自然接地体和人工接地体

Loading in 2 Seconds...

play fullscreen
1 / 3

自然接地体和人工接地体 - PowerPoint PPT Presentation


  • 59 Views
  • Uploaded on

自然接地体和人工接地体. 一、自然接地体和人工接地体.

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about ' 自然接地体和人工接地体 ' - raphael-delacruz


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
slide2

一、自然接地体和人工接地体

接地装置是接地体(极)和接地线的总称。运行中电气设备的接地装置应当始终保持良好状态。自然接地体是用于其他目的、且与土壤保持紧密接触的金属导体。例如,埋设在地下的金属管道(有可燃或爆炸性介质的管道除外)、金属井管,与大地有可靠连接的建筑物的金属结构、水工构筑物及类似构筑物的金属管、桩等自然导体均可用作自然接地体。利用自然接地体不但可以节省钢材和施工费用,还可以降低接地电阻,并能等化地面及设备问的电位。如果有条件,应当优先利用自然接地体。当自然接地体的接地电阻符合要求时,可不敷设人工接地体(发电厂和变电所除外)。在利用自然接地体的情况下,应考虑到自然接地体拆装或检修而被断开时,断口处出现的电位差及接地电阻发生变化的可能性。自然接地体至少应有两根导体在不同地点与接地网相连(线路杆塔除外)。利用自来水管及电缆的铅、铝铠皮作接地体时,必须取得主管部门同意,以便施工和检修时互相配合。

slide3

人工接地体可采用钢管、角钢、圆钢或废钢铁等材料制成。人工接地体宜采用垂人工接地体可采用钢管、角钢、圆钢或废钢铁等材料制成。人工接地体宜采用垂

直埋设,多岩石地区可采用水平埋设。垂直埋设的接地体可采用直径为40~50

mm的钢管或40 mm×40 mm×4 mm至50 mm×50 mm×5 mm的角钢,可以

成排布置,也可以作环形布置。水平埋设的接地体可采用40 rnm×4 mm的扁钢

或直径为16 H1rn的圆钢,多呈放射形布置,也可成排布置或环形布置。

电力线路杆塔接地体引出线应镀锌,截面积不得小于50 mm 。