AutroSafe SelfVerify Interactive Fire & Gas Detection System. ID: ASAFE_intro_Eng, 2007-09. Overview and a brief introduction of;. Reference to traditional systems The AutroSafe system Background for development – IEC EN54 AutroSafe terminology Features introduction SelfVerify

Download Presentation

AutroSafe SelfVerify Interactive Fire & Gas Detection System

An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -

Presentation Transcript


Autrosafe selfverify interactive fire gas detection system l.jpg

AutroSafe SelfVerifyInteractive Fire & Gas Detection System

ID: ASAFE_intro_Eng, 2007-09


Overview and a brief introduction of l.jpg

Overview and a brief introduction of;

  • Reference to traditional systems

  • The AutroSafe system

  • Background for development – IEC EN54

  • AutroSafe terminology

  • Features introduction

  • SelfVerify

  • System Integrity (SIL)

  • Reliability

  • Communication

  • Software Tools


Traditional analogue addressable fire alarm systems l.jpg

BRANN

Traditional Analogue Addressable Fire-Alarm Systems

BU-100

5th Deck

BU-70

4th Deck

BU-100

3rd Deck

BU-70

2nd Deck

BU-100

LER

CCR

1st Deck

Utility Deck

DYNAMIC FILTER PROCESS


Autrosafe selfverify interactive fire gas detection system4 l.jpg

AutroSafe SelfVerify Interactive Fire-& Gas Detection System

Corridor

LER

5th deck

Corridor

LER

4th deck

Corridor

LER

3rd deck

Corridor

LER

2nd deck

CCR

LER

1st deck

AUTROLON

Utility-deck


Traditional f g system l.jpg

Traditional F & G System

AutroSafe

DCS system

Operator Station

Standard Loop Units

Node 1

Redundant Network

Node 2

Node 3

Node 4

Node 5

Node 6

EX Loop Units

AutroPoint

AutroFlame

Third party detectors

Kidde Fenwal Analaser II

Third party detectors

AutroPathHC600 RX

Simrad

AutroPathHC600 TX

AutroFlame CCTV


Autrosafe ifg l.jpg

AutroSafe Panel

(TCP/IP)

AutroOS

AutroSafe Panel

AutroSafe IFG

ModBus

To Process

AutroSafe Controller

Control

System

Al_Com

AutroLON

loop

Standard AutroSafe

loop units

Information/

Barrier unit

Repeater

BZ-500

panel

BSD-340

AutroFieldBus

AutroSafe

EX loop units

BSD-321

PowerLoop

AutroFlame

Video

X33/1 PL

BN-342

(4-20mA)

Third-party Detector

Third-party Detector

Kidde Fenwal Analaser II

AutroPath HC600

AutroFlame CCTV


Autrosafe and en 54 l.jpg

AutroSafe and EN 54

  • AutroSafe:Developed and approved in accordance with EN 54-2 and EN 54-4

  • AutroSafe:Considers the demands of future EN 54 norms

  • AutroSafe:Exploits all the possibilities of EN 54

    (American equivalent is NFPA 72 – AutroSafe is also FM

    approved – thus tested and approved against NFPA 72)


Features performance functionality l.jpg

Features, Performance, Functionality..

  • Interactive loop Communication

  • Automatic addressing

  • Intelligent field devices

  • Increased reliability – key terms:

    • SelfVerify TM

    • DYFI+ (Dynamic Filter Process)

  • Built-in Short circuit isolators

  • Loop topology

  • Fail-safe loop communication

  • Roughed loop communication


Terminology mostly based on en54 l.jpg

DECK 3, CORRIDOR

Heat Detector

DECK 3, LER SOUTH

Smoke Detector

Operator panel

DZ-2

AZ-1

DZ-1

CCR

Optical Smoke

Detector

DZ-3

FWRE

AK2

AK1

FARE

OZ-1

AZ-2

= DZ: Detection zone

WORKSHOP

Multi-sensor

Detector

= AZ: Alarm zone

AZ-3

DZ-4

= OZ: Operation zone

Terminology – mostly based on EN54

Some examples:


