Check the panel overlay Sensitivity Settings can be changed for individual devices or groups of devices The internal charger is the S9000 EN54 but external chargers can be utilised.

  19. Device Editor Unique Serial Number Sensitivity settings are changeable. LOOP No Address No. Zone – Geographical Representation – up to 32 zones. Alt. display shows more options for the device. Input Group - 96 Output Group - 96 Reset Class resets the device to the default setting.

  20. 6400

  21. 6400 System Features • Distributed Network System. • Designed for Medium to Large sized buildings such as hotels, Offices, Universities and Hospital Sites. • EN54 Compliant • DCN (Display Control Node) • LPN (Loop Processing Node) • Distributed Loop and Sounder Wiring

  22. 6400 System Features • 6400 DCN • Accessed Via hinged Lockable Door • Main Fire Lamps • Quarter VGA Graphics LCD Display • Backlit Zonal display UP TO 100 Zones • Fault Lamps

  23. 6400 System Features • 6400 DCN • Sound Alarms, Silence, Accept and Reset Buttons • Access to Menu Keys • On demand Low Noise 40 Character Printer • Qwerty Key Board

  24. Location Text Location text displayed during fault & Fire

  25. Alarm text Alarm text displayed only for Fire

  26. 6400 System Features • 6400 LPN • Processes Loop Data • Network Communication • Implementation of Cause and Effects • Sounder Circuitry • Auxillary Changeover Contacts • 127 devices per loop either 2 Loop (2LPN) or 4 loop (4LPN) • Two Full Duplex RS232 Ports for Graphics and Programming 6400 LPN

  27. 6400 System Features & = 5400 DCN 5400 DCN / LPN 5400 LPN • 6400 DCN/LPN • Combining DCN and LPN in single Point Enclosure. • Combination gives fully functional system functions and controls in a stand alone panel. • DCN/LPN often used as Master Panel for a fully networked system

  28. RDN / LCD / Mimic The 6400 RCN, LCD and MIMIC all use the same Processor PCB

  29. Repeat Display Node • Menu / Select / Mute / Silence and Repeat Buttons • Optional Printer • Node on the Network • Can be Combined with LPN

  30. 6400 LCD Repeater • Listen Only Device • Menu / Silent / Mute Buttons • No System Controls • Not a Node on the Network but sits on Network. • Loop Powered version available.

  31. Mimic Repeater • Customised Illuminated Mimic Display • LEDS activated by appropriate zone • Node on Network • Customised Control Options

  32. 6400 Secure Network • Interconnects all Node Options • All nodes are accessible from any 6400/DCN location. • Wired as a loop. • Dual Channel Fault Tolerant RS 485 • No Single fault disables the system. • Can act as Stand Alone • Up to 99 Nodes on Network • Wired as Copper or Fibre Optic

  33. 6400 Secure Network 2 CORE RS485 NETWORK Single and Dual Break safety 99 NODES per NETWORK 1 KM Max

  34. Graphics • Windows Based • Large Sites – Full Display and Control. • Touch Screen option. • Zoom Levels • Event Logging System available RS232 1 x GRAPHICS PER DCN MAX 20 Mtrs

  35. 6400

  36. 6000 PLUS Sensors • Low Profile Design • Advanced Fire Sensing Technology • Electronic Sounders • High Intensity LED Warning Beacons • Speech Enhanced Talking Sounder • Semi Flush Option and Fast Fix Base. • All Incorporated in to the Sensor Head Temperature Optical Op/ht/co Op/Ht

  37. 6000 PLUS Sensors Base Options Fast Fix Recessed Base. Standard Base

  38. 6000 PLUS Sensors Recessed Fast Fix Bases Step 1 Wire base to diagram shown. Fit and commission sensor, or leave sensor commissioning until after false ceiling is fitted. Step 4 Rotate screw covers to reveal screws. Step 2 Pull sensor/base combination, or base only through ceiling tile hole. (121mm dia) Step 5 Tighten screws until resistance is felt, and clamps have engaged ceiling tile. Do not overtighten Step 3 Push trim onto base. Rotate clockwise to lock trim in position. Push base back through false ceiling so trim is flat to ceiling. Step 6 Rotate screw covers back to original position.

