1 / 16

局部排氣導管設計

局部排氣導管設計. 單一氣罩範例. 例題. 具單一氣罩之局部排氣裝置 氣罩風量: 8.5 m 3 /min 氣罩壓損係數: F h = 0.85 氣罩至排氣機導管: 管壁摩擦因數: f = 0.024 長度: 11.6 m 搬運風速: 23 m/s 以上 含有一肘管( F e = 0.22 ) 排氣機至出口導管 長度: 2.4 m 直徑: 20 cm. 0. P t 0 = P v 0 = P s 0 = 0. P s 4 = 0. 2. 3. 4. 1. 2.4 m. 11.6 m. 計算方向. 計算方向.

wayne-kim
Download Presentation

局部排氣導管設計

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. 局部排氣導管設計 單一氣罩範例

  2. 例題 • 具單一氣罩之局部排氣裝置 • 氣罩風量:8.5 m3/min • 氣罩壓損係數:Fh = 0.85 • 氣罩至排氣機導管: • 管壁摩擦因數:f = 0.024 • 長度:11.6 m • 搬運風速:23 m/s 以上 • 含有一肘管(Fe = 0.22) • 排氣機至出口導管 • 長度:2.4 m • 直徑:20 cm

  3. 0 Pt0 = Pv0 = Ps0 = 0 Ps4 = 0 2 3 4 1 2.4 m 11.6 m 計算方向 計算方向 空氣密度r = 1.2 kg/m3 氣罩風量需求:Q = 8.5 m3/min 氣罩壓損係數:Fh = 0.85 肘管壓損係數:Fe = 0.22 排氣機前導管最低搬運風速:vmin = 23 m/s 排氣機後導管管徑:10 cm 導管摩擦損失因數 f = 0.024

  4. 0-1 • Q = (8.5 m3/min)(1 min/60 s) = 0.1417 m3/s • 導管截面積最大為:Amax = Q/vmin = (0.1417 m3/s)/(23 m/s) = 0.006159 m2 • 若導管截面積小於此值,導管內風速會小於規定的 23 m/s • 導管最大管徑dmax = (4Amax/p)1/2 = [(4)(0.006159 m2)/p]1/2 = 0.08856 m • Amax = pdmax2/4

  5. 0-1(續) • 若導管管徑只能使用 2、3、4、…cm:取管徑d1 = 8 cm = 0.08 m • 若以四捨五入取d1 = 9 cm > dmax,會使導管內風速小於規定的 23 m/s • 若導管管徑可以訂做(自由選取),則令d1 = dmax = 0.08856 m • 若管徑d1已事先給定,則無需上述步驟

  6. 0-1(續) • 以管徑d1 = 0.08 m 繼續以下計算: • 導管截面積:A1 = pd12/4 = p (0.08 m)2/4 = 0.005027 m2 • v1 = Q/A1 = (0.1417 m3/s)/(0.005027 m2) = 28.18 m/s > vmin = 23 m/s • Pv1 = rv12/2 = (1.2 kg m/s)(28.18 m/s)2/2 = 476.6 Pa • 在 20°C 時,若要求單位為 mmAq,則可使用Pv1 = (28.18/4.04)2 = 48.7 mmAq

  7. 0-1(續) 氣罩後方導管動壓 • 氣罩壓損:DPth = FhPv1 = (0.85)(476.6 Pa) = 405.1 Pa • 氣罩後方(點 1): • Pt1 = 0 – DPth = -405.1 Pa • Ps1 = Pt1 – Pv1 = -405.1 Pa – 476.6 Pa = -881.7 Pa • 或Ps1 = -(1 + Fh) Pv1 = (1 + 0.85)(476.6 Pa) = -881.7 Pa acceleration factor

  8. 1-2 • 導管壓損:f(L12/d1)Pv1 = (0.024)(11.6 m)/(0.08 m)(476.6 Pa) = 1659 Pa • 肘管壓損:FePv1 = (0.22)(476.6 Pa) = 104.9 Pa • 1-2 的總壓損DPt1-2 = 1659 Pa + 104.9 Pa = 1763 Pa • 通式:DPt1-2 = (fL12/d1 + SF)Pv1 =[(0.024)(11.6)/(0.08) + 0.22](476.6 Pa) = 1763 Pa = DPs1-2 導管上配件壓損係數總和 導管摩擦壓損係數 A1 = A2,v1 = v2,Pv1 = Pv2,DPt 1-2 = DPs1-2

  9. 1-2(續) • 排氣機入口(點 2): • Pv2 = Pv1 = 476.6 Pa • Pt2 = Pt1 – DPt1-2 = -405.1 Pa – 1763 Pa = -2168 Pa • Ps2 = Pt2 – Pv2 = -2168 Pa – 476.6 Pa = -2645 Pa • 或Ps2 = Ps1 – DPs1-2 = -881.7 Pa – 1763 Pa = -2645 Pa • 一氣喝成求Pt2的方法: • Pt2 = -(Fh + fL12/d1 + SF)Pv1 =-[0.85 + (0.024)(11.6)/(0.08) + 0.22](476.6 Pa) = -2645 Pa = DPs1-2

  10. 4-3 • 排氣機後方導管:由出口往前算 • 排氣機後方導管管徑已給定: • d3 = d4 = 10 cm = 0.1 m • A3 = A4 = pd42/4 = pd32/4 = p (0.1 m)2/4 = 0.007854 m2 • v3 = v4 = Q/A3 = Q/A4 = (0.1417 m3/s)/(0.007854 m2) = 18.04 m/s • Pv3 = Pv4 = rv32/2 = rv42/2 = (1.2 kg/m3)(18.04 m/s)2/2 = 195.2 Pa

  11. 4-3(續) • 出口(點 4) • Ps4 = 0(大氣) • Pt4 = Ps4 + Pv4 = 0 + 195.2 Pa = 195.2 Pa • 導管 3-4 壓損: • DPt3-4 = fL34/d3Pv3 = (0.024)(2.4 m)/(0.1 m)(195.2 Pa) = 112.4 Pa = DPs3-4 A3 = A4,v3 = v4,Pv3 = Pv4,DPt 3-4 = DPs3-4

  12. 4-3(續) • 排氣機出口(點 3) • Pt3 = Pt4 + DPt3-4 = 195.2 Pa + 112.4 Pa = 307.7 Pa • Ps3 = Pt3 – Pv3 = 307.3 Pa – 195.2 Pa = 112.4 Pa • 其實就是DPs3-4,因為Ps3 = Ps4 + DPs3-4 = 0 + DPs3-4

  13. Pv Pt FTP Ps FSP

  14. FTP 與 FSP • 排氣機全壓(FTP) = 排氣機出口全壓 – 排氣機入口全壓 = Pt3 – Pt2 = 307.7 Pa – (-2168 Pa) = 2476 Pa • 用來計算耗電量 • 排氣機靜壓(FSP): • = FTP – 排氣機出口動壓(Pt3 – Pt2 – Pv3) • = 排氣機出口靜壓 – 排氣機入口全壓(Ps3 –Pt2)= 112.4 Pa – (-2168 Pa) = 2281 Pa • 排氣機標準規格(可以提高多少壓力) FTP

  15. 排氣機耗電量 總效率 h P = (0.1417 m3/s)(2476 Pa)/0.4 = 877 W = 0.877 kW 每運轉一小時耗電 0.877 度

  16. 系統需求曲線 FSP ≈Q2 設計點: FSP = 2281 Pa @8.5 m3/min 排氣機風量