TESTING GROUNDING SYSTEMS PowerPoint PPT Presentation


  • 837 Views
  • Uploaded on
  • Presentation posted in: General

TESTING GROUNDING SYSTEMS. Enhanced by: Roy W. Milam Electrical Engineer/Instructor National Mine Health and Safety Academy Beckley, West Virginia. Originally Developed by: RONALD J. RENOWDEN - CMSP Denver Field Office Supervisor, MNM MSHA Rocky Mountain District Denver, Colorado.

Download Presentation

TESTING GROUNDING SYSTEMS

An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -

Presentation Transcript


Testing grounding systems l.jpg

TESTING GROUNDING SYSTEMS

Enhanced by:

Roy W. Milam

Electrical Engineer/Instructor

National Mine Health and Safety Academy

Beckley, West Virginia

Originally Developed by:

RONALD J. RENOWDEN - CMSP

Denver Field Office Supervisor, MNM MSHA

Rocky Mountain District

Denver, Colorado


Testing grounding systems2 l.jpg

TESTING GROUNDING SYSTEMS

30 CFR §56/57.12028

As required by:


56 57 12028 the reg l.jpg

56/57.12028 the REG.

“Continuity and resistance of grounding systems shall be tested immediately after installation, repair, and modification; and annually thereafter. A record of the resistance measured during the most recent test shall be made available on request by the Secretary or his duly authorized representative.”


Why do we test l.jpg

WHY DO WE TEST ?

Ensure that continuity & resistance tests are conducted on a specific schedule (at least annually)

Alert mine operators if there is a problem in the grounding system

Problem may not allow the circuit protective devices to quickly operate when faults occur


Why do we test5 l.jpg

WHY DO WE TEST?

With exception of fixed installations - Numerous fatalities and injuries have occurred due to HIGH resistance or LACK of continuity in equipmentgrounding systems

Proper testing and maintenance of grounding systems can prevent electrical accidents

This all sounds so good that we made it the policy regarding 12028.


Slide6 l.jpg

56/57.12028 the POLICY

The intent of this standard is to ensure that continuity and resistance tests of grounding systems are conducted on a specific schedule. These tests will alert the mine operator if a problem exists in the grounding system which may not allow the circuit protective devices to quickly operate when faults occur. With the exception of fixed installations, numerous fatalities and injuries have occurred due to high resistance or lack of continuity in equipment grounding systems. These accidents could have been prevented by proper testing and maintenance of grounding systems.


Slide7 l.jpg

  • Grounding systems typically include the following:

    • 1.equipment grounding conductors - the conductors used to connect the metal frames or enclosures of electrical equipment to the grounding electrode conductor;

    • 2.grounding electrode conductors

    • - the conductors connecting the grounding electrode to the equipment grounding conductor; and

    • 3.grounding electrodes

    • - usually driven rods connected to each other by suitable means, buried metal, or other effective methods located at the source, to provide a low resistance earth connection.

P

O

L

I

C

Y


Slide8 l.jpg

  • Operators shall conduct the following tests:

    • 1.equipment grounding conductors - continuity and resistance must be tested immediately after installation, repair, or modification, and annually if conductors are subjected to vibration, flexing or corrosive environments;

    • 2.grounding electrode conductors - continuity and resistance must be tested immediately after installation, repair, or modification, and annually if conductors are subjected to vibration, flexing or corrosive environments; and

    • 3.grounding electrodes - resistance must be tested immediately after installation, repair, or modification, and annually thereafter.

P

O

L

I

C

Y


Slide9 l.jpg

56/57.12028 the POLICY

Conductors in fixed installations, such as rigid conduit, armored cable, raceways, cable trays, etc., that are not subjected to vibration, flexing or corrosive environments may be examined annually by visual observation to check for damage in lieu of the annual resistance test. When operators elect to conduct this visual examination as a method of compliance with 30 CFR56/57.12028, MSHA will require that a record be maintained of the most recent annual visual examination.


