An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Petroleum Storage Tank Bureau

  2. Petroleum Storage Tank Bureau 20.5.6 NMAC Release Detection • Section 600 Deadlines for Release Detection for All Storage Tank Systems • Section 601 Requirements for Storage Tank Systems • Section 602 Requirements for Hazardous Substance Storage Tank Systems • Section 603 Methods of Release Detection for Tanks • Section 604 Methods of Release Detection for Piping • Section 605 Alternative Methods • Section 606 Record Keeping

  3. Petroleum Storage Tank Bureau 20.5.7 NMAC Release Reporting, Investigations, and Confirmation Detection • Section 700 Reporting of Spill or Release • Section 701 When Releases and Suspected Releases must be Reported • Section 702 Investigation of off-site impacts • Section 703 Release Confirmation Steps • Section 704 Reporting of Cleanup of Spills and Overfills

  4. Petroleum Storage Tank Bureau 20.5.8 NMAC Out-of-Service Systems and Closure • Section 800 Temporary Closure • Section 801 Permanent Closure and Changes in service • Section 802 Assessing the Site at Closure or Change in service • Section 803 Applicability to Previously Closed Storage Tank Systems • Section 804 Closure Records

  5. Petroleum Storage Tank Bureau 20.5.6 NMAC Part 6 - Release Detection Presented by Joe Godwin Stakeholders, 7/31/02

  6. Petroleum Storage Tank Bureau Section 600 - Deadlines • No changes for underground storage tank systems. • Existing USTs must have met requirements by 1998 Deadline • New USTs must meet requirements upon installation.

  7. Petroleum Storage Tank Bureau AST Systems Deadlines • Installed on or before June 30, 1991 or where date of installation is unknown shall be inspected and tested by one year from effective date of regulations. The testing will be to ascertain if the tank and piping are structurally sound and if a release is occurring. • If a release is suspected from the results of the tank testing the owner and operator will comply with 20.5.7 NMAC

  8. Petroleum Storage Tank Bureau AST Systems Deadlines • Owners and Operators will meet release detection requirements by July 1, 2004. • Regardless of age any aboveground system that is completely aboveground and can be visibly inspected does not have to be inspected and tested as required by D.1. • Owners and Operators will close any system by July 1, 2004 if they cannot apply a method of release detection that complies with Part 6.

  9. Petroleum Storage Tank Bureau Section 601 - Petroleum Tanks • All petroleum storage tank systems will be monitored monthly for releases by applicable method in 603. • No significant changes for UST systems from previous regulations. • AST systems can perform monthly inventory control in conjunction with testing in accordance with either API 653 or STI SP001-00.

  10. Petroleum Storage Tank Bureau Petroleum Piping • Requirements apply to all petroleum piping. • All piping that conveys regulated substances by pressure will be tightness tested annually unless the entire piping run is aboveground and can be visually inspected. • All pressurized piping will be equipped with an automatic line leak detector.

  11. Petroleum Storage Tank Bureau Petroleum Piping • All pressurized and suction double-walled piping whether aboveground or underground shall have a method of release detection that monitors the interstice of the piping. • No release detection on suction piping if it meets all of the standards listed in 601.B.2.

  12. Petroleum Storage Tank Bureau 20.5.6 NMAC Part 6 - Release Detection

  13. Petroleum Storage Tank Bureau Section 603 – METHODS OF RELEASE DETECTION FOR TANKS Presented by John Cochran Stakeholders, 7/31/02

  14. Petroleum Storage Tank Bureau There are three types of leak detection methods: • Internal • External • Interstitial

  15. Petroleum Storage Tank Bureau Leak Detection Methods: • Internal – monitoring the volume of liquid in the tank to try to detect a loss • Inventory control and tank tightness testing • Manual tank gauging • Automatic tank gauging • Statistical inventory reconciliation (SIR)

  16. Petroleum Storage Tank Bureau Leak Detection Methods: • 2. External – monitoring the environment outside the tank to detect evidence of a leak • Groundwater monitoring (UST only) • Vapor monitoring (UST only) • Visual inspection (ASTs only)

  17. Petroleum Storage Tank Bureau Leak Detection Methods: • 3. Interstitial – monitoring the space between the primary and secondary walls of a secondarily contained tank • Double-wall tanks • Secondary containment with interstitial monitor

