An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. MINISTERO DELL’INTERNO DIPARTIMENTO DEI VIGILI DEL FUOCO, DEL SOCCORSO PUBBLICO E DELLA DIFESA CIVILE DIREZIONE CENTRALE PER LA FORMAZIONE An Application In Fire Safety Engineering C. Barbera, A. Bascià, G. Di Salvo, A. Galfo, R. Lala, S. Lucidi, D. Maisano, G. Mancini, V. Puccia, F. Vorraro I e II Corso Direttori Antincendi Istituto Superiore Antincendi Roma Fire Service College Moreton-in-Marsh

  2. FIRE SAFETY Deterministic Approach Fire Engineering Approach Laws and regulations Fire Models FIRE ENGINEERING APPLICATIONS • In absence of specific laws and regulations • When specific laws and regulations can’t be complied with • Fire investigation • High risk activities (safety report)

  3. FIRE ENGINEERING: OPERATIVE VS. NUMERICAL MODELS Fitted parameters models (or operative models or zone models) • They solve exactly a set of simplified semi – empirical equations (momentum, energy, mass) • The computational domain is divided into mixed zones, where intensive properties (i.e., P, T, concentrations) are assumed to be homogeneous • They yield temperature and gases and smoke concentration in each zone Distributed parameters models (or numerical models or field models) • They solve numerically (i.e., approximately) a set of exact balance equations (momentum, energy, mass) • The computational domain is meshed by means of a calculation grid, whose refinement affects the accuracy of the result • They yield temperature and concentration profiles as a function of time and space

  4. equivalence factor AN OPERATIVE MODEL: CFAST Hypotheses • Confined fires • Two mixed volumes: upper layer (hot layer) + lower layer (cold layer) • tcomb << t = V / Q ventilation controlled fire Controlling parameters • S: stoichiometric ratio air / fuel • m: specific combustion rate [=] kg m-2 s-1 • A: compartment section [=] m-2 • me: air mass flow rate [=] kg s-1 • Ventilation factor, • Heat Release Rate (HRR) Correlation equation • X: output variable • X0 : X evaluated in unconfined fires • a, b, z: correlation parameters

  5. mass equation pressure equation energy equation volume equation density equation temperature equation AN OPERATIVE MODEL: CFAST Equations

  6. AN OPERATIVE MODEL: CFAST Inputs • Geometry (compartment dimension, ventilation surface, etc.) • Material properties (thermal conductivities, etc.) • Fire geometry and position • HRR vs. time curve Outputs • Average temperature in both layers • height of layer interfacies • O2 concentration • CO concentration • visibility index • mass and enthalpy exchange rates

  7. A NUMERICAL MODEL: FDS (Fire Dynamics Simulator) Hypotheses • Both confined and unconfined fires • Rate of Heat Release (HRR) not depending on O2 concentration Equations • Mass conservation • Momentum conservation (three scalar equations) • Constitutive law (nine scalar equations) • Energy conservation • Chemical species conservation

  8. A NUMERICAL MODEL: FDS (Fire Dynamics Simulator) Inputs • Geometry (compartment dimension, ventilation surface, etc.) • Material properties (thermal conductivities, etc.) • Position and characteristics of ignition sources • Rate of Heat Release (HRR): depends on fuel and combustion conditions Outputs • Pressure, temperature, velocity and chemical species concentrations as a function of time and space • Fluxes and exchange rates

  9. COMPUTATIONALDOMAIN (D.M. 16/2/1982 All.I – act. 87) Plan Cross Section North View South View

  10. COMPUTATIONALDOMAIN (D.M. 16/2/1982 All.I – act. 87) • Geometry • Two compartments • Ventilation surfaces (2 windows + 1 external door + 1 internal door) • Material properties • Concrete walls (r = 2100 kg m-3; cp = 0.88 kJ kg-1 K-1; kT = 1 W m-1 K-1) • Fire geometry and position • 7 cellulosic material stacks • Heat Release Rate (HRR): • depends on fuel and combustion conditions

  11. HRR [=] MW t [=] s CFAST NUMERICAL RUNS t0 t1 t2 t3 Run 1: sensitivity analysis on the role of a

  12. A TYPICAL CFAST OUTPUT WINDOW Profiles Values

  13. a = 0.009 kW s-2 a = 0.0069 kW s-2 a = 0.02 kW s-2 a = 0.011 kW s-2

  14. OUTPUTS OF CFAST RUN 1 • h1: interfacies heightin compartment 1 • h2: interfacies heightin compartment 2 • Tu1: maximum temperature in the upper layer in compartment 1 • Tl1: maximum temperature in the lower layer in compartment 1 • Tu2: maximum temperature in the upper layer in compartment 2 • Tl2: maximum temperature in the lower layer in compartment 2

  15. CFAST NUMERICAL RUNS Run 2: sensitivity analysis on the role of ventilation factor

  16. OUTPUTS OF CFAST RUN 2 • t600: t corresponding to Tu = 600 °C

  17. FDS NUMERICAL RUNS Operative assumptions Distributed parameters model Fire load can be splitted! 7 stacks with HRR = HRRmax / 7 Fire starts from stack 1 Each stack burns when T ≥ 200°C (ignition temperature) Run1: without sprinklers Run 2: with sprinklers

  18. OUTPUTS OF FDS RUN 1 Ceiling temperature Ceiling temperature vs. time t (T1max) = 338 s Ceiling temperature distribution at t = 338 s

  19. OUTPUTS OF FDS RUN 1 Smoke propagation: even though at t = 180 s only one stack burns, smoke invades both the compartments.

  20. FDS NUMERICAL RUN 2 Sprinklers lay-out Sprinklers characteristics • Operating pressure: 0.483 bar • K: 79 l min-1 bar -1/2 • Activation temperature: 74°C • RTI (Response Time Index): 110 (m·s)1/2

  21. Synoptic Tc1 Tc7 Tc4 OUTPUTS OF FDS RUN 2 Ceiling temperature

  22. OUTPUTS OF FDS RUN 2 Smoke propagation and sprinkler activation: the first sprinkler activates at t = 111.6 s… … and the last one at t = 330 s

  23. CONCLUSIONS… • Zone models are very sensitive to ventilation factor and HRR vs. time curve (controlling parameters): they are quick and simple • Field models allow a more realistic and flexible problem description: accurate input estimation is required and simulations are very time expensive • T vs. t curves yielded by the two models are different but similarly shaped … AND FURTHER INVESTIGATIONS • A set of numerical runs has to be carried out in order to gain a deeper insight in T vs. t curves • A comparison between model prediction and deterministic approach results can be performed