Slide10 l.jpg

56/57.12028 the POLICY

  • Grounding conductors in trailing cables, power cables, and cords that supply power to tools and portable or mobile equipment must be tested as prescribed in the regulation. This requirement does not apply to double insulated tools or circuits protected by ground-fault-circuit interrupters that trip at 5 milli-amperes or less.


Slide11 l.jpg

56/57.12028 the POLICY

Testing of equipment grounding conductors and grounding electrode conductors is not required if a fail-safe ground wire monitor is used to continuously monitor the grounding circuit and which will cause the circuit protective devices to operate when the grounding conductor continuity is broken.


Slide12 l.jpg

56/57.12028 the POLICY

A record of the most recent resistance tests conducted must be kept and made available to the Secretary or his authorized representative upon request. When a record of testing is required by the standard, MSHA intends that the test results be recorded in resistance value in ohms.

That’s all the policy! But what does it all mean ?


Typical grounding system has three parts l.jpg

TYPICAL GROUNDING SYSTEMhas three parts

EQUIPMENT GROUNDING CONDUCTORS

(the most important part!!!)

Grounding Electrode Conductors

Grounding Electrodes


Equipment grounding conductor l.jpg

EQUIPMENT GROUNDING CONDUCTOR

The conductors used to connect the metal frames or enclosures of electrical equipment to the grounding electrode conductor

Life Wire; Life Line

Most important electrical safety item in the electrical system

People protector


Slide15 l.jpg

Equipment Grounding Conductors

GROUNDING BUS maybe in MCC

Motor 1

Motor 4

Motor 2

Motor 3


Grounding electrode conductor l.jpg

GROUNDING ELECTRODE CONDUCTOR

Conductor that connects the grounding electrode and the transformer to the equipment grounding conductor

TRANSFORMER

Main Ground Bus

maybe in the MCC

Earth

Grounding

Electrode


Grounding electrodes l.jpg

GROUNDING ELECTRODES

Usually driven rods connected to each other by suitable means, buried metal plates, or any other effective methods located at the power source to provide a low resistance earth connection.

What is actually in contact with Earth.

Grid

Rod


Equipment grounding conductors test for continuity and resistance l.jpg

EQUIPMENT GROUNDING CONDUCTORSTest for Continuity andResistance

Immediately after -

INSTALLATION,

REPAIR, OR

MODIFICATION, AND

ANNUALLY, IF conductors are subjected to

VIBRATION

FLEXING

CORROSIVE ENVIRONMENTS


Grounding electrode conductor test for continuity and resistance l.jpg

GROUNDING ELECTRODE CONDUCTORTest for Continuity and Resistance

Immediately after -

INSTALLATION,

REPAIR, OR

MODIFICATION, AND

ANNUALLY, IF conductors are subjected to

VIBRATION

FLEXING

CORROSIVE ENVIRONMENTS


Grounding electrodes testing l.jpg

GROUNDING ELECTRODESTesting

Test for Resistance (Earth)

Immediately after -

INSTALLATION,

REPAIR, OR

MODIFICATION, AND

ANNUALLY thereafter.


Are there exceptions l.jpg

Are there EXCEPTIONS?

YES !!!

  • In lieu of doing annual resistance tests, the Groundsmay be examined annually by visual observation to check for damage…..

  • BUT ONLY IF:

  • The conductors are in fixed locations such as;

    • RIGID CONDUIT

    • ARMORED CABLE

    • RACEWAYS

    • CABLE TRAYS, ETC (there’s more)


More exceptions l.jpg

MORE EXCEPTIONS

These FIXED LOCATIONS

MUST NOTbeSUBJECTED TO:

Vibration

FLEXING

CORROSIVES


Slide23 l.jpg

HOW MUCH IS TOO MUCH ?

FLEXING

VIBRATION

CORROSIVES


Slide24 l.jpg

HOW MUCH IS TOO MUCH ?

