NFPA 13 ACTUALIZACION EDICION 2013. Presentado por Michael Wade McDaniel F Tech www.ftech.com.mx [email protected] Alcance : 1.1.2 SISTEMAS DE ROCIO DE AGUA .

Download Presentation

NFPA 13 ACTUALIZACION EDICION 2013

An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -

Presentation Transcript


Nfpa 13 actualizacion edicion 2013

NFPA 13ACTUALIZACION EDICION 2013

Presentado por Michael Wade McDaniel

FTech

www.ftech.com.mx

[email protected]


Alcance 1 1 2 sistemas de rocio de agua

Alcance: 1.1.2 SISTEMAS DE ROCIO DE AGUA

Este estandard no da los requerimientospara el diseño o instalacion de sistemas contra incendio de rocio de agua, que no son consideradossistemas contra incendio a base de rociadores y que son tratados por NFPA 75, Estandar en Sistemas Contra Incendio de Rocio de Agua.

Nebulizado.


Cap tulo 3 definiciones

Capítulo3 - Definiciones

  • Válvula de control

  • Cortina de corriente de aire

  • Unidad de ocupación

  • Ventilador Alto Volumén

  • Baja Velocidad

  • Obstrucción Continuo

  • Obstrucción no continuo

  • Espaciolibre al Techo

  • Fuente de aguacruda

  • Sistema de Rociadores

  • Cuarto pequeño

  • Sistemaanticongelante

  • Combinacióntuboseco /pre acción

  • Cabezal

  • Riser del Sistema

  • Espaciolibre al almacenamiento

  • CaracteristicasGenerales de Rociadores

  • ContenedorAbierto

  • Soporteria 4 vias

    • Colgador

    • Fuerza vertical neto

    • Ensamble de separacionsísmica


3 3 7 v lvula de control

3.3.7* - Válvulade Control

  • Unaválvulaquecontrola el flujo a sistemas contra incendio a base de agua.

  • *Clarificaciónque no incluyevalvulas de inspectores, mangueras, drens, trim, check, alivio, etc.

  • Básicamente son válvulas en el anillo y riser


3 3 18 1 obstrucci n continuo 3 3 18 2 obstrucci n no continuo

3.3.18.1 – ObstrucciónContinuo3.3.18.2 ObstrucciónNo Continuo

Obstrucción Continuo.Unaobstrucciónque se encuentra en o abajo del nivel de deflectores de rociadoresqueafecte el patron de descarga de dos ómásrociadoresadyacentes.  

Obstrucción No Continuo. Unaobstrucciónque se encuentra en o abajo del nivel de deflectores de rociadoresqueafectesolo un rociador.


3 3 22 sistema de rociadores

3.3.22* Sistema de Rociadores

Una red integrada de tuberiadiseñada de acuerdo con estandares de ingeniería en proteccion contra incendioqueincluyan: Unafuente de agua, unaválvula de control de agua, unaalarma de flujo de agua, y un desahogue. La porcion del sistema de rociadoresque se encuentra por arriba del nivel del sueloesuna red de tuberiacuyodiámetro ha sidoespecificadaódiseñadohidraulicamenteinstalado en un edificio, estructuraó area, generalmenteporencima (overhead) donde se conectanrociadores en un patron sistemático. El sistemacomunmente se activa por calor de un incendio y descargaaguasobre el area del incendio.


3 11 3 soporte de 4 vias

3.11.3*- Soporte de 4 vias

  • Soportes de oscilaciónadyacentesó un ensamble de soporte de oscilacióncuyaintenciónesresistir el movimientodiferencial de la tubería en el sistemaen todaslasdireccioneshorizontales.


3 11 4 colgador

3.11.4 - Colgador

  • Un artefactoóensambleutilizadoparasoportar la cargagravitacional de la tubería del sistema


4 6 soporte de componentes no propios de un sistema de rociadores

4.6 – Soporte de componentes no propios de un sistema de rociadores

  • Componentes de sistemas de rociadores no debenserusadoparasoportarcomponentes no propios del sistema de rociadores.


Capitulo 6 componentes del sistema

Capitulo 6 – Componentes del Sistema

  • 6.1.1.1 – RegistroóListado

  • Materialesóartefactos no designadosespecificamente por esteestándarddebenserusado de acuerdo con todaslascondiciones, requerimientos y limitacionesde suregistro especial.


