Transient Overvoltage Surge Suppression Overview for ITS Applications Paul Saa BSEE, MSISE, MBA

Transient Overvoltage Surge Suppression Overview for ITS Applications Paul Saa BSEE, MSISE, MBA Engineering Sales Manager Engineering Labs Quality Manager Advanced Protection Technologies (800) 237-4567. What Causes Surges/Transients?. Lightning Switching:

kato
Download Presentation

Transient Overvoltage Surge Suppression Overview for ITS Applications Paul Saa BSEE, MSISE, MBA

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Transient Overvoltage Surge Suppression Overview for ITS Applications Paul Saa BSEE, MSISE, MBA Engineering Sales Manager Engineering Labs Quality Manager Advanced Protection Technologies (800) 237-4567

  2. What Causes Surges/Transients? Lightning Switching: Load Switching – (Motors, Large Reactive Loads) Source Switching (Smart Grid, Gensets) Arcing/Flashing Animals Unexpected Internally generated surges: ≈70% Externally generated surges: ≈30% In outdoor environment, this ratio probably reverses 2

  3. MOV - Metal Oxide Varistor Varistor - variable resistor Semiconductor; generally zinc oxide Connects parallel to load (not series) Thickness determines clamping voltage Diameter determines current capacity MOV symbol

  4. SPD Operation Load 1 Load 2 Load 3 MOV/SPD tries to: 1.) Send surge away (to ground) 2.) Acts as a momentary ‘short circuit’ ‘short circuit’ ≈ voltage equalization ≈no overvoltage ≈ protected load

  5. Safety, UL 1449-3 & NEC • TVSS/SPDs arguably the most regulated electrical product category in the 2000’s • UL 1449-2 (Aug 1998) • 2002 NEC Article 285 • 2005 NEC Article 285 • UL 1449-2.5 (Feb 2007) • 2008 NEC Article 285 • UL 1449-3 (Sept 2009) • 2011 NEC Article 285 SPD Surge Arresters TVSS • Safety evolved quickly as the body of knowledge grew • UL 1449 Plays Huge Role in Surge Industry • Much More Than a Safety Standard • Perform Multiple Performance Tests • UL uses for internal UL 96A Lightning Protection Master Label Eval • Appears that Traffic/DOT/ITS were left out of the loop

  6. Typical Sequence of SPD Failure – Safety & UL • System-level Sustained Overvoltage – Not From Surges! Voltage exceeds MCOV – as little as 2-3 cycles • MOV attempts to protect • MOV fails towards short circuit • Follow-on/fault current causes MOV to catastrophically overheat MOV/SPD Load If extremely rapid overheat, and/or faster than OCP can clear – can rupture If overheats ‘slowly’ – can catch fire

  7. UL 1449 Safety Testing • MOVs/SPDs have multiple failure scenarios • UL tests at L-L voltage (i.e., 208V, 480V, 600V, etc.) • UL limits fault current (i.e., 0.5A-200kA) • UL tests one mode at a time Techno-babble For Engineers, By Engineers Trying to prevent these types of failures Individual tests at 0.5A, 2.5A, 5A, 10A, 100A, 500A, 1000A & SCCR Fault Current Levels 7

  8. Noise Filtering Caution: EMI/RFI Filtering was oversold many years ago using scare tactics, hocus-pocus & games with oscilloscopes Utility feeds simply do not have that much noise (more are underground now) Most EMI/RFI noise is self-generated Noise is relatively low amplitude and tends to dissipate Higher frequency noise goes through the air bypassing copper wire & SPDs Multiple ways of filtering Parallel connected capacitive filters – no major side effects unless the caps are very large Series connected inductive filters – Significant issues: Load must go through them, prone to overheating, UL regulations became very tough, many series SPDs are no longer UL listed and pose additional threats beyond the filter During ground strikes, energy can attempt to leave via the service entrance, back towards the utility. The same physics that prevents noise from entering, prevents surge energy from leaving. The filter traps energy in your equipment! These have fallen out of favor in other industries. Sinewave tracking is a fancy name for modulating high frequency noise on a 60 Hz carrier. (This is nothing new and is how radio works!) 8

  9. SPD Application Surge Environment in Traditional Structures is Well Defined by ANSI/IEEE & ANSI/UL StandardsDOT & Outdoor Applications Appear to Differ Based on Increased Likelihood of Lightning Activity and Ground Reference Issues

