Palo Verde Hub Risk Assessment Study for PV Hub-TS5 and TS5-RY 500kV 4th BTA Presentation

June 6, 2006. 4th BTA. 2. PV Hub to TS5 500kV line. 2008 Heavy Summer power flow case w/ Hassayampa-Pinal West-Santa Rosa 500kV in-serviceSome load shedding is still requiredAdd the TS5 500kV line connected to ArlingtonNo load shedding needed. June 6, 2006. 4th BTA. 3. TS5 to Raceway 500kV line.

radwan
Download Presentation

Palo Verde Hub Risk Assessment Study for PV Hub-TS5 and TS5-RY 500kV 4th BTA Presentation

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


    1. Palo Verde Hub Risk Assessment Study for PV Hub-TS5 and TS5-RY 500kV 4th BTA Presentation Bob Smith Manager Transmission Planning June 6, 2006

    2. June 6, 2006 4th BTA 2 PV Hub to TS5 500kV line 2008 Heavy Summer power flow case w/ Hassayampa-Pinal West-Santa Rosa 500kV in-service Some load shedding is still required Add the TS5 500kV line connected to Arlington No load shedding needed

    3. June 6, 2006 4th BTA 3 TS5 to Raceway 500kV line 2014 Heavy Summer power flow case w/ Santa Rosa-Browning 500kV, Harquahala-Devers 500kV, Harquahala Junction-TS5 500kV, and Raceway(TS9)-Pinnacle Peak 500kV in-service No load shedding is needed Add the TS5-Raceway(TS9) 500kV line No load shedding needed nor did it degrade the system’s stability