NRIC IV Network Reliability and Interoperability Council

NRIC IV Network Reliability and Interoperability Council. Washington, DC October 14, 1999 Rick Harrison Telcordia Technologies 732-699-6720 rick6@telcordia.com. NRIC IV Focus Group 3. Subcommittee 1 : Observations/Findings Power Continued: Focus on Year 6 7/1/98 - 6/30/99 Outages

Download Presentation

NRIC IV Network Reliability and Interoperability Council

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. NRIC IVNetwork Reliability and Interoperability Council Washington, DC October 14, 1999 Rick Harrison Telcordia Technologies 732-699-6720 rick6@telcordia.com

  2. NRIC IVFocus Group 3 Subcommittee 1 : Observations/Findings Power Continued: Focus on Year 6 7/1/98 - 6/30/99 Outages • 22 Outages • 12 - Root Cause Commercial/Backup Power Failure • 10 Root Cause Procedural • 8 Sub Cause Standby Generator • BPT Findings • 15 Outages with Best Practice implications

  3. NRIC IVFocus Group 3 Subcommittee 1 : Observations/Findings Power Continued: Focus on Year 6 7/1/98 - 6/30/99 Outages • BPT Findings Continued • PW69-71 & PR03 All relate to MOPs and Installation Guidelines • PW69 - Telcos should have documented installation guidelines • PW70 - Telcos should clearly communicate their installation guidelines to all involved parties • PW71 - On-site installation acceptance should include a quality review of conformance to the company's and vendor’s guidelines • PR03 - MOPs and Acceptance/Verification Check-off Sheets for Hardware and Software Growth/Change Activities … • All of the above were rated highly effective, implemented and low cost to implement

  4. NRIC IVFocus Group 3 Subcommittee 1 : Observations/Findings Power Continued: Focus on Year 6 7/1/98 - 6/30/99 Outages • BPT Findings Continued • Six remaining Outages • 1- Under-engineered for load • 1- Lightning • 4- Engine/hardware failure • 3- multiple failures • 1 - Remote location in the mountains, bad weather forced back helicopter and SnowCat trip was over 4 hours. • Two new Best Practices identified related to Low Voltage Disconnect and Alarm

  5. NRIC IVFocus Group 3 Subcommittee 1 : Observations/Findings Continued • Essential Services • ECOMM of NRCII had 33 recommendations which posed many options and alternatives to improve reliability • Many of the above recommendations were complementary and Supplementary • Survey Data indicated confusion regarding implementation responses

  6. NRIC IVFocus Group 3 Subcommittee 1 : Observations/Findings Continued • Essential Services • SC1 analysis resulted in a complete revamping of the Essential Services Best Practices • Deleted redundant BPs • Deleted “Not Best” • Combined related options and alternatives that supported the same goals and objectives • ES01 + ES02/ES01 + ES03 = ES04

  7. NRIC IVFocus Group 3 ES01 + ES02/ES01 + ES03 = ES04 • ES01- Diverse Interoffice Transport Facilities • ES02 - Diverse Interoffice Transport Facilities with Standby Protection (Option of ES01) • ES03 - Diverse Interoffice Transport Facilities Using DCS (Option of ES01) • ES04 - Fiber Ring Topologies for 911 Circuits (Accomplishes the goals of ES01,02&03)

  8. NRIC IVFocus Group 3 • Subcommittee 1 : Observations/Findings Continued • Essential Services • 33 Best Practices Evaluated • 8 Deleted • 7 combined with others • 18 Best Practices

  9. NRIC IVFocus Group 3 • Subcommittee 1 : Observations/Findings Continued • Supplier Best Practices • SP05 Human factors represents a new paradigm for vendors. There will be increased “emphasis” due to the Procedural. Errors Team Report. • SP12 Establish Core Team to plan, test and evaluate change - Service Provider initiated BP that suppliers should participate in. Not a Supplier BP Delete (See PR14) • Add PR04 Information Sharing Guidelines - as SP12 • Survey reflects continued high implementation • Confirmed broad industry applicability beyond traditional Telcom suppliers • Combined categories of DCS, Switch and Signaling into 1 Network element category

  10. NRIC IVFocus Group 3 Next Steps July -A Best Practice by Best Practice review and analysis of the survey responses COMPLETE -Review NRSC Facilities Solution Team Report for Best Practice implications ONGOING August -Complete survey analysis and gain consensus around final recommendations COMPLETE November -Draft 1 of final report ( deferred due to renewed focus on Power) December -Complete final report