Listado cont

Listado (Cont)

Los componentes de lasvalvulas (incluyendo valve trim, partesinternas, empaques y similares) no se requierequeseanlistadasindividualmente.

Tuberiaaceropermitido en la Tabla 6.3.1.1 y Table 6.4.1 no requiereserlistado (sicumple con ASTM y ANSI).

Tuberia no metálica y conexionesincluidas en la Tabla 6.3.1.1 y la Tabla 6.4.1 debenserlistadas.


6 1 1 3 tubos de acero cobre y hierro

6.1.1.3 – Tubos de Acero, Cobre y Hierro

  • Tubería de acero, cobre, hierro y conexionesfabricados de acuerdo a los estándares en la Tabla 6.3.1.1 y la Tabla 6.4.1 e instalados de acuerdo a lassecciones 6.3.2 al 6.3.5. no requieren ser listados.


6 2 1 1 rociadores

6.2.1.1 - Rociadores

  • Cuando un rociador ha sido des-instalado por cualquiermotivo, no sera re-instalado.


6 2 6 2 2 6 2 6 2 3 pintando rociadores

6.2.6.2.2/6.2.6.2.3PintandoRociadores

Donderociadoreshansidopintados por otrosque no sea el fabricante, debenser re-emplazados por rociadoreslistados de lasmismascaracteristicas, incluyendo el factor K, respuestatermica y distribución de agua.

Dondelas tapas en rociadoresocultoshansidopintados por otrosque no sea el fabricante, la tapa debeser re-emplazada.


6 2 7 4 chapetones de rociadores

6.2.7.4 – Chapetones de Rociadores

  • No se permitira el uso de calafateoópegamentoparasellar la penetraciónóparafijar los componentes de un chapetonó tapa oculta.


Nfpa 13 actualizacion edicion 2013

Va a operar?


6 3 7 tuber a no met lica

6.3.7 – TuberíaNo Metálica

Debeserinvestigadotubería no metálicacontenida en la Tabla 6.3.1.1 parasuidoneidad en instalaciones de sistemasautomáticos de rociadores y listadosparaesteservicio.


Tuber a no met lica cont

TuberíaNo Metálica(Cont)

  • Cuandose usatuberia no metálicaen sistemascombinados, los aceitesparacortar y lubricantesutilizados en la fabricaciónde la tuberíade acero, serácompatible con los materiales no metalicos.

    Materiales anti fuegoqueseanutilizados en laspenetraciones de tubería no metálica se le investigaráparasucompatibilidad con materiales no metálicos.

    Estasección (6.3.7) esparacubrirsituaciones de compatibilidad.


6 10 letreros

6.10 - Letreros


7 1 1 medidores de presi n sistemas h medos

7.1.1 – Medidores de Presión(sistemashúmedos)

  • Un manómetroaprobado de acuerdo a 8.17.3 se instalará en cadasistema de riser.

  • Aprobado no necesariamenteListado.

  • No afecta el funcionamiento del sistema.


Rociadores en equipo mec nico

Rociadores en EquipoMecánico

  • No se requiereinstalación de rociadoresdentro de equipoeléctrico, equipomecánicoóunidades

  • quemanejenaire.

  • Si el aislamientoes

  • combustible?


7 11 2 aditivos y recubrimientos

7.11.2 – Aditivos y Recubrimientos

Aditivos a la fuente de aguapara control de la corrosiónmicrobiológico (MIC) u otros, debenserlistadosparasuusodentro de sistemas contra incendio de rociadores.

Recubrimientosinternos de tubería, excluyendogalvanización, para control de corrosion microbiológico u otrascorrosionesdebenserlistadosparasuuso en sistemas contra incendio de rociadores.


8 3 3 4 uso de rociadores

8.3.3.4 – Uso de Rociadores

  • Cuandosistemasexistentes de riesgoligeroseanconvertidos a usarrociadores de respuestarapidoóresidenciales, todos los rociadores en un compartimientoserén re-emplazados.