Autrosafe selfverify system panels l.jpg

AutroSafe SelfVerify System Panels

Maximum flexibility: Easy to read, understand and operate

Fire & Gas Alarm panel

Operator Panel

Repeater Panel

Information Panel

Controller


Autrolon l.jpg

AutroLON

AutroLON

  • AutroSafe panels in a Ring loop

  • Short-circuit isolators in every panel – all panels will continue to operate even with a single break or short circuit on the AutroLON

  • Maximum 32 panels in one LON-ring (but needs a Booster for each 8th panel)

  • Fibre-optic modems available (3000 meters between two panels)

Back to main page


Autrosafe panel l.jpg

AutroSafe Panel

  • A complete fire and gas control panel with full operatorcapabilities

  • Supports up to 6 fire detection loops and 1 AutroFieldBus

  • 2 AutroCom Serial, 1 AutroCom Ethernet (TCP/IP)

  • Outputs and inputs, monitored or unmonitored

Back to main page


Autrosafe controller l.jpg

AutroSafe Controller

  • Serves as a connection unit for detection loops (maximum 6)

  • 1 AutroFieldBus

  • 2 AutroCom Serial, 1 AutroCom Ethernet

  • Outputs and inputs, monitored or unmonitored

  • Communicates with other system units on AUTROLON

Back to main page


Autrosafe information repeater panel l.jpg

AutroSafe Information/ Repeater Panel

Information Panel

  • Serves as an indication device only

  • Provides information related to the defined operation zone(s).

    Repeater Panel

  • Displays alarms and allows operation of alarms and receipt of additional information related to the relevant operation zone

Back to main page


Autrosafe selfverify a modular system l.jpg

AutroSafe SelfVerify, a Modular System

A variety of DIN rail mounted I/O modules available..

  • Loop drivers

  • Digital output modules

  • 24V alarm output modules

  • Digital input modules


A wide range of products for all applications l.jpg

A Wide Range of Products for All Applications

Optical

smoke

detectors

High-sensitivity

smoke

detectors

Series

Multisensor

smoke

detectors

Heat

detectors

Interface/

address units

Manual

Call-points

Sounder

Units

Series 200

Standard

Interactive-

Addressable

units

Series 300

With SelfVerify®

functions

Series 500

With special

protection for

marine, offshore,

Exi applications


Al com loop l.jpg

AL_Com Loop

AL_Com Loop

  • Ring loop-topology with detectors, I/O interfaces and sounders

  • Short-circuit isolators in every loop unit – all detectors and interfaces will continue to operate even with a single break or short circuit on the AL_Com Loop

  • One branch between two units on the main loop

  • All ‘decisions’ made by loop unit, event messages sent to panel

  • Fail-safe operation if communication fails.

Back to main page


Standard autrosafe loop units l.jpg

Standard AutroSafe Loop Units

  • The detection loop is connected directly to the Loop Driver Module

  • All types and series of AutroSafe detectors, manual call-points and I/O units can be connected to the same detection loop (99 det/mcp + 27 I/O)

Back to main page


Autrosafe ex loop l.jpg

AutroSafe EX Loop

  • Connected to one barrier (branch) between two units on the main loop

  • Maximum 20 EX-units on one branch

  • Most Autronica-detectors and I/O-units are produced in EX-versions

Back to main page


Large assortment of i o units l.jpg

Large Assortment of I/O Units

A number of loop controls and Interface units are available

  • Disablement input-units

  • Interface units for alarm and faults

  • Door control and monitoring units

  • Output control unit

  • General monitoring and control units

  • Sprinkler monitoring units


Bsl 330 x l.jpg

BSL-330/X

  • Interfaces on-site third-party systems

  • The following messages can be transmitted (from/to an AutroSafe fire-alarm panel):

    • fire alarms

    • pre-alarms

    • faults

    • technical alarms from I/O units and event handling from third-party devices

  • Four different versions

Back to main page


Autrocom directly to dcs l.jpg

AutroCom directly to DCS

  • ABB AC400

  • ABB AC800

  • Siemens

  • Kongsberg

  • Emerson

  • Hima

    Advantages of direct communication and propriatary protocol:

    Fuctionality and SIL!


