Comparison of circuit breaker stress related to the first pole to clear factor

Background. A circuit breaker experiences different stresses depending on the grounding condition of the networkTRV for the circuitbreaker depending on first,second or third clearing phase Necessary arcing time windowA comparison of the stresses is given. . . Not covered if tested for ungrounded condition.

Faraday
Download Presentation

Comparison of circuit breaker stress related to the first pole to clear factor

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


    1. Comparison of circuit breaker stress related to the first pole to clear factor Helmut Heiermeier 14. October 2007

    4. Conclusion If a test is performed at undgrounded condition Short arcing times are tested with higher TRV Medium arcing times are tested with lower TRV Long arcing times are not tested ? testing under ungrounded condition if the majority of the faults are grounded leaves some major stresses untested and lowers confidence