1 / 17

Utility Wildfire Risk Mitigation: A California Perspective

Utility Wildfire Risk Mitigation: A California Perspective. August 16, 2019 Koko Tomassian, P.E. Sr. Utilities Engineer Safety and Enforcement Division Koko.Tomassian@cpuc.ca.gov. California Wildfires. Agenda. Understanding the Problem The 5 W’s CPUC Response CPUC Fire-Threat Map

mcushman
Download Presentation

Utility Wildfire Risk Mitigation: A California Perspective

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Utility Wildfire Risk Mitigation: A California Perspective August 16, 2019 Koko Tomassian, P.E. Sr. Utilities Engineer Safety and Enforcement Division Koko.Tomassian@cpuc.ca.gov

  2. California Wildfires

  3. Agenda • Understanding the Problem • The 5 W’s • CPUC Response • CPUC Fire-Threat Map • Utility fire ignition data collection and reporting • Risk-based decision-making framework in GRCs

  4. Understanding the Problem

  5. Before Solving a Problem, We Must First Understand It • Need to get the complete picture • Before discussing “How” to implement effective mitigation measures, we must ask the 5 W’s: • Who? • What? • When? • Where? • Why?

  6. When? • When an ignition occurs is of critical importance • Weather information: • Wind speeds and gusts • Temperature • Humidity • Environmental information: • Fuel load conditions (i.e. fuel moisture content)

  7. Where? • CPUC Fire-Threat Map & High Fire Threat District (HFTD) • Collection & reporting of utility fire ignition data • Incorporation of a risk-based decision making framework in GRCs

  8. CPUC Response

  9. CPUC Fire-Threat Map & the HFTD

  10. CPUC Fire-Threat Map Land Coverage in California

  11. Regulatory & Mitigation Efforts in HFTD Areas • Increased vegetation clearance requirements • Increased inspection frequencies and shortened repair timeframes • Utilities targeting conductor and equipment replacement programs to HFTD areas • Weather station installations on circuits in HFTD areas For more information visit: www.cpuc.ca.gov/firethreatmaps

  12. Reporting of Utility Ignition Data • Adopted in 2014 by D.14-02-015 • Reported annually on April 1st by: • PG&E • SCE • SDG&E • Reportable Ignitions: • Utility asset provides heat source for ignition • Self-propagating of material other than utility facility • Travels > 1m from ignition point • Utility has knowledge of fire occurrence • First reports submitted on April 1, 2015, covering the latter half of 2014 • Over 2,500 ignitions reported to-date

  13. Plot of Suspected Initiating Events2014 – 2018 by Utility

  14. Object Contact Events by Object Type

  15. Equipment/Facility Failure Events by Equipment Type

  16. Informative Takeaways from Utility Ignition Data Analysis • 75% of ignitions result in fires ≤ 0.25 acres • Only 1% of ignitions result in fires > 1,000 acres • Nearly 97% of all reported ignitions occurred on the distribution system • Over 77% of all reported ignitions occurred in Q2 or Q3

  17. Thank You! For further information related to any information presented today, feel free to contact me at: Koko Tomassian, Sr. Utilities Engineer Safety & Enforcement Division 213-576-7099 Koko.Tomassian@cpuc.ca.gov www.cpuc.ca.gov