  • 8.3.4.1 Los rociadorestendrén un factor K nominal mínimo de 5.6


8 4 6 6 rociadores de esfr en riesgos de ocupaci n

8.4.6.6 – Rociadores de ESFR en riesgos de ocupación

  • Rociadores ESFRdiseñadosparacumplir con cualquiercriterio en los Capítulos 12 hasta el Capítulo 20 se le permitiráprotejerocupacionesligeros y ordinarios.


8 4 7 4 rociadores cmsa en riesgos ocupacionales

8.4.7.4 – Rociadores CMSA en RiesgosOcupacionales

  • Rociadores CMSA de respuestarapidadiseñadosparacumplir con cualquiercriterio del Capitolo 12 hasta Capítulo 20, son permitidosparaprotegerriesgosocupacionalesligeros y ordinarios.

  • Rociadores CMSA de respuestaestándardiseñadosparacumplir con cualquiercriterio del Capitolo 12 hasta Capítulo 20 son permitidosparaprotegerriesgosocupacionalesordinarios.


8 5 5 3 1 1 pisos con rejillas abiertas

8.5.5.3.1.1Pisos con rejillasabiertas

  • Entresuelos con rejillasabiertas de mas de 4 pies de anchorequierenprotección de rociadoresdebajo de lasrejillas.

  • Con suplaca de protection de aguaarribacomo los rociadores in-racks.


8 5 5 4 obstrucciones y closets

8.5.5.4 - Obstrucciones y Closets

  • En todos los closets y compartamientos, incluyendoesosquecontienenequipomecánico, que no seanmayores a 400 pies³ (11.3 m³) en area, un solo rociadorubicado en el punto mas alto del techo sera suficiente sin consideración de obstruccionesódistanciamínima a la pared.


8 15 1 2 7 espacios ocultos que no requieren rociadores

8.15.1.2.7 – Espaciosocultosque no requierenrociadores

  • Espaciosocultosrellenados con aislamento no combustible no requiereproteccion de rociadores.

  • Un espacio de aire de máximo 2 pulgadas se permite en la parte superior del espacio.


Techo con eps

Techo con EPS


Exposed polystyrene eps o espuma expandida

Exposed Polystyrene (EPS) o Espuma Expandida

  • Cuidado: Auto extinguible???

  • Alto inflamabilidad

  • Humodenso y toxico

  • 18,000 btu/lb

  • Gasolina 19,000 btu/lb


Techo de poliuretano expandido edificio de alto nivel en panama

Techo de PoliuretanoExpandido (Edificio de Alto Nivel en Panama)


Situaci n epidemia

SituaciónEpidemia

  • Dóndeestanmisrociadores?

  • Dóndeestamismangueras y de quétemaño?


8 15 5 3 cuartos de ascensores y cuartos de maquinaria

8.15.5.3 – Cuartos de ascensores y cuartos de maquinaria

  • No se requierenrociadores contra incendioautomáticos en cuartos de maquinaria de ascensores y, espacios de control óhuecos de ascensores de traccióninstalados de acuerdo a lasprovisionesaplicables en NFPA 101 ó los códigosaplicables del edificio, donde se cumplantodaslassiguientescondiciones:

  • (1) se dediqueexclusivamente a contenerequipo de ascensor.


8 15 5 3 cuartos de ascensores y cuartos de maquinaria1

8.15.5.3 – Cuartos de ascensores y cuartos de maquinaria

  • (2) Estanprotegidos por detectores de humo u otromedio de detecciónautomático contra incendioinstaladosconforme a NFPA 72.

  • (3) Estanseparados del resto del edificio por paredes y ensambles de piso/techoótecho/pisoquetenganunacalificación de resistencia al fuego no menor al specificado por el códigoaplicable del edificio. (normalmentecomo 2 horas).


8 15 5 3 cuartos de ascensores y cuartos de maquinaria2

8.15.5.3 – Cuartos de ascensores y cuartos de maquinaria

  • (4) Ningun material que no tengaquever con el equipo del ascensor, sea guardado en los cuartos de maquinaria de ascensor, espacios de maquinaria del ascensor, el cuarto de control, el espacio de control ó el hueco del ascensor de tracción.

  • (5) La maquinaria del ascensor no es del tipohidraúlico.


8 15 7 1 proyecciones exteriores

8.15.7.1Proyeccionesexteriores

  • Al no ser que se cumplan con los 8.15.7.2, 8.15.7.3, or 8.15.7.4 , se instalaránrociadores en lasproyeccionesexterioresqueexcedan 4 pies (1.2 m) de ancho.