  39. Interactive Algo-Tec evaluates the data of each fire sensor and is able to learn from the information received. This may simply be to recognise that a sensor is becoming contaminated or in a dirty environment and to automatically increase the alarm threshold to compensate for the background levels (Threshold compensation). More complex Algo-Tec functions include the ability to discriminate between certain fire and non-fire conditions, filtering out certain environment stimuli, such as steam from a hotel bathroom, and increasing the sensitivity of a sensor (6000 plus OPHT) when an increase in temperature is detected. The net effect of the interaction between the sensors and the Algo-Tec decision making is enhanced performance, through immunity to false alarm and more responsive fire detection.

  40. 6000 Plus Sensors • Heat Sensor & Optical Sensor • Dual Technology High Performance • Multi Criteria High Performance Optical Smoke, Heat and CO Sensor • Independent Channel Control • Day/Night Operation • Protec Algo-TecTM 6000PLUS Protocol • Devices Display Address Number • Easy To Address • FASTTM Addressing • Reduced False Alarms • Electronic Sounder • High Intensity LED Beacon • Voice Enhanced ‘Talking’ Sounder with selectable msgs Optical Sensor

  41. 6000 Plus Sensors • Heat Sensor & Optical Sensor • Dual Technology High Performance • Multi Criteria High Performance Optical Smoke, Heat and CO Sensor • Independent Channel Control • Day/Night Operation • Protec Algo-TecTM 6000PLUS Protocol • Devices Display Address Number • Easy To Address • FASTTM Addressing • Reduced False Alarms • Electronic Sounder • High Intensity LED Beacon • Voice Enhanced ‘Talking’ Sounder with selectable msgs Temp Sensor

  42. 6000 Plus Sensors • Heat Sensor & Optical Sensor • Dual Technology High Performance • Multi Criteria High Performance Optical Smoke, Heat and CO Sensor • Independent Channel Control • Day/Night Operation • Protec Algo-TecTM 6000PLUS Protocol • Devices Display Address Number • Easy To Address • FASTTM Addressing • Reduced False Alarms • Electronic Sounder • High Intensity LED Beacon • Voice Enhanced ‘Talking’ Sounder with selectable msgs Op/Ht/Co Sensor

  43. 6000 Plus Sensors • Heat Sensor & Optical Sensor • Dual Technology High Performance • Multi Criteria High Performance Optical Smoke, Heat and CO Sensor • Independent Channel Control • Day/Night Operation • Protec Algo-TecTM 6000PLUS Protocol • Devices Display Address Number • Easy To Address • FASTTM Addressing • Reduced False Alarms • Electronic Sounder • High Intensity LED Beacon • Voice Enhanced ‘Talking’ Sounder with selectable msgs Op/Ht Sensor

  44. 6000 / Beam

  45. 6000 / SSR 2 Loop Powered Sounder (2 wire) No of addresses -1 address No of Cables - 2 cables Alarm Current - 5 mA Quiescent Current - 0.5 mA DB Output - 101 dB (@ 1m) Colour - RED or White

  46. 6000 / ZAI Connections 6000 Loop 6000 Loop Mains Supply Max 1 amp Load Max 20 x 3000 detectors 8k2 or 100uF EOL 10k EOL Alarm Circuit Detection Circuit

  47. 6000 / Micco Connections 6000 Loop 6000 Loop NO switch 47K EOL Volt free changeover contacts 240 VAC (5amp)

  48. Loop Test Unit • Compatible with all current Protec • 6000 series and 6000 plus Series devices • Enables rapid confirmation of correct • loop wiring • Allows verification of correct number • and type of loop devices • User may activate a single output at a time • Retrieves analogue values from devices • Drives 6000PLUS talking sounders • Robust construction • Easy to read display • Can be powered from mains (via supplied charger), or internal batteries

  49. Bar-Codes documentation