The inspector makes the final determination concerning areas acceptable to visual examinations


If visual exams are conducted l.jpg

IFVISUALEXAMS ARE CONDUCTED

MSHA policy requires that a WRITTENRECORD be maintained of the most recent ANNUALVISUALEXAMINATION, can be electronic


Equipment grounding conductors in l.jpg

EQUIPMENT GROUNDING CONDUCTORS IN:

Trailing cables

Power cables

Cords supplying power to tools

Cords and cables supplying power to portable or mobile equipment

MUST BE TESTED AS PRESCRIBED IN THE REGULATION


When is testing not required l.jpg

When Is Testing NOT Required?

IF a fail-safe ground wire monitor is used. The monitor will cause the circuit protective device to open when the grounding conductor continuityis broken. It continuously monitors the continuity of the grounding conductor.

Double insulated tools are used. There is no grounding conductor to test.

If the circuit used incorporates a GFCI that trips at 5 milli-amps or LESS. There are 110v and 220v devices now available.


Records l.jpg

RECORDS

RESISTANCE VALUES IN OHMS

Most recent tests

Must be available for review by MSHA upon request

No specific format required

Be legible

Visual exam records


A little advice l.jpg

A little ADVICE ?

Should have electrical knowledge

Know how to test and use the instrument/PPE

Know what kind of electrical system

Check circuit protective device vs. Ohms test

Check with power off

Proper size ground wire

Never let metal framework or earth be the primary grounding conductor

Never use peg grounding


National electrical code l.jpg

NATIONAL ELECTRICAL CODE

Section 250-51-EFFECTIVE GROUNDING PATH: The path to ground from circuits, equipment, and metal enclosures for conductors shall:

Be permanent and electrically continuous

Have capacity to conduct safely any fault current likely to be imposed on it, and

Have sufficient low impedance to limit the voltage to ground and to facilitate the operation of the circuit protective devices.

The earth SHALL NOT be used as the sole equipment grounding conductor


Slide31 l.jpg

OK, now that the operator has tested his grounding circuit and recorded the results, what do we do with them?

In other words……


How do you know if the ground wire resistance is okay l.jpg

How do you know if the ground wire resistance is okay?

  • Can apply good old OHM’S LAW:

    • E = IRE = VOLTSI = AMPS (current)R = RESISTANCE (ohms)EI =R

E

I

R


But first l.jpg

BUT …..FIRST !

  • Remember OHM’S LAW ! ( E = IR )

  • Circuits are protected by fuses/breakers against SHORT CIRCUITS AND GROUND FAULTS

  • IF GF occurs, we want the fuse/breaker to clear ASAP!

  • Question? Where does the current go when a ground fault occurs?

  • GROUNDING CONDUCTOR carries the fault current back to the SOURCE (current does not return to earth, but sometimes travels thru it).

  • FAULT CURRENT takes path of LEAST resistance?


Continued l.jpg

CONTINUED

  • IF ground wire is missing or high resistance, current will flow in dangerous places to return to the source.

  • TOUCH AND STEP POTENTIALS MAY EXIST ON THE FRAMES OF EQUIPMENT AND ON THE EARTH

  • HAZARDOUS!!!!! : SHOCK, BURNS, ELECTROCUTION……..DEATH


Example l.jpg

EXAMPLE:

  • The operator’s record of resistance testing (in OHMS) shows the following:

  • Crusher motor = 1 ohm

  • Screen Deck = .5 ohm

  • Stacker main motor = 1.5 ohm

  • Conveyor 1 = 1 ohm


Example what s next l.jpg

Example:What’s Next ?

  • Need: Circuit/System VOLTAGE:

    • Motors supplied with 3 phase, 460 volt AC

    • Grounded WYE Service; Ø-Ø=460v; Ø-grd=265v

  • Need: Fuse/Circuit Breaker Size (for each)

    • 100hp, 125amps, 3-fuses @ 300amps each (crusher motor)

    • 40hp, 52amps, 3-fuses @ 100amps each (screen)

    • 25hp, 34amps, 70 amp breaker(stacker)

    • 10hp, 14amps, 30 amp breaker (conveyor 1)


Grounded wye l.jpg

GROUNDED WYE

  • Grounded WYE Service; 460 V, 3-PHASEØA-ØB=460v; ØA-grd=265VØA-ØC=460v; ØB-grd=265VØB-ØC=460v; ØC-grd=265V

O A

B

A

O B

C

O C

Ground

Ground


How good is the equipment grounding l.jpg

How good is the equipment grounding?