8 15 8 1 1 ba os de hoteles

8.15.8.1.1* - Baños de Hoteles

  • No se requiernrociadores en los bañosque no excede de 55 pies² (5.1 m²) y con construcción no combustible.


8 16 1 5 1 v lvulas de control de piso en edificios multi piso

8.16.1.5.1* Válvulasde control de piso en Edificios multi piso

  • Los edificiosquetengamás de dos pisos de alturadebentenerunaválvula de control de piso, unaválvula check, válvula de drenaje y switch de flujo por cadapiso.


8 17 2 5 1 v lvula check para conexiones de bomberos

8.17.2.5.1VálvulaCheck paraconexiones de bomberos

  • Unaválvula check listadadebeserinstalado en cadaconexión del departamento de bomberos y debeseraccesiblefacilimente.


8 17 5 1 3 mangueras

8.17.5.1.3Mangueras

  • Son necesarias?

  • Las conexiones de lasmangueras se suministrarán de la sigueinte forma:

  • (6) Conexiones de mangueras en un áreaqueno tienealmacenamientoy que no sean parte de un sistema standpipe, se le permitirá se suministre de la tuberia de los rociadores del techo en la mismaáreaque la conexión de la manguera.


Nfpa 13 actualizacion edicion 2013

Conexión Hidrantes de Manguera

LOOP PVC TUBERIA SUBTERRANEA

SISTEMA 1

SISTEMA 2

CASA DE MAQUINAS

LOOP PVC TUBERIA SUBTERRANEA

RISER

RISER

HIDRANTE DE BARRIL

SISTEMA 1

SISTEMA 2


Nfpa 13 actualizacion edicion 2013

Conexión Hidrantes de Manguera

SISTEMA 1

ESTRUCTURA

SOPORTERIA

MURO

RAMAL SISTEMA 1

SISTEMA 2

CABEZAL PRINCIPAL SISTEMA 1

TUBERIA DE HIDRANTE

CABEZAL SISTEMA 1

HIDRANTE CONECTADO DEL SISTEMA 2

HIDRANTE CONECTADO DEL SISTEMA 1

HIDRANTE DE MANGUERA

CABEZAL SISTEMA 2

TUBERIA DE HIDRANTE

HIDRANTE DE MANGUERA

SISTEMA 1

RISER 1

RISER 2

SISTEMA 2


Chapter 9 soporte bracing y con e xi n de un sistema de tuber a

Chapter 9 - Soporte, Bracingy conexiónde un sistema de tubería

  • 9.1.1.3Estructuras de soportecompartidasdebensercertificadas por un ingenieroprofesionalregistrado y uno de estos:

  • 9.1.1.3.1.1 Cincoveces la tubería de contra incendio con agua y lasotrassistemassoportadosmás 250 lb. o

  • 9.1.1.3.1.2 Cincoveces la tuberíade contra incendio con aguamás 250 lb. y 1.5 veceslasotrassistemassoportados.


9 2 3 2 5 9 2 4 7 el espaciamiento de los colgadores

9.2.3.2.5*/9.2.4.7* El espaciamiento de los colgadores

  • Unasección de tuberia no requiere un colgadorcuando la distanciacumulativa entre los colgadores en el ramal no excede el espaciadorequerido por la Tabla 9.2.2.1(a) y Tabla 9.2.2.1(b). Básicamentees 4.6 m portuberíaacero y 3.7 m portuberíaligera


D nde est el techo

Dóndeestáel Techo?

Cuáles la altura del edificio?

Cuáles la distancia del techo al deflector del rociador?

Cuáles el espaciolibre entre del techo y el almacenamiento?


D nde est el techo metal corrugado

Dóndeestáel techo? Metal corrugado

Para mayoresprofundidadesuse el punto mas superior.

3” ómenos de profunidad, use el puntomás inferior

12.1.3.4.1.1 Para techos de metal corrugadohasta 3” de fondo, el espaciolibre se mide de la punta de lo almacendo al puntomasbajo del techo. Para techos de masprofundidad, el espaciolibre se mide al puntomas superior el techo.


