An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. FRR Request for ApprovalBAL-012-WECC-2-CR W. Shannon Black Manager, Business Practices and Standards Processes June 2009 Operating Committee, SLC

  2. FRRDT Criterion is Complete Solicited / Answered Comments Three times Final Drafting April 17, 2009 Communicated to the OC 30-days notice May 22, 2009 http://www.wecc.biz/documents/2009/Standards/FRR/OC/OC%20notification%20letter%20for%20FRR%20Regional%20Criterion%20Vote.pdf Presented for your approval

  3. Majority Vote The Process requires a majority vote of the Team to move the criterion to the OC. 15 member team 9 = “Yes” 3 = “No” 1 = “Abstain” 2= “No Response”

  4. Overview Proposed Criteria

  5. What it’s not… • Not a standard. • It is a criteria. • Not a replacement for spinning reserves • Reserve standards and criteria stay intact • BAL-002-WECC-1 • BAL-STD-002-0 • Not a mandate to change governor settings • Outside the stated scope of the Request

  6. What it is… A Measurement Criteria

  7. How does it work? • Resources • Check the filing on the WECC Web • Over 100 pages of studies to support the direction and conclusions drawn by the drafting team. • http://www.wecc.biz/index.php?module=pnForum&func=viewtopic&topic=1005 • Over 500 Web hits in the last few weeks

  8. Where Did We Start? Keep the lights on Prevent triggering Under Frequency Load Shedding Some trigger as early 59.5 Hz Assuming the worst Two largest generators tripped at the same time at the same plant About 2800 MW of gen / NERC Category C event (AKA: Primary Frequency Response Amount) Load was at its lowest 80 GW

  9. Where Did We Start? If two of the three generators at Palo Verde dropped off line at the same time… On the day with the lightest reasonable load… What would we have to do to keep the lights on?

  10. What’s in it? • Modeled the data • Showed two basic responses • Primary Response • (AKA: Point C) • Zero to 30 seconds • Secondary Response • (AKA: Point B) • 31 seconds to 15 minutes

  11. A Question of Magnitude What should we measure in the Primary Response? “Plethora” of minor deviations each year The benefit of measuring and responding was outweighed by the burden “About 10” annually lower than 59.85 Hz Reasonable balance between benefit/burden Burden is light Significant enough to be a good indicator

  12. A Question of Magnitude Frequency Response Measurement Event Trigger point Set at 59.85 Hz and below Measure response for two periods Primary 0 – 30 seconds Secondary 31 seconds through 15 minutes or 59.9 which ever comes first

  13. What happens when an event occurs? RC Notes the excursion Within five business days Tells the BAs or RSGs “Point A” (When the event begins) Total WECC gen on-line The BAs/RSGs “Allocation Ratio” Needed so the BA/RSG can self score their response

  14. Primary Frequency Response Percent (PFRP) Formula: A/B = CX100% Primary Frequency Response Percent = (PFR / PRO) * 100%. A = PFR is the max change in NIa during the PFRP (1st 30 seconds) B = PRO is [PFRA * (0.5 BA Gen + 0.5 BA Load) + PFRT] * (AR) Total WECC Gen

  15. Just The Primary Basics • Step 1 - Find it! • (A) BA’s Max change in Net Actual Interchange during PFRP 15 MW • Assume 15 MW. • (B) BA’s total Gen plus Load divided in half 1500 MW • Assume 1500 MW. • (C) WECC total on-line gen during the PFRP 150,000 MW • Assume 150,000 MW • (D) N-2G 2800 MW • Assume 2800 MW. • (E) Frequency delta .5 Hz • Actual frequency minus schedule frequency. Assume .5 Hz drop. • Step 2- Divide • BA’s total Gen plus Load divided in half (B) / WECC gen (C) = (F) .1% • Step 3 - Times • ((F) X (D)) X (E) / .5 = (G) 28 MW • A/G = Score!!! 53%

  16. Primary Frequency Response (PFR) “Shall average greater than or equal to 100% during the Primary Frequency Response Measurement Period.” Why average 100%? Primary purpose Measure interconnection – not punish the BA/RSG Machines are not “always” dependable but “on average” they are The average mitigates the abnormal but serves as a solid indicator of available reserves Risky to game / hard to recover from “zero”

  17. Secondary Response Formula If ACE is greater than or equal to zero: (For brevity the separate formula for less-than-zero is not covered in this PPT.) n BRR = {∑ [(10BΔFj + ACEj) / SROj] / n} * 100 j= 0 Bias Response Ratio = is the measure of a BA’s frequency response relative to a BA’s Bias – measured by BA’s ACE or change in ACE

  18. Just The Secondary BasicsIf Ace is greater than or equal to zero when event occurs • Step 1 - Find it! • (A) The Frequency Bias stated in MW/Hz. -750 MW • For the specific BA. Assume -750 MW/Hz. • (B) The frequency dip in HZ -0.126 HZ • In a given scan rate. Assume -0.126. • (C) The frequency dip response in MW 94.5 MW • A X B = C • (D) ACE -35 MW • In a given scan rate. Assume -35 MW. • Step 2 - Add • The frequency dip response in MW (C) + ACE (D) = (E) 59.5 MW • Step 3 - Divide • ((E) / (C)) X 100 = The frequency dip response in MW 63% • Your Score!!!!! 63%

  19. Secondary Response Why a response average greater than or equal to 50% and less than or equal to 200%? Purpose Get enough response without violating SOLs Enough is 50% WECC Bias is about 2088 or twice what it takes to restore frequency to normal for a 59.75 Hz dip once secondary period begins Too much to 200%

  20. Averaging the Scan Rates • For each frequency event during the secondary response all scans are averaged until 59.9 Hz regardless of the number of scans.

  21. Request for Approval: Errata Section D.1.3 Data Retention Refers to “M.1 through M7” Should be “M1 through M6” Should replace / retire current measurement criteria BAL-00X-1 M5 has a typo where "during the" has been repeated. Delete one of them. R3.1.1 references M4.6, which doesn’t exist anymore. Corrected.

  22. Request for Approval: Motion 1 of 2 • Suggested Motion • “Move that the Operating Committee approve BAL-012-WECC-2-CR known as the Frequency Responsive Reserves criteria and forward the criteria to the WECC Board of Directors for appropriate action.”

  23. Request for Approval: Motion 2 of 2 • Suggested Motion if BAL-012-WECC-2-CR is approved • “Having approved BAL-012-WECC-2-CR as a replacement for the current Frequency Responsive Reserves criteria designated as BAL-00X-1 (also entitled Frequency Responsive Reserves), move to retire BAL-00X-1.”

  24. Questions? • Panel • Mr. Baj Agrawal • Mr. David Lemmons • Mr. John Stout • Mr. Ken Wilson