  18. Petroleum Storage Tank Bureau Release Detection Requirements for Underground Storage Tanks have not changed!

  19. Petroleum Storage Tank Bureau RELEASE DETECTION FOR ABOVEGROUND STORAGE TANKS (ASTs)

  20. Petroleum Storage Tank Bureau Release Detection Methods for ASTs • Inventory Control and Tank Tightness Testing • Automatic Tank Gauge • Interstitial Monitoring • Visual Inspection

  21. Petroleum Storage Tank Bureau Release Detection Methods for ASTs • Inventory Control and Tank Tightness Testing • Tank tightness tests at 0.2 gallons-per-hour (gph) must be performed 10 years after installation and every 10 years thereafter

  22. Petroleum Storage Tank Bureau Release Detection Methods for ASTs • 2. Automatic Tank Gauge • Must be able to detect a 0.2 gph leak from any portion of the tank that routinely contains a regulated substance

  23. Petroleum Storage Tank Bureau Release Detection Methods for ASTs • 3. Interstitial Monitoring • Double wall tanks • Testing method complies with the requirements of the current edition of an industry code or standard approved in advance by the department

  24. Petroleum Storage Tank Bureau Release Detection Methods for ASTs • 3. Interstitial Monitoring • ASTs inside secondary containment • tanks manufactured or upgraded to contain a double-walled bottom which can be remotely monitored; or • tanks installed inside the secondary containment with an impervious barrier beneath the tanks and the interstice can be remotely monitored;

  25. Petroleum Storage Tank Bureau Release Detection Methods for ASTs • 3. Interstitial Monitoring • ASTs inside secondary containment • Groundwater, soil moisture, or rainfall will not render the testing or sampling method inoperative • Owners and operators conduct an annual test of the operation of the interstitial sensor in accordance with the manufacturer’s requirements

  26. Petroleum Storage Tank Bureau Release Detection Methods for ASTs • 4. Visual Inspection • May be used if all portions of the tank, including the tank bottom, are visible and readily accessible. • The tank(s) must be inspected monthly and the owner and operator must keep a log that includes the date, time, initials of the inspector, comments on the condition of each tank, and the results of each inspection

  27. Petroleum Storage Tank Bureau Section 604 - METHODS OF RELEASE DETECTION FOR PIPING: Presented by Joseph Romero Stakeholders, 7/31/02

  28. Petroleum Storage Tank Bureau Release Detection Methods for Piping • Automatic Line leak Detectors • Line Tightness Testing • Interstitial Monitoring • Visual Inspection

  29. Petroleum Storage Tank Bureau Release Detection Methods for Piping • 1. Automatic Line Leak Detectors • All pressurized piping will be equipped with an automatic line leak detector • 2. Line Tightness Test • Pressurized piping shall be tightness tested annually unless the entire piping run is aboveground and can be visually inspected

  30. Petroleum Storage Tank Bureau Release Detection Methods for Piping • 3. Interstitial monitoring • Owners and operators may use interstitial monitoring if they ensure that interstitial monitoring for double-wall piping, under pressure and under suction, complies with the current edition of an industry code or standard approved in advance in writing by the department, or with piping manufacturer’s requirements

  31. Petroleum Storage Tank Bureau Release Detection Methods for Piping • 4. Visual inspection • For above ground tanks, visual inspection may used for piping if all portions of the piping are visible and readily accessible, and are inspected monthly

  32. Petroleum Storage Tank Bureau Section 605 - ALTERNATIVE METHODS If owners and operators want to install another method of release detection equipment for tank or piping required in Section 601 through 604 of 20.5.6 NMAC in accordance with the current edition of an industry code or standard, owners and operators shall apply in writing to the department, shall provide supporting documentation, and shall not begin the installation unless and until the department approves the request in writing.

  33. Petroleum Storage Tank Bureau Section 606 - Record Keeping Presented by Patrick Moore Stakeholders, 7/31/02

  34. Petroleum Storage Tank Bureau Record Keeping Requirements • This Section Pertains To All Storage Tank System Owners and Operators ( AST and UST ) • If the owner and operator of a storage tank are separate persons, only one person is required to maintain the records required by this section; however, both parties are liable in the event of noncompliance

  35. Petroleum Storage Tank Bureau Record Keeping Requirements • All written performance claims pertaining to any release detection system – 5 years from date of installation • Results of sampling, testing, or monitoring – 1 year • Tank tightness testing – Until the next test is conducted • Written documentation of all calibration, maintenance, and repair of release detection equipment – 1 year after the servicing work is completed • Any schedules of required calibration and maintenance provided by manufacturer – 5 years from date of installation

  36. Petroleum Storage Tank Bureau 20.5.7 NMAC Part 7 - Release Reporting, Investigation, and Confirmation Detection

  37. Petroleum Storage Tank Bureau Reporting of a Release • Owners and Operators shall give notice of any known release, suspected release, or any spill, or any other emergency situation to PSTB within 24 hours.