D nde est el techo aislamiento a

Dóndeestáel techo? Aislamiento (A)

(A) Para aislamientoqueestaadheridodirectamente al techoóestructura del techo, y estainstalado de maneraplana y paralelo al techoóestructura del techo, el espaciolibre se mide de la punta de lo almacenado a la parte inferior del aislamiento.


D nde est el techo aislamiento b

Dóndeestáel techo? Aislamiento (B)

12.1.3.4.1.2 (B) Para aislamiento que se instale de modo que cause una desviación ó que haga que el aislamiento se hunda del techo ó estructura del techo, el espacio libre al techo se medirá de la punta más alta de lo almacenado al  punto a la mitad de la distancia entre el punto más alto y el punto más bajo del aislamiento afectado. Si la desviación ó hundimiento del aislamiento excede las 6 pulgadas (152 mm), el espacio libre al techo se medirá de lo almacenado al  punto más alto del aislamiento.


D nde est el techo aislamiento b1

Dóndeestáel techo? Aislamiento (B1)

Se hunde 6” o menos

La mitad de estadistancia

(B) Para aislamientoque se desviaó se hunde . . . El espaciolibre se midedesde la punta de lo almacenado a un punto entre el puntomás alto y el puntomásbajo. La mitad de la distancia de la deflexión del puntomás alto del aislamiento al puntomásbajo.


D nde est el techo aislamiento b2

Dóndeestáel Techo? Aislamiento (B2)

Espacio mayor a 6”

Distancia de deflexión

(B)…Si la deflexionóhundimiento en el aislamientoexcede de 6 pulgadas (152 mm), el espaciolibre se mide del puntomás alto de lo almacenado hasta el puntomás alto del aislamiento.


Techos con alturas excesivas

Techos con alturasexcesivas

12.1.3.4.6  Donde el espaciolibreexcede los 3.1 m (10 pies) para la sección 17.3, la protección se basará al proveer un nivel de rociadores en rack de respuestarápidasuplementales, ubicadosdirectamenteabajo de la hileramásalta y en cadaespaciointerseccional(flue space).

O protege hasta la alturaqueresulta en un espacio no més de 3.1 m.


12 1 4 ventiladores de alto volumen velocidad baja hvls

12.1.4 Ventiladores de alto volumenvelocidadbaja (HVLS)


12 1 4 ventiladores hvls alto vol men baja velocidad

12.1.4* Ventiladores (HVLS) Alto VolúmenBaja Velocidad

12.1.4* La instalación de ventiladores HVLS en edificiosquecuentan con rociadores, incluyendorociadores ESFR, cumplirán con lo siguiente:

(1) El diametromáximo del ventilador sera de 24 pies.

(2) El ventilador HVLS sera aproximadamentecentrado entre 4 rociadoresadyacentes.

(3) El espaciolibre vertical del ventilador HVLS al deflector del rociador sera de 3 pies minimo.

(4) Todos lo ventiladores HVLS estaránconectadosparasuapagadoinmediato al recibir la señal de flujo de agua del sistema de alarma de acuerdo a los requerimientos de NFPA 72.

High Volume Low Speed (HVLS) Fans.


Densidad m nima para almacenes

Densidadmínimaparaalmacenes

12.7.7.3  El diseñomínimo de densidad de cualquiersistema de rociadores en un almacen de almacenamiento sera no menos de 0.15 gpm por pie2después de hacertodos los ajustes.


Margen para mangueras y duraci n en almacenes

Margenparamangueras y duraciónen almacenes


Tarimas desocupadas arriba de puerta

Tarimasdesocupadasarriba de puerta

TechoAltura

AlmacenamientoAltura

12.12.3.3 Cuando se almacenentarimasencima de puertas, la altura de sualmacenamiento y altura del techo se calcularadesde la base del area de almacenamientoaplicando el criterio de protecciónreferenciado en la Sección 12.12


Cap tulo 13 normas para almacenamiento de miscelaneos

Capítulo13 – Normasparaalmacenamiento de Miscelaneos

CurvasmodificadasDensidad / Area


Ubicacion de rociadores in rack

Ubicacion de Rociadores In-Rack

13.3.4 Ubicacion de Rociadores In-Rack

13.3.4.1 Cuando se requierenrociadores in-rack paraalmacenamiento de miscelaneos, seráncolocados en ó por encima de la mitad de la altura del nivel del rack.