  10. IEEE C62.41.2-2002 Categories & Surge Environment Surge Environment based on Location within electrical distribution system Cat C – 10kA Cat B – 3kA Meter IEEE Categories Cat A – 0.5kA Svc. Disc. Panel 10m (30feet) Trans

  11. Surges in DOT Environments Transient overvoltages are not limited to utility or power conductors An Instantaneous Ground Potential Change is Also a Surge Lightning strike to earth-grounded pole raises Ground Potential, also causing Transient Overvoltage On Power Conductor Surge or Transient Overvoltage On Ground Conductor 11

  12. Traffic Applications Different Due to Multiple Threats: Surge To Service Entrance: 1.) Surge Hits Power/Line 2.) Traditional Building? 3.) Inductance Limits Propagation 4.) IEEE C62.41 Categories C, B & A (enter for animation 1) Surge Near Load: 1.) Surge Hits Ground/Grounded Equip. 2.) Elevated NON-Traditional Structure 3.) Inductance Limits Propagation 4.) IEEE C62.41 Categories C, B & A? (enter for animation 2) • Takeaways: • Multiple Threats • Plenty of Unknowns! • Need Additional • Modes of Protection Amber Alert How Much to Ground? How Much to Power Lines? Meter Cabinet Cat C – 10kA Svc. Disc. Cat B – 3kA 10m (30feet) Cat A – 0.5kA Trans ??Cat C – 10kA?? Cat B – 3kA? Power System Ground Pole Ground 12

  13. Modes of Protection • Different ways to configure protection within SPDs • MOVs equalize potential across either side of MOV • Various ways to connect MOVs • L-N • L-G • N-G • L-L

  14. Different Modes of Protection: Service Scenario Assumes (Split Phase): 1.) Surge Is From Outside 2.) SPD near Service Entrance or Separately Derived System 3.) Propagation, Return Paths and Ground are Ideal 4.) SPD chops off surge and sends it to Ground (Enter for Animation) Phase A SPD Transformer Impedance N A-N Ground Could have L-G protection too, which is functionally the same as L-N at a service entrance because N and G are bonded together Earthed

  15. Different Modes of Protection: Downstream or Outdoor (Split Phase) 1.) Surge Is From Outside to Ground or Grounded Enclosure or Pole 2.) Surge might go towards Ground, but inductance will limit propagation. And/Or, there will be Ground Potential Rise. This will have the effect of ‘trapping’ the surge near the load 3.) SPD will equalize potentials among Phases, Neutral and Ground (Enter for Animation) SPD A-G Phase A Neutral N-G C-G Ground Assumes L-N, L-G and N-G protection A service entrance style SPD with L-N only has almost no chance of protecting. Modes of Protection Are Important!! (Gee, I had an SPD, but still lost my equipment.)

  16. Consider: There is ongoing perception that ‘downstream’ applications can get by with modest SPDs on the presumption that the surge environment is less hostile. At Service Entrance: Traditional surge protection makes sense. Because electrical system references ground at the service, L-N protection is generally adequate (and is effectively the same as L-G protection). Downstream: Load is subject to reduced amplitude surges from service. I.e., L-N protection. In addition, depending on height and situation, load could be More vulnerable due to induced lightning, which is poised to enter or couple via ground or grounded enclosure. Thus, protecting G-L & G-N makes sense. (This is more commonly referred to as L-G and N-G.) Unfortunate reality is that ‘exposed’ downstream applications probably need a more feature-laden SPD.

  17. Specification Suggestions: UL 1449-3 Listed (for ease of review) UL 20kA I-n rating (Used by UL 96A – biggest, toughest rating) UL VPRs of 700V or less for L-N, L-G & N-G (low clamps) Minimum MOV size of 32mm round (more robust MOVs) Diagnostic Monitoring for Every MOV UL declared MCOV of 150V (prevents game-playing & early failure) No Gas Tubes or Spark Gaps (prevents high clamps) SCCR =>50kA (safety) Thermal Disconnectors required for all MOVs (safety) 50kA per mode, 100kA per phase (generally adequate)

  18. Advanced Protection Technologies(800) 237-4567 Thank you for your time APT offers no-cost detailed training for FL PE and/or EC credits. We also welcome tours of our facilities & labs in Clearwater