Rack cooling in building 904

Rack cooling in building 904. Primary side. Secondary circuit. 13/18oC. Total flow= 21.5m3/h, DN80. Chiller side. DP=1bar. 9 rooms 50kW. Total flow=14.35m3/h DN65. Flow per room= 0.8m3/h, 5.5kW, DN25. 45 racks, Max Power per rack 10kW, 1.4m3/h DN25.

Download Presentation

Rack cooling in building 904

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Rack cooling in building 904

  2. Primary side

  3. Secondary circuit 13/18oC Total flow= 21.5m3/h, DN80 Chiller side DP=1bar 9 rooms 50kW Total flow=14.35m3/h DN65 Flow per room= 0.8m3/h, 5.5kW, DN25 45 racks, Max Power per rack 10kW, 1.4m3/h DN25