ezPAC SA320/330. April 2011. SATEC 25 years of Innovation in measurement & management of Energy and Power Quality. The Full Range of Electricity Management Solutions for Every Application. PAS. eXpertpower™ Server ( SaaS ). eXpertpower™ Server (Pro Edition). Internet. eXpertpower™. LAN.

Download Presentation

ezPAC SA320/330

An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -

Presentation Transcript


Ezpac sa320 330

ezPACSA320/330

April 2011


Satec 25 years of innovation in measurement management of energy and power quality

SATEC25 years of Innovation in measurement & management of Energy and Power Quality


Ezpac sa320 330

The Full Range of Electricity Management Solutions for Every Application

PAS

eXpertpower™ Server (SaaS)

eXpertpower™

Server (Pro Edition)

Internet

eXpertpower™

LAN

ETC2002

RS232/422/485, Profibus, TCP/IP, Dialup modem, GPRS, RF

Modbus RTU, ASCII, DNP3.0, Modbus/TCP, DNP3/TCP, IEC 61850

PM130 PLUS

BFM136

C192PF

PM172

PM296

PM174/5

EM720

EM920

ezPAC

Substation

Automation

Asset Management

Power Measurement

Fault Recording

Energy Efficiency & Cost Allocation

Revenue Metering

Energy Management & Billing

Smart Grid & Demand Response

Power Quality Analysis

Multi-Tenant Submetering

UTILITIES & RENEWABLE

COMMERCIAL & INDUSTRIAL

ALL


Ezpac sa320 330

Universities

Gas

Pharmaceutical

Transportation

Transmission

Data Centers

Supermarkets /Wholesale

Banks

Process Industry

Generation

OEM

COMMERCIAL

INDUSTRIAL

UTILITIES

Mining

Telecom

Hi-Tech

Automotive

Distribution

Sports

Semiconductors

Residential


Ezpac sa320 3301

ezPAC SA320/330

6-in-1 solution:

  • Revenue Metering

  • Power Quality

  • Distributed Fault Recorder

  • Sequence of Events (SoE)

  • Backup Protection Equipment

  • Devices Control


Ezpac movie

ezPAC Movie


Substation automation

Substation Automation

  • Relay Target Information

    • Get all of the information available from a digital relay without replacing the electromechanical one

  • Add-On Protective Relaying Backup

    • Under / over frequency relay

    • Automatic load shed & restore (0.01 Hz with adjustable time delay)

    • Reclosing relay

    • Multi-shot automatic reclosing

    • Synchro-check and LLDB/LBDL supervision

    • Permit / block reclose

    • Phase angle, slip frequency, LLDB/LBDL control

    • Time over-current relay backup

    • Back up prime TOC relay curve with up to 32 current magnitude and duration set-points

  • Various Communication protocols

    • Modbus

    • DNP3.0

    • IEC 61850


Sequence of events soe

Sequence of Events (SoE)

  • Four types of events:

    • digital input

    • relay output

    • Fault

    • Set-point

  • Each input point is programmableto be NO or NC

  • Programmable status words

  • Programmable De-bounce times 1-256 msec

  • Up to 160 discrete inputs – wet or dry contacts


Fault recorder

Fault Recorder

  • 4 measured currents

  • IRIG-B time synchronization

  • Up to 20 minutes of continuous recordingwith 256 MB memory

  • Programmable fault thresholds and hysteresis

  • Up to 150 amps fault currents (30 x In)

  • Zero-sequence currents and voltages

  • Current and voltage unbalance

  • Under-voltage, neutral current

  • Ready-to-use fault reports—fault currents magnitude and duration, coincident volts magnitude, faultwaveforms and RMS

  • Distance to fault calculation

  • Multi-feeder (up to 3) fault recorder

  • Waveforms from 2 separate locations (via PAS)


Power quality recorder

Power Quality Recorder

  • Class A IEC 61000-4-30 Power Quality analysis:

    • Sags/swells (dips/over-voltages), interruptions, frequency variations, Flicker, voltage unbalance, harmonic and inter-harmonic voltages

  • Programmable thresholds and hysteresis

  • Built-in EN50160 statistics & reports

  • Redundant auxiliary power supply for recording major dips & interruptions

  • Harmonics & inter-harmonics according to IEC 61000-4-7

  • Directional power harmonics and power factor phasors

  • THD, TDD and K-Factors

  • Symmetrical components

  • Flicker measurement according to IEC 61000-4-15

  • Selectable sampling rate up to 256 samples/cycle

  • Event recorder for logging internal diagnostic events, control events and I/O operations

  • Waveform & data recorder


Transient recorder

Transient Recorder

  • Transient pulses as short as 20μs at 50 Hz (17μs at 60 Hz)

  • Up to 1024 samples per cycle

  • Amplitude relative to ground as per EN 50160 (4 channels)

  • Up to 2kV measurement, 6kV withstand


Display options

Display Options


Case study substation automation system sas

Case StudySubstation Automation System (SAS)

  • SATEC products (ezPAC, PM175 and PM130) are the heart of the substation automation system (SAS) solution provided by NPT throughout the entire Russian Federation

  • Two configurations:

    • Comprehensive for220 and 750kV

    • Standard for 6, 10,35 and 110 kV


Key design concepts

Key Design Concepts

  • SATEC IEDs provide protection, automation, measurement and control functions

  • SCADA-system for operational control

  • Open system concept reduces dependency on vendors

  • Standard protocols for IED and HMI communication

  • Wide use of Factory Acceptance Testing (FAT)

  • Integration of substation protection and automatics into control software


Bay controllers rtu sa300 330

Bay controllers RTU SA300-330

SATEC ezPAC SA330 bay controllers are used on lower level to collect digital, analogue information as well as to control switchgear.


Sa330 functions

SA330 functions


Pm1 75

PM175

  • Power Quality Analysis (EN50160, IEEE 1159 and GOST 13109-97)

  • Time Of Use (TOU)

  • Accuracy Class 0.2S

  • RTC and 10-year calendar

  • Full galvanic isolation

  • Non-volatile memory

  • Registration of parameters on set-point or time


Ezpac iec 61850 protocols

ezPAC IEC 61850 Protocols

  • IEC 61850-7-2,3,4

    • Basic communication structure for substation and feeder equipment – Abstract communication service interface (ACSI), Common Data classes, Compatible logical node classes and data classes

  • IEC 61850-8-1

    • Specific Communication Service Mapping (SCSM) – Mappings to MMS (ISO 9506-1 and ISO 9506-2) and to ISO/IEC 8802-3

  • IEC 61850-10

    • Conformance testing


Implementation in npt expert sas

Implementation in NPT Expert SAS

IEC 61850 configurator and system driver allow:

  • IED configuration reading

  • Data receiving via read requests and via event reports referenced by Report Control Blocks

  • Files downloading (in particular COMTRADE files)

  • Data Sets configuration

  • Report Control Blocks and GOOSE Control Blocks configuration


Satec empowering the smart grid www satec global com

SATECEmpowering the Smart Gridwww.satec-global.com


  • Login