Autroos l.jpg

AutroOS

  • Aremote monitoring and control system thatenables full operation of the AutroSafe fire-alarm panels

  • All alarms, faults, inhibits, overrides and outputs can bemonitored and controlled from the AutroOS stations

  • Video from CCTV flame cameras

  • Microsoft Windows platform

Back to main page


Autrosafe sys utility software package l.jpg

AutroSafe Sys. & Utility Software Package

  • AS Configuration Tool

    • Merge Tool

    • Power Calculators

    • Import/Export Tools

    • Download Tools

  • AS I/O Simulator Tool

    • The perfect Application Software verification Tool

  • Loop Diagnostics Tool

    • WAS-2000 and AS-2000


What is selfverify l.jpg

What is SelfVerify®?

SelfVerify® function:The detectors are tested once every 24 hours with a calibrated signal


Standard analogue addressable fire alarm system l.jpg

Power Supply

Detector Loop

Communication

interface

Fault Warning

Fault Signal

ALARM!

Fire Alarm

Fire Alarm Signal

STOP!

Detector

smoke

chamber

Alarm

signal

Standard Analogue Addressable Fire-Alarm System

Power supply

Monitored parts

Communication

interface

Non-Calibrated test

Smoke detector

Fault warning

Fault signal

Fire Alarm

Fire Alarm signal

Operation

Detector test

with test gas

Alarm

signal


Selfverify l.jpg

Fail-safe detectors give increased reliability, and reduce maintenance costs dramatically

Power supply

Communication-

interface

SV-

control

Smoke detector

Fault warning

Fault signal

ALARM!

Fire Alarm

Fire Alarm Signal

Calibrated test

Detector

smoke

chamber

STOP!

SelfVerify®

stimulator

Operating

Alarm-

signal

Monitored part

SelfVerify®


Why selfverify l.jpg

Why SelfVerify®?

SelfVerify®

– Reduces the need for manual testing is significantly


System integrity l.jpg

System Integrity

  • R&D target for System Integrity: No single fault shall degrade system performance

  • SIL 2 (Safety Integrity Level2) in accordance with IEC-61508 (By TÛV and NEMCO)


Sil 2 certificates by t v and nemco l.jpg

SIL 2 Certificates by TÛV and NEMCO


Comprehensive list of approvals l.jpg

  • American Bureau of Shipping

  • ATEX (NEMCO)

  • Bosec

  • BUREAU VERITAS AND AUTORITES MARITIMÈS FRANCAISES

  • China Compulsory Certification

  • China Classification Society

  • China National Quality Supervision and test centre for explosion protected electrical products

  • Dansk brand- og Sikringsteknisk Institut

  • Det Norske Veritas (DNV)

  • Forsikringsselskapenes Godkjenningsnevnd

  • FM APPROVALS

  • Germanischer Lloyd

  • Japanese Government

  • Lloyd's Register of Shipping

Comprehensive list of Approvals

  • Maritime and Coastguard Agency

  • Nonprofit Independent Research Organisation “Certification Centre of Explosion-proof and Mine Electrical Equipment" - Nanio “CCVE"

  • Nippon Kaiji Kyokai

  • Polski rejestr Statków

  • Registro Italiano Navale

  • Russian Maritime register of Shipping

  • Svensk Brand- och Säkerhets Certifiering ab

  • United States Coast Guard

  • Vniipo/Gost


  • Login