1 / 74

Prepared by: Ahmad F. Amad Ahmad A. Zeineddin Fawzi S. Abu-Aladas Mahhmoud A. Sukkar

Evaluation of The Structural Design of Nursing and Optical Faculty-An Najah National University. Prepared by: Ahmad F. Amad Ahmad A. Zeineddin Fawzi S. Abu-Aladas Mahhmoud A. Sukkar. Supervisor: Mr. Ibrahim M. Arman. Out Lines.  Project description.  Three dimensional modeling.

millerj
Download Presentation

Prepared by: Ahmad F. Amad Ahmad A. Zeineddin Fawzi S. Abu-Aladas Mahhmoud A. Sukkar

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Evaluation of The Structural Design of Nursing and Optical Faculty-An Najah National University Prepared by: Ahmad F. Amad Ahmad A. Zeineddin Fawzi S. Abu-Aladas Mahhmoud A. Sukkar Supervisor: Mr. Ibrahim M. Arman

  2. Out Lines  Project description.  Three dimensional modeling.  Structural design and evaluation

  3. Project Objectives Evaluation Comparison

  4. Location

  5. Project Description  This structure is used for educational purposes.  The faculty consists of seven floors.  Six main floors and roof floor.  This structure includes mechanical rooms and three water tanks.  The project has two axes of symmetry.

  6. Plan of Ground Floor

  7. Loads  Gravity loads: ◦ Dead load. ◦ Live load. LOAD (KN/m2) CASE Offices, class rooms 3.0 MECHANICAL ROOMS 7.5 Staircase 4.0 Roofs: With access 1.5 Without access 1.0 Mechanical equipment 7.5 ◦ Snow load:1.5 KN/m2.

  8. Loads  Lateral loads: ◦ Wind loads. ◦ Seismic loads (UBC-97 is used).  I= 1  Seismic zone 2B.  Z=0.2  Cv=0.2  Cs=0.2  R=5.5  Soil profile type =Sp

  9. Load Cases and Load Patterns

  10. Design Codes  ACI 318 – 02 American concrete institute  UBC – 97 Uniform building code  ASCE7 – 02 American society of civil engineering  JCLF – 06 Jordan code for loads and forces  JSC – 05 Jordan seismic code.

  11. Structural System  Shear walls.  Frames, which consist of: ◦ Beams. ◦ Columns.

  12. THREE DIMENSIONAL MODELING

  13. Material Property for concrete

  14. Shell Data •Ribbed slab definition

  15. Modifiers equations where: Modifiers for ribbed slab

  16. Modifiers Shear wall Two way solid slab

  17. Modifiers For columns For beams

  18. Response Spectrum

  19. EQULIPRIUM this result from sap

  20. Dead load This include own weight for all structural elements Slabs, Beams, columns and walls. floor weights (KN) B3 7184.74 B2 15775.82 B1 13096 GF 13964.56 F1 10331.02 F2 10103.91 RF 9396.28 TR 1215.66 total 81068.08

  21. Live load  Live load in this project has different values depending on the function, which are mechanical room, offices, class rooms and stairs. TOTAL LIVE floor NO LOAD(KN) B2 3765.75 B1 3200.4 GF 3652.5 F1 2553.9 F2 2553.9 RF 1721.955 TF 198 total 17646.405

  22. Snow load Roof floor and top roof are exposed to snow load floor snow LOAD * 100% =0.7%. Error = TF 296.97 RF 1044.765 Super imposed dead load This project has two SID; first one on the slab (include partition load tiles and fill) and the other outer shear wall (include masonry, mortar and plaster) total 1341.735 Super imposed Floor number dead load (KN) Total SID= 14232.2 + 19556.28 = 33778.5 B2 4507.2 B1 4208.8 GF 4146.68 F1 3346.8 F2 3346.8 *100% =3.4% Error = RF 0 TF 0 Total 19556.28

  23. Soil load :  Soil is covering the three basements floor in the north approach, and this affect on retaining wall.  K 0 = 1- sin α (α= 30 0), k =0.5  Unit weight equal 20 KN/m3  Live load = 15 KN/m3 Long of wall=31.25m  Total load = (845*31.25)+(97.5*31.25) =29453.1 KN/m Error =0% 

  24. Check moment in beams  The live load is chosen as an example of load carried by beams to make the comparison: Beam Name Moment by T.A.M (KN.m) 11.34 Moment by SAP (KN.m) % of error GB5 10.5 7.98 1B1 46.25 44.17 4.7 2B11 69.77 71.75 2.76

  25. Check moment in slabs

  26. Period calculation Period from SAP2000=0.327 S Error = 2.75 %

  27. Seismic load

  28. STRUCTURAL DESIGN AND EVALUATION

  29. Columns  Number of columns at the building 216 columns.  The columns uniformed into 9 sets in the basement floors and 8 sets in the upper floors. Floor Columns sets B3 3BC1 3BC2 3BC3 3BC4 3BC5 3BC6 3BC7 3BC8 3BC9 B2 2BC1 2BC2 2BC3 2BC4 2BC5 2BC6 2BC7 2BC8 2BC9 B1 1BC1 1BC2 1BC3 1BC4 1BC5 1BC6 1BC7 1BC8 1BC9 Gr GC1 GC2 GC3 GC4 GC5 GC6 GC7 GC8 - 1 1C1 1C2 1C3 1C4 1C5 1C6 1C7 1C8 - 2 2C1 2C2 2C3 2C4 2C5 2C6 2C7 2C8 - Rf RC1 RC2 RPC1 RPC2 - - - - -