Ubicaci n de rociadores in rack

Ubicaciónde rociadores In-Rack

13.3.4.2 Cuandorociadores in-rack seanrequeridosparaalmacenmientomiscelaneo, se ubicarán:

  • Longitudinalmente en los espaciosventilados

  • Colocados en los cruces con espaciosventiladostransversales (flue spaces).

  • Máximo de 12 pies de espaciadopara la mercanciaClaseI, II, y III

  • Maximo de 8 pies de espaciadoparamercanciaClaseIV óplasticosGrupo A


Ubicaci n de rociadores in rack1

Ubicaciónde rociadores In-Rack

13.3.4.3 Donde se requiererociadores in-rack paraalmacenamientomiscelaneo y no existeventilastransversales, los rociadores se instalarán en espacioslongitudinalesventiladosque no excedan de lasdistanciasmaximas en la Sección 13.3.4.2.


Nfpa 13 actualizacion edicion 2013

Rociadores In-Rack


Nfpa 13 actualizacion edicion 2013

Interconexión al sistema

Ramal

  • Interconexión al sistema

  • Ventilación o Chimenea Vertical

  • Vista Isométrico


Nfpa 13 actualizacion edicion 2013

Rack

Ventilación o Chimenea Vertical

  • Hidrante viene de sistema

  • Isométrico

  • Losa

  • Ventilación o Chimenea Vertical

  • Rack

  • Sistema / Tubería / Sprinkler

  • Ramal

  • Ventilación o Chimenea Vertical

Ventilación o Chimenea Horizontal

Ventilación o Chimenea Horizontal

  • NPT

Sección Longitudinal


Cap tulo 16 mercancia clase i iv almacenado en racks

Capítulo16 MercanciaClase I – IVAlmacenado en Racks

  • Se cambiaron los requerimientos de diseño de rociadores In-rack a la sección de diseño de techo

Reorganización


Cap tulo 16 mercancia class i iv almacenado en racks

Capítulo16 Mercancia Class I – IVAlmacenado en Racks

Versección 12.8.6 paramargen de mangueras y duración del suministro.

NUEVO MENSAJE

16.1.6.6 La demanda de aguapararociadores in-rack no tienequeestarbalanceada a la demanda de rociador de techodonde se instalenrociadoresadicionales de caraabajo de cadaanaquelsolido en lassubientesverticales de los racks y los rociadores in-rack estancalculados a descargar por lo menos 60 gpmde 8 rociadores.


Cap tulo 16 mercancia class i iv almacenado en racks1

Capítulo16 Mercancia Class I – IV Almacenadoen Racks

NUEVO LENGUAJE

16.1.7 ContenedoresDescubiertos. La protecion de contenedoresdescubiertos se encuentrafuera del alcance del Capitulo 16. Versección C.12


Cap tulo 17 mercancia de plastico y hule almacenado en racks

Capítulo17 Mercancia de Plastico y Hulealmacenadoen Racks.

Reorganizacióncompleto.

Combinado los criterios de techo con in-rack.

Ahora - Hay protecciónparaplasticos

Grupo A no expendidaexpuestos.

Sigue - No hay proteccionparaplasticos

Grupo A expandidaexpuestos.


Protecci n particular para tiendas tipo caja grande ej sams

ProtecciónParticular paraTiendastipoCaja Grande (ej. Sams)

17.2.4.1.2 Un sistema de tubohúmedoque sea diseñadoparasuministrar:

0.6 gpm/pie2sobre2000 pie2 (186 m2)

o

K-14.0 (200) ESFR’s a 50 psi (3.5 bar),

o

K-16.8 (240) rociadores a 32 psi (1.7 bar),

o

K-25.2 (360) ESFR’s a 15 psi

Y cumplen con otras 10 condiciones .


Cap tulo 21 dise os alternativos para los cap tulos 12 al 20

Capítulo21 Diseñosalternativospara los Capítulos12 al 20

  • Si lasalternativas de proteccion de Capítulos 12 a 20 no son suficienteparati, yatienennuevaopción.

  • Completamentenuevo y basado en pruebas de fuegosactuales (full-scale fire tests).