  • CONVEYOR 1: 1ohm, Ø-grd=265v.

    • How much FC will flow if GF at motor frame?

    • To find current (ohms law) I= E/R.265vI = =265 amp FC; On 30 amp 1ohm breaker

  • 265a.(FC)/30a(bkr) = 8.83...What’s this mean?

  • Breaker will TRIP almost instantaneous level ASAP

  • GOOD GROUNDING!


Let s check another l.jpg

LET’S CHECK ANOTHER !

  • SCREEN:.5 ohms,Ø-grd=265v265vI = =530 ampFC; On 100 amp .5ohm fuses

  • 530a.(FC)/100a.(fu) = 5.30...What’s this mean?

  • Fuse will not TRIP near instantaneous level (ASAP)

  • GOOD GROUNDING ?Questionable! Review trip curve chart for fuse to find trip time….

  • ADVICE: Check connections; loose, dirty, wire size? CORRECT/ REPAIR! Screens- flexing and vibration!


Let s check another40 l.jpg

LET’S CHECK ANOTHER !

  • CRUSHER: 1 ohm,Ø-grd=265v265vI = =265 ampFC; 300 amp fuses 1ohm

  • 265a.(FC)/300a.(fu) = .88 ...What’s this mean?

  • Fuse will not BLOW (must see at least 125% to begin)

  • DANGEROUSGROUNDINGUNACCEPTABLE!

  • ADVICE: Check connections; loose, dirty, wire size? CORRECT & REPAIR!Crushers - flexing and vibration


Slide41 l.jpg

Let’s make a small change!!!

CRUSHER: 1 ohm,Ø-grd=265v, but this time we’re going to use a 100 Amp, Magnetic Trip Circuit Breaker with a trip range of 150-480 amps, set on LOW, as protection.

265v

I = =265 amp FC; CB set 150 Amps

1ohm

  • 265a.(FC)/150a.(Inst.) = 1.77 ...What’s this mean?

  • Breaker will TRIP instantaneously.

  • GOOD GROUNDING!


Corner grounded delta l.jpg

Corner Grounded Delta

  • Corner Grounded Delta Service; 460 V, 3-PHASEØA-ØB=460v; ØA-grd=0VØA-ØC=460v; ØB-grd=460VØB-ØC=460v; ØC-grd=460V

O A

B

O B

C

O C

A

Ground


Corner grounded delta43 l.jpg

Corner Grounded Delta

  • CONVEYOR 1: 1ohm, Ø-grd=480v.

    • How much FC will flow if GF at motor frame?

    • To find current (ohms law) I= E/R. 480vI = =480 ampFC; On 30 amp breaker 1ohm

  • 480a.(FC)/30a(bkr) = 16.0...What’s this mean?

  • Breaker will TRIP at instantaneous level ASAP

  • GOOD GROUNDING !


Corner grounded delta44 l.jpg

Corner Grounded Delta

  • SCREEN:.5 ohms,Ø-grd=480v480v

    I = .5ohm =960 ampFC; On 100 amp fuses

  • 960a.(FC)/100a.(fu) = 9.60...What’s this mean?

  • Fuse will TRIP near instantaneous level (ASAP)

  • GOOD GROUNDING !


Corner grounded delta45 l.jpg

Corner Grounded Delta

  • CRUSHER: 1 ohm,Ø-grd=480v480vI = =480 ampFC; 300 amp fuses 1ohm

  • 480a.(FC)/300a.(fu) = 1.6 ...What’s this mean?

