Ultima ® X Gas Monitor with HART. Display Version. Agenda. HART: General Information Network Topology Ultima X Features Calibration Options. HART – General Information. HART (Highway Addressable Remote Transducer) MSA device is a slave in a polled network

niveditha
Download Presentation

Ultima ® X Gas Monitor with HART

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Ultima® X Gas Monitor with HART Display Version

  2. Agenda • HART: • General Information • Network Topology • Ultima X Features • Calibration Options

  3. HART – General Information • HART (Highway Addressable Remote Transducer) • MSA device is a slave in a polled network • HART is a software protocol running over 4-20mA Hardware • Point to point • 1200 baud FSK

  4. HART – General Information con’t • HART Communication is a bi-directional industrial field communication protocol used to communicate between intelligent field instruments and host systems. • HART provides two simultaneous communication channels: • 4-20mA analog signal • Communicates the measured gas • Fastest and most reliable in industry • Digital signal • Device status, diagnostics, additional measured / calculated values, etc • Together, the two communication channels provide a complete field communication solution that is easy to use and configure, is low-cost and is very robust. Visit www.hartcomm2.org for more information

  5. Typical HART Network Topology

  6. Ultima X with HART Features • Standard enclosure options • XP, SS • GP, SS • PL, Plastic • New HART PCBAs • 2-wire (no LEDs, no relays) • 3-wire (LEDs are standard) • with relays • without relays • I.S. HART Port • Same as Ultima XL

  7. Calibration Options • Calibration utilizing: • Portable handheld communicator, DCS or laptop • IR Controller or Calibrator • Disconnect under power (in-shop calibration) • Sensor X-change program

  8. External AC for relays Ultima X with HART - Options Possible HART access DC In 4-20 mA & HART HART port + sensor

  9. Ultima X with HART - Options Possible HART access XE with HART port & remote sensor North American Remote (2008) Continuing to use white box for North America in 2008

  10. Ultima X with HART - Options Possible HART module + HART port XE with pushbutton HART modules automatically supplied under certain conditions

  11. Customer will receive a HART Module if: Order Internal Power Supply + HART port or Order Pushbutton + HART port or Order Reactive gas for Div 1 area (ATEX)+ HART port + + + HART Module

  12. HART Module • Consists of: • HART port • HART barrier (Intrinsically Safe) • Terminal board for connections • XL PCB cup • XL enclosure • Mounting bracket

  13. AC Ultima X with HART - Options Possible HART module Pushbutton + HART port + remote sensor