IS CAN Bus – CiA WD 103 Update Rick Ales Swagelok Company CPAC May 2006. NeSSI Bus History. 2000-1Wireless, Bluetooth preferred solution 9/2001Selected CAN bus as preferred solution 7/2003ODVA & NIST IS CAN workshops 2/2004Profibus PA selected for DoE project

Download Presentation

IS CAN Bus – CiA WD 103 Update Rick Ales Swagelok Company CPAC May 2006

An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -

Presentation Transcript


IS CAN Bus – CiA WD 103 UpdateRick Ales Swagelok CompanyCPAC May 2006


NeSSI Bus History

  • 2000-1Wireless, Bluetooth preferred solution

  • 9/2001Selected CAN bus as preferred solution

  • 7/2003ODVA & NIST IS CAN workshops

  • 2/2004Profibus PA selected for DoE project

  • 6/2004IEEE p1451.6 Working group formed

  • 7/2004Foundation Fieldbus for DoE project

  • 1/2005IEEE p1451.6 IS CAN Draft Spec.

  • 3/2005Fieldbus Foundation and CPAC announce FF

  • 5/2005 DoE project defunct.

  • 1/2006Transition p1451.6 effort to CiA WD 103

  • 3/22/06CiA WD 103 Meeting.

  • 3/31/06North America CiA office transitions to DE.


CiA WD 103 Attendees


IS CAN NeSSI Bus System


IS CAN Major Parameters

  • The CAN communication model is described in /ISO11898-1/ and /CiA301/.

  • Single power source, co-cable was the only option considered.

  • Power bus specification is derived from commercially available IS power systems.

  • 9.5 Vdc @ 1.0 A Maximum

  • 10 Meter cable distance

  • M12, 5 circuit connector


Why Only 10 Meters?

  • Since this system is expected to work with NAMUR IS solenoid valves, which require 7.7 volts.

  • IOMAX = 1 amp

  • VOMAX = 9.5 V

  • With typical 5% regulation, then:

  • VOTYP = 9.0 V, VOMIN = 8.6 V

  • For a 10 m @ 24 AWG, resistance is 0.87 ohms

  • 1 amp * 0.87 ohms = 0.9 V

  • Therefore, actual power delivered to the device could be:

  • VDEV MIN = 8.6 V – 0.9 V = 7.7 V


Associated Apparatus Entity Parameters


System Power Parameters


What is next?

  • Bill Seitz, President IXXAT to replace C. Menon as committee chair.

  • Sigrid Stramka, CAN in Automation, DE, assigned as CiA technical representative.

  • Next CiA WD 103/ IEEE 1451.6 teleconference to be scheduled for early June.

  • Update Draft Standard and circulate for general review & comment.

  • Develop & validate an apparatus example circuit.


Discussion?