  38. Petroleum Storage Tank Bureau Reporting of a Release • Owner and Operator shall provide the following information: • Owner and operator’s name, address, and telephone number • Facility agent in charge of the site: name, address, and telephone number • Site information (name, address, and location) • Source and cause of spill, release or suspected release

  39. Petroleum Storage Tank Bureau Reporting of a Release • Owner and Operator shall provide the following information: • Description of spill, release or suspected release • Estimated volume of spill, release or suspected release; • Any action taken to mitigate immediate damage from spill, release or suspected release

  40. Petroleum Storage Tank Bureau Reporting of a Release • Owners and Operators shall mail or deliver a written report and any investigation or follow-up action taken or to be taken to the department within 14 days.

  41. Petroleum Storage Tank Bureau WHEN RELEASES AND SUSPECTED RELEASES MUST BE REPORTED • The discovery of regulated substances in the surrounding area, ie: the presence of phase separated liquid and or vapors in soil, basements, utility lines, groundwater and drinking water, and nearby surface water; • Erratic behavior of product dispensing equipment; • Sudden loss of regulated substances; • Unexplained presence of water in the tank; • Presence of regulated substance in the interstitial space;

  42. Petroleum Storage Tank Bureau WHEN RELEASES AND SUSPECTED RELEASES MUST BE REPORTED • Anything other than a pass result from any release detection method; • Monitoring results from a release detection method that indicate a release may have occurred; • Sudden loss of regulated substances; • An indication from a field instrument.

  43. Petroleum Storage Tank Bureau INVESTIGATION OF OFF-SITE IMPACTS When required by the department, the owners and operators shall follow Release Confirmation Steps listed in Section 703 to determine if the storage tank system is the source of off-site impacts.

  44. Petroleum Storage Tank Bureau RELEASE CONFIRMATION STEPS Unless corrective action is initiated in accordance with Part 12 and 13, owners and operators shall immediately investigate and confirm all suspected releases of regulated substances within 14 days

  45. Petroleum Storage Tank Bureau RELEASE CONFIRMATION STEPS • Owners and operators shall use either system test, monitoring result check or site check or another procedure approved by the department: • System Test- Owners and Operator shall conduct appropriate tests approved by the department; eg: line tightness test, tank tightness test. • Site Check- investigation where contamination is most likely to be present. Sample types, sample locations and measurement methods, shall be approved by the department

  46. Petroleum Storage Tank Bureau REPORTING AND CLEANUP OF SPILLS AND OVERFILLS • Owners and operators shall contain and immediately clean up a spill or overfill and report to the department within 24 hours in the following cases: • Spill or overfill that results in a release that exceeds 25 gallons; • Spill or overfill that causes a sheen on nearby surface water; • Spill or overfill of a hazardous substance that results in a release that exceeds its reportable quantity;

  47. Petroleum Storage Tank Bureau REPORTING AND CLEANUP OF SPILLS AND OVERFILLS • Owners and operators shall contain and immediately clean up any spill or release that is less than 25 gallons and a spill of hazardous substances that is less than its reportable quantity. • Owners and operators shall notify the department if cleanup cannot be accomplished within 24 hours. • Arelease of hazardous substance in excess of its reportable quantity shall also be reported the National Response Center

  48. Petroleum Storage Tank Bureau 20.5.8 NMAC Part 8 – Out of Service Systems and Closure Presented by Keith Chavez and Tom Gray Stakeholders, 7/31/02

  49. Petroleum Storage Tank Bureau Storage Tank Temporary Closure Requirements: • Owners and Operators shall continue to operate: • Corrosion protection - 20NMAC5.5 • Any release detection method unless the tank is empty - 20NMAC5.6

  50. Petroleum Storage Tank Bureau Storage Tank Systems Temporarily Closed for 3 months or more • Requirements: • Maintain vents • Cap and secure lines & equipment • Protect the tank from flotation • Disconnect all piping from ASTs as soon as the tank is emptied