  • La intenciónestener los fabricantes a hacerlaspruebas y presentar al comitéparasuaprobación.


Cap tulo 21 algunas normas para nueva tecnolog a

Capítulo21 Algunasnormasparanuevatecnología

21.1.7 Las instrucciones al fabricanteparaestosrociadoresespecificarán . . . Por lo menos lo siguiente:

(1) Mercanciaómercancias a proteger (Riesgo)

(2) Los arreglos de almacenamientopermitido

(3) Lineamentos de instalación . . . Obstrucción y techo . . . Limitaciones

(4) Alturas máximas del techo y almacenamiento… presionesminimas de operación . . . Número de rociadoresque se requieren . . . En el cálculo

(5) Margen del chorro de la manguera y duración

21.1.8 El número de rociadores a considerar en el diseño del sistema de rociadoresserá el resultado del peorcasoobtenido de la prueba de incendio de gran escalaaumentado por un mínimo del 50 por ciento.


Cap tulo 21 algunas normas para nueva tecnolog a1

Capítulo21 Algunasnormasparanuevatecnología

21.1.8.1 Independientemente de la cantidad de rociadoresqueoperarondurante la prueba a gran escala del peorcaso, la cantidad en la demanda no sera menor a lo siguiente:

(1) 12 rociadorespararociadores de coberturaestándard

(2) 8 rociadorespararociadores de coberturaextendidabasado en espaciado de 12 pies por 12 pies.

(3) 6 rociadorespararociadores de coberturaextendidabasado en espaciado de 14 pies por 14 pies.

21.1.8.2 Unavezque se ha establecido la cantidad de rociadoresparaunademanda de area, el area mínima de operaciónno serámenor a 768 pies2 (71 m2).


Cap tulo 21 aplicando las nuevas normas

Capítulo21 Aplicandolasnuevasnormas


23 4 4 5 4

23.4.4.5.4

  • Dondeexistanrociadoresinstaladoarribaó por debajo de un techoódonde mas de dos areas son suministrados de un juegocomún de ramales, los ramales y el suministro se calcularáparaproveer la demandamásalta de de agua.


23 4 4 2 m todo de rociadores cmsa

23.4.4.2 Métodode rociadores CMSA

23.4.4.2.1 Para rociadores CMSA, el area diseñadadebeser un área rectangular teniendounadimensiónparalelo a los ramales por lo menos 1.2 veces la raízcuadrada del áreaprotejida por la cantidad de rociadoresincluídos en el area diseñada.

El area diseñadaprotejida por la cantidad de rociadores a usarse por la regla de 1.2 sera basada en el área maxima permitida por rociador.


Nfpa 13 actualizacion edicion 2013

  • Ramal 1

  • Ramal 2

  • Ramal 3

  • Estructura

  • 60,90m

  • Sprinkler

  • Cabezal

  • Muro

  • Área calculada 1500pies²

  • Espaciamiento 13 pies x 10 pies = 130 pies

  • 1500 = 1154 --- Calcular 12 rociadores

  • 130

  • 1.2 1500 = 3.58

  • 13

  • Utilice cuatro rociadores/tuberías

  • 1”

  • 1”

  • 1”

  • 1 ¼”

  • 1 ¼”

  • 1 ¼”

  • Ramal

  • 1 ½”

  • 1 ½”

  • 1 ½”

  • 39,62m

  • 2 ½ ”

  • 2”

  • 2 ½ ”

  • 2 ½ ”

  • 2 ½ ”

  • 3”

  • 3”

  • 3”

  • 3”

  • 3”

  • 1 ½”

  • 1 ½”

  • 1 ½”

  • 1 ¼”

  • 1 ¼”

  • 1 ¼”

  • Grupo I 1500pies²

  • Densidad 0.15 gpm/pie²

  • de la Figura 11.2.3.1.1

  • 1”

  • 1”

  • 1”


Nfpa 13 actualizacion edicion 2013

  • 23.4.4.6.3.1 No debeserincluido en los cálculoshidraúlicos los rociadoresabajo de obstrucciones.

  • 23.4.4.6.3.2 Donde la tubería a los rociadoresbajoobstruccionessiguen el mismo patron de medidas de los ramales, no se necesitamayorescálculoshidraúlicospara los rociadoresbajoobstrucciones.