  • Fuse will start heating up. (must see at least 125% to begin) Will blow on very long delay.

  • DANGEROUS GROUNDINGUNACCEPTABLE!

  • ADVICE: Check connections; loose, dirty, wire size? CORRECT & REPAIR!Crushers - flexing and vibration


Floating or ungrounded systems l.jpg

FLOATING or UNGROUNDED SYSTEMS

BE AWARE!

HAZARDOUS- IF NOT MONITORED FOR GROUNDS AND MAINTAINED

ELECTRICAL SHOCK

THERMAL ARC FLASH BURNS

ELECTROCUTION

FIRES


Slide47 l.jpg

Now let’s look at some of the test instruments that can be used to test the grounding system


Slide48 l.jpg

Instruments used to test the grounding electrode


Slide49 l.jpg

This is a Biddle Earth Tester that is battery powered. It uses 6 “C” cells. It is used to test the grounding electrode resistance.


Slide50 l.jpg

This a type of Biddle Earth Tester that is battery powered. It is powered by 4 “C” cells. It is used to test the grounding electrode resistance.

Measuring the resistance of the equipment grounding conductor for this piece of equipment.


Slide51 l.jpg

This is a Biddle Earth Tester that is used to test the resistance of the grounding electrode. It is powered by the use of the hand crank on the side of the device.


Slide52 l.jpg

This is the Field Kit that is used with an Earth Tester to measure the resistance of the grounding electrode. It contains 2 metal stakes, and 3 conductors of various lengths.


Slide53 l.jpg

Set-Up for Testing Grounding Electrode Resistance

C1 P1 G P2 C2

Earth

Test Rods

Grounding Electrode


Slide54 l.jpg

This person is driving a test rod to be used while testing the grounding electrode resistance.


Slide55 l.jpg

This is the method used when testing the grounding electrode resistance with a Biddle Earth Tester.


Slide56 l.jpg

The results obtained during the testing of the grounding electrode resistance are plotted on a graph. The actual resistance of the electrode is the flat part of the graph.


Slide57 l.jpg

Another method of testing the resistance of the grounding electrode is using a voltage source, such as a vehicle battery, a voltmeter and an ammeter. We do not recommend this method as it can be extremely dangerous.


Slide58 l.jpg

This is one possible set-up for testing the grounding electrode resistance.


Slide59 l.jpg

This is the method used when testing the grounding electrode resistance with a Biddle Earth Tester.


Slide60 l.jpg

Use OHM’S LAW to calculate the resistance values your tests found.

R=E/I


Slide61 l.jpg

The results obtained during the testing of the grounding electrode resistance are plotted on a graph. The actual resistance of the electrode is the flat part of the graph.


Slide62 l.jpg

This is the ECOS Pow-R-Mate Tester. It is used to test the resistance and impedance of the grounding electrode. It is both battery powered and plug-and-cord connected.


Slide63 l.jpg

This is a Biddle Insulation Tester that is used to test the insulation value of conductors, motors, transformers, and cables. It is powered by the hand crank on the side of the device. This device should not be used to test the grounding electrode nor the equipment grounding conductors.


Slide64 l.jpg

Instruments used to test the grounding electrode conductor and the equipment grounding conductors


Slide65 l.jpg

This is a Fluke Graphics Multi-Meter which can be used to measure the resistance of the equipment grounding conductors.


Slide66 l.jpg

This is a Fluke Multi-Meter which can be used to measure the resistance of the equipment grounding conductors.


Slide67 l.jpg

This is a Simpson Multi-Meter which can be used to measure the resistance of the equipment grounding conductors. It is reading an open conductor now.


Slide68 l.jpg

This is a Simpson Multi-Meter, with test leads attached, which can be used to measure the resistance of the equipment grounding conductors. It is reading an open conductor now.


Slide69 l.jpg

This is a Simpson Multi-Meter, with test leads attached, which can be used to measure the resistance of the equipment grounding conductors. It is reading Zero ohms resistance as the test leads are contacting each other. The meter is being zeroed.