Harmonics. Is a distortion in an electrical network created by non-linear electrical devices which use solid state switching hardware

mervin
Download Presentation

Harmonics

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Harmonics • Is a distortion in an electrical network created by non-linear electrical devices which use solid state switching hardware • Is a component of a periodic wave which has a frequency which is a multiple of the fundamental power line frequency of 50 Hz: i.e. 150Hz is third order harmonic frequency • Is a steady-state phenomenon, not a transient condition

  2. Harmonics • 3-phase non-linear loads typically create 5th, 7th, 11th and 13th harmonic • 2-phase non-linear loads typically create 3rd order harmonics and higher order multiples of 3 • Total harmonic distortion of a waveform (THD) = the level of voltage or current harmonic distortion existing at any point on a power system

  3. Harmonics • Usual side-effect of harmonics: • Higher peak-to-peak voltage resulting in insulation failure of motors, transformers and capacitors • Higher rms currents resulting in higher equipment operating temperatures • Overheating cables • Nuisance trips or damage to CB’s and fuses

  4. Harmonics and capacitors • Capacitors do not generate harmonics BUT they can amplify them significantly • When harmonic levels are elevated, there is a significant risk of harmonic resonance between the PFC capacitors and the supply transformer • Amplification of harmonics by the capacitors has a negative impact on the life of the capacitors as well as the rest of the plant equipment • Harmonics can be absorbed or “filtered” through the fitment of reactors in series with pf correction capacitor banks

  5. Harmonic Filtration • A reactor is placed in series with each of the capacitor banks of a PFC system • The reactor creates a inductive impedance path to those currents created at harmonic frequencies (typically blocking any frequency above 135 Hz) • The capacitors can no longer amplify harmonic voltages and currents, eliminating the risk of parallel resonance • If the total non-linear load of a plant is above 25%, harmonic filters will almost always be required for power factor correction purposes • Blocking reactors have a significantly cost implication for PFC equipment