Conquest FireSpray Fire Rated Ductwork

Conquest FireSpray Fire Rated Ductwork . Warren Michigan . Manufacturing Capabilities. Two fabrication facilities (130,000 + sq. ft.) History of large projects (Ohio State Univ.) Full 3D modeling & project management staff All styles of duct (spiral, flat oval, rectangular, welded).

marly
Download Presentation

Conquest FireSpray Fire Rated Ductwork

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Conquest FireSpray Fire Rated Ductwork Warren Michigan

  2. Manufacturing Capabilities • Two fabrication facilities (130,000 + sq. ft.) • History of large projects (Ohio State Univ.) • Full 3D modeling & project management staff • All styles of duct (spiral, flat oval, rectangular, welded)

  3. Enclosure by Design: • In the USA the predominate method for fire protection is subdivided into categories: • Compartments • Detection • Alarm/Notification • Evacuation • Sprinklers • Smoke Removal

  4. Enclosure by Design: • What about smoke removal? • Are we engineering a smoke removal system tested for that use? • Or are we utilizing the existing systems to perform a function they are not tested to provide?

  5. Enclosure by Design: • According to SMACNA and the corresponding British standard ventilation and exhaust ductwork have no tested fire resistive standard in their respective designs. • That means the SMACNA tables are not designed to include a fire rating. • HVAC systems with openings will introduce hot gasses into the duct that is not designed to handle.

  6. What is Fire Rated Ductwork Search of 2009 IBC and 2009 IMC No mention in the code of Fire Resistive Ductwork How do we handle Fire Resistive Ductwork?

  7. Enclosure by Design: • There is no USA (ASTM) test today that recognizes fire rated duct systems. • There is however an International Standard ISO 6944 (1985 and 2008) .

  8. ISO 6944 • ISO 6944 • Test Fire Resistive performance of ductwork. • Test follows time temperature curve in E119 • Developed in EU for Fire Duct and Smoke Extraction Ductwork.

  9. ISO 6944 • ISO 6944 • Tests Ductwork for 2 conditions • Fire inside a duct Type B • Fire outside a duct Type A • Conditions of the Test • Integrity • Stability • Insulation

  10. Type A and Type B Duct (Wrap is only rated for Type A) THE DUCT IS THE ENCLOSURE

  11. Alternate Systems Drywall Enclosures • Conventional Shaft Riser with 2 hour Rated Gypsum Enclosure (3 layers) • Fire dampers must be in wall

  12. Alt. Wrap Enclosures Firewrap Insulated Duct • Insulated Fire Wrap • 1 and 2 hr protection • Type A only (fire outside the duct) • Upgraded Duct • Upgraded Supports • Multiple Trades

  13. Fire Rated Duct Tested and Classified by UL & ETL Classified for up to 2 & 4 hours as a smoke and fire duct (ISO-6944) and complies with NFPA 96

  14. Fire Rated Ductwork • US Codes are evolving to accept a duct as an enclosure. • ASTM E2816-11 Metallic Fire Resistive Duct Enclosures. • Passed Committee July 2011 • ICC Evaluation Services • Acceptance Criteria November 2011

  15. Fire Rated Ductwork & Metalic Enclosure • Test Procedure based on ISO 6944 (2008) standard • Tests Ductwork for both conditions • Horizontal Condition A, C • Vertical Condition B, D • Test for fire inside and outside the duct. You cannot guarantee a fire will remain outside the duct.

  16. Fire Rated Ductwork & Metalic Enclosure • Test Procedure based on ISO 6944 (2008) standard • Conditions of the Test • Integrity • Stability • Insulation • Test includes Hangers, Supports and Firestop conditions. • Inserts and structural connections not inlcuded.

  17. Grease Duct • June 2012 • ICC ES issued Acceptance Criteria AC101.2 • Recognized galvanized duct without porcelain coating. • Tested to conditions of UL1978 except for those related to coating. • Field enclosure

  18. Conquest FireSpray sales@conquest-firespray.com 586-576-7600