1 / 13

IBM PDU’s xSeries unique models

IBM PDU’s xSeries unique models. April 2005. UL derating. Underwriter Laboratories derates all PDUs in the US by 20%. Thus: - a 20amp PDU will only officially support 16amps - a 30amp PDU will only officially support 24amps - a 60amp PDU will only officially support 48 amps.

twila
Download Presentation

IBM PDU’s xSeries unique models

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. IBM PDU’s xSeries unique models April 2005

  2. UL derating Underwriter Laboratories derates all PDUs in the US by 20%. Thus: - a 20amp PDU will only officially support 16amps - a 30amp PDU will only officially support 24amps - a 60amp PDU will only officially support 48 amps

  3. IEC-320-C19 to C20, to connect to FE PDUs IEC-320-C19 to NEMA L5-20P, to connect to 110v Shipping power cords IEC-320-C19 to NEMA L6-20P, to connect to 208v Universal PDU SKU 32P1736 20amps, 110v or 208v 1760 watts (110v), 3328 watts (208v) derated ½ U (2 bolt together to fill 1U space) Ships with 3 different power cords 7x IEC-320-C13 connectors 1x IEC-320-C20 connector for the power cord

  4. 30 amp Front End PDU (FEPDU) SKU 32P1766 30amps, 208v 4992 watts (208v) derated ½ U (2 bolt together to fill 1U space) Ships with 1 power cords 3x IEC-320-C19 connectors 1x proprietary 63a connector for the power cord Supports 1 BladeCenter (requires 1 pair) Shipping power cords Proprietary to NEMA L6-30P, to connect to 208v

  5. 60 amp Front End PDU (FEPDU) SKU 32P1767 60amps, 208v 9984 watts (208v) derated ½ U (2 bolt together to fill 1U space) Ships with 1 power cords 3x IEC-320-C19 connectors 1x proprietary 63a connector for the power cord Shipping power cords Proprietary to IEC-309-2P+G, to connect to 208v

  6. 60 amp 3 phase Front End PDU (FEPDU) SKU N/A 60amps, 208v 14976 watts (208v) derated ½ U (2 bolt together to fill 1U space) Ships with 1 power cords 3x IEC-320-C19 connectors 1x proprietary 63a connector for the power cord Shipping power cords Proprietary to IEC-309-3P+G, to connect to 208v

  7. 60 amp Front End PDU (FEPDU) SKU 26K4256 60amps, 208v 9984 watts (208v) derated 1U Ships with 1 power cords 6 outets, 16amp breaker per outlet 6x IEC-320-C19 connectors 1x proprietary 63a connector for the power cord Supports 2 BladeCenters (requires 1 pair) Shipping power cords Proprietary to IEC-309-2P+G, to connect to 208v

  8. 60 amp 3 phase Front End PDU (FEPDU) SKU 26K4258 60amps, 208v 14976 watts (208v) derated 1U Ships with 1 power cords 6 outets, 16amp breaker per outlet 6x IEC-320-C19 connectors Hard wired power cord IEC-309-3P+G, to connect to 208v Supports 3 BladeCenters (requires 1 pair)

  9. 30 amp 1 phase Front End PDU (FEPDU) SKU 26K4246 30amps, 208v 4992 watts (208v) derated 1U Ships with 1 power cords 6 sets of 2 outlets, 16a breaker per pair 12x IEC-320-C13 connectors 1x proprietary 63a connector for the power cord Shipping power cords Proprietary to NEMA L6-30P, to connect to 208v

  10. 60 amp 1 phase FE PDU (FEPDU) SKU 26K4242 60amps, 208v 9984 watts (208v) derated 1U Ships with 1 power cords 6 sets of 2 outlets, 16a breaker per pair 12x IEC-320-C13 connectors 1x proprietary 63a connector for the power cord Shipping power cords Proprietary to IEC-309-2P+G, to connect to 208v

  11. 60 amp 3 phase Front End PDU (FEPDU) SKU 26K4244 60amps, 208v 14976 watts (208v) derated 1U Ships with 1 power cords 6 sets of 2 outlets, 16a breaker per pair 12x IEC-320-C13 connectors Hard wired power cord IEC-309-3P+G, to connect to 208v

  12. Notes on IEC-309 part numbers and how to read them Notes on the nomenclature:     The first position is the number of pins (3 in this case) Next is the amps (60 in this case)  Next is P for plug, R or C for recepticle (one is wall mount, one is on a whip) Next is the clock position of the recepticle ground pin (6 o'clock in this case) Next is W for watertight 360P6W IEC 309 2P+G (60a)

  13. IEC-309 common part numbers 60 amp, single phase 360R6W or 360C6W or 363R6W or 363C6W 32 amp, three phase 532R6W or 532C6W 60 amps, three phase 460R9W or 460C9W Notes on acquiring IEC-309 outlets Some customers complain of difficulties acquiring the outlets to connect these PDUs to. Here it is, nice and simple: Home Depot Sears There are other places as well, but if they can’t find another source, these two should be everywhere.

More Related