Exercise Ducting Design. Determine type and number of resisters Decide on the air distribution Decide on velocity and noise criteria Find worst case scenario Duct Sizing method selected: equal Friction. Data. 10m. 7m. Airflow =3214 m³/h = 896 l/s. H = 3,5 m. Trox Air Distribution.

Download Presentation

Exercise Ducting Design

An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -

Presentation Transcript


Exercise ducting design

Exercise Ducting Design

  • Determine type and number of resisters

  • Decide on the air distribution

  • Decide on velocity and noise criteria

  • Find worst case scenario

  • Duct Sizing method selected: equal Friction

Daikin Europe, Consulting Sales Section


Exercise ducting design

Data

10m

7m

Airflow =3214 m³/h = 896 l/s

H = 3,5 m

Daikin Europe, Consulting Sales Section


Exercise ducting design

Trox Air Distribution

Daikin Europe, Consulting Sales Section


Exercise ducting design

Trox Air Distribution

Daikin Europe, Consulting Sales Section


Exercise ducting design

Trox Quick Selection

Daikin Europe, Consulting Sales Section


Exercise ducting design

Position and type of resisters

10m

How many resisters?

L < 1,5 * W

10 < (1,5 * 7 = 10,5)

L < 3 * H

10 < 3 * 3,5 = 10,5

in theory, 1 resister could do

but the airflow = 896 l/s is

TOO BIG for 1 resister

7m

For a better air distribution, to avoid draft and noise, we select 8 diffusers

H = 3,5 m

Airflow=896l/s

Daikin Europe, Consulting Sales Section


Exercise ducting design

A

C

B

C

Air Distribution

10m

8-off TDF500’s

For 112l/s

7m

Airflow=896l/s

Daikin Europe, Consulting Sales Section


Exercise ducting design

Duct Layout

Daikin Europe, Consulting Sales Section


Exercise ducting design

Duct Layout

Daikin Europe, Consulting Sales Section


Exercise ducting design

Duct Layout - results

Daikin Europe, Consulting Sales Section