  30. Columns  Dimensions

  31. Columns Plan shows columns distribution at the floor

  32. Columns  The design of the columns. • SAP2000 • Longitudinal • Lateral

  33. Columns Comparison between SAP2000 and office’s designs for the ground floor Floor No. Reinforcement from structural drawings Reinforcement from SAP2000 Gr (mm) (mm) (mm)2 Longitudinal reinforcement Lateral reinforcement Longitudinal Lateral reinforcement Longitudinal Lateral Column No. Width Depth area # bars Ab As # legs Av S As # bars As # legs Max. S Practical S Comments Comments ɸ ɸ ɸ ɸ GC1 300 300 90000 8 14 153.86 1230.88 4 10 314 200 900 14 6 157 10 4 224 200 Safe Safe GC2 400 400 160000 8 16 200.96 1607.68 4 10 314 200 1600 16 8 157 10 4 256 250 Safe Safe GC3 400 400 160000 8 16 200.96 1607.68 4 10 314 200 1600 16 8 157 10 4 256 250 Safe Safe GC4 400 400 160000 8 20 314 2512 4 10 314 200 1600 20 6 157 10 4 320 300 Safe Safe GC5 400 400 160000 8 18 254.34 2034.72 4 10 314 200 1600 18 8 157 10 4 288 250 Safe Safe GC6 400 400 160000 8 18 254.34 2034.72 4 10 314 200 1600 18 8 157 10 4 288 250 Safe Safe GC7 400 400 160000 8 16 200.96 1607.68 4 10 314 200 1600 16 8 157 10 4 256 250 Safe Safe GC8 400 400 160000 8 16 200.96 1607.68 4 10 314 200 1600 16 8 157 10 4 256 250 Safe Safe

  34. Columns  The differences between the two designs: ◦ 3BC2 & 2BC2 ◦ 3BC8 ◦ 1C1 ◦ 1C2

  35. Columns  The column 1C1 Moments in 1C1 Moments in GC1

  36. Columns  The column 2C1 Axial loads in 2C1 Axial loads in GC1

  37. Columns Axial forces diagram from SAP2000

  38. Shear walls  All the exterior walls and the elevators’ wells are shear walls.  Shear walls were treated as columns.

  39. Shear walls The shear walls were taken. Shear wall Width (m) Depth (m) P (KN) M (KN/m) A B C D 9.3 3.625 2.5 6.625 0.2 0.2 0.25 0.25 4477.6 2231.61 1296.6 3901.54 5203.375 332.54 171 3208 E 6 0.2 4191.49 3699 F 2.5 0.25 963.66 152.75

  40. Shear walls Interaction diagram for shear wall A 30000 25000 20000 15000 P (KN) 10000 5000 0 0 10000 20000 30000 40000 50000 -5000 -10000 M (KN.m)

  41. Beams  Number of beams sets varies from 12 to 16 depending on the floor.  Number of spans and the dimension of the beams different from one set to another.

  42. Beams  list of selected beams Beam Name 2BB9 2BB10 1BB1 1BB2 1BB4 Gb1 Gb7 Gb10 1B2 1B12 1B16 2B2 2B12 2B15 Rb2 Rb8 Rb17 Floor Width Depth B2 B2 B1 B1 B1 Gb Gb Gb B1 B1 B1 B2 B2 B2 Rb Rb Rb 400 300 300 300 300 300 250 300 300 250 400 300 250 800 300 400 400 800 1500 600 600 800 600 800 1500 1005 800 800 1005 800 300 900 800 800

  43. Beams  Design of beams: ◦ Longitudinal reinforcing. ◦ Lateral reinforcing. ◦ Structural drawings.

  44. Beams TOP Structural Drawings SAP2000 Left Middle Right Left Middle Right Beam No. Floor width depth para. Span # Bars # Bars # Bars # Bars # Bars # Bars Comments ɸ ɸ ɸ ɸ ɸ ɸ The left and middle are safe, the right is not safe 400 800 2400 1 3 25 3 16 3 16 2 25 2 16 4 16 400 800 2400 2 3 25 3 16 3 25 2 25 2 16 2 25 All are safe 2BB9 B2 400 800 2400 3 3 25 3 16 3 25 2 25 2 16 2 25 All are safe The left is not safe, the middle and right safe 400 800 2400 4 3 16 3 16 3 25 7 16 3 16 2 25

  45. Beams  Top reinforcing differences. Moment from gravity combination Moment from earthquake combination

  46. Beams  Comments on beams: ◦ Longitudinal reinforcing steel. ◦ Lateral reinforcing. ◦ Deflection.

  47. Slabs  There is two types of slabs; one way ribbed slab and two way solid slab.  All slabs have a thickness of 30 cm.  A representative strip were taken in solid slabs and a representative sample slab were taken in ribbed slab.

  48. Slabs  Design of slabs: ◦ Two way solid slabs. ◦ One way ribbed slab.

  49. Slabs  M11 diagram for the second basement slab

More Related