Exercise 2

Loading in 2 Seconds...

play fullscreen
1 / 16

Exercise 2 - PowerPoint PPT Presentation


  • 51 Views
  • Uploaded on

Exercise 2. S-18.3150 High Voltage Engineering S-18.3146 Suurjännitetekniikka. 450. 400. 350. 300. 250. U 50 [kV]. 200. 150. d=20 mm. 100. D=54 mm. 50. d. 0. D. 0. 1. 2. 3. 4. 5. 6. 7. 8. p [ bar ]. Question 1.

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about ' Exercise 2' - holly


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
exercise 2

Exercise 2

S-18.3150 High Voltage Engineering

S-18.3146 Suurjännitetekniikka

question 1

450

400

350

300

250

U50 [kV]

200

150

d=20 mm

100

D=54 mm

50

d

0

D

0

1

2

3

4

5

6

7

8

p [bar]

Question 1
  • The figure depicts average breakdown voltage (U50) as function of gas pressure (p) for a coaxial SF6 insulator. The structure was originally designed for 6 bar. However, it became apparent that it wasn’t economically efficient to design the system for such high pressures. For this reason, pressure was decreased to 4 bar. Design the structure again so that the 50% breakdown voltage and the ratio D/d remains the same. What are the new D and d parameters? Assume constant electric field strength.
slide3

d=20 mm

D=54 mm

d

D

450

Average breakdown voltage:

400

350

300

(original)

250

U50 [kV]

200

(reduced)

150

100

50

0

0

1

2

3

4

5

6

7

8

Coaxial Geometry:

p [bar]

slide4

Breakdown field strength, p = 4 bar:

Assume critical field strength remains constant

Denote d´= new inner conductor diameter

slide5

Fixed ratio:

New outer diameter:

6 bar:

D = 54 mm

d = 20 mm

∆ = 34 mm

4 bar:

D´= 71 mm

d´= 26 mm

∆ = 45 mm

Although, the ratio D/d remains the same, distance between electrodes has increased.

  • Originally, breakdown at 4 bar would have occurred at 280 kV. With the new increased distance, voltage has to increase to 370 kV for breakdown to occur

Thus, breakdown voltage level has stayed the same compared to original structure.

question 2

100

10

U50 [kV]

1

0,1

0,001

0,01

0,1

1

10

pd [bar∙mm]

Question 2
  • Calculate the onset of partial discharge for the resin test object when breakdown voltage in the cavity obeys Paschen’s law. Pressure in the cavity is 1013 mbar and its dimensions are 1 mm x 5 mm (h x w). Both cavity and the test object are cylindrical. Calculate the apparent charge and consumed energy of the discharge.
slide7

f = 30 mm

e

e

=

=

4

4

3 mm

f = 5 mm

r

r

Three-Capacitance Model:

Cb

Ca

Cc

ha

hc

Cb

Voltage is distributed inversely proportional in relation to capacitance:

slide8

100

10

U50 [kV]

1

0,1

0,001

0,01

0,1

1

10

pd [bar∙mm]

Paschen’s Law: Ub = f(pd)

p =1013 mbar, d =1 mm  Inception voltage of discharge in cavity uci = 4.5 kV

  • Inception voltage (applied voltage required to ignite discharge in cavity) ui = 1.5∙ uci= 6.75 kV ≈ 6.8 kV
slide9

Discharge is much faster than the feeding circuit (external circuit is too slow to react to discharge  circuit can be removed)

During discharge, from the point of view of Cc representing the capacitance in the void, the rapid change in voltage is distributed between the series connection of Cb and Ca which are now in parallel with Cc

~

C´a

∆ uc

Cc

Cb

  • Calculating apparent charge:

Extinction voltage = 0 V

Assuming

  • Apparent charge:
slide10

Calculating energy:

where q = 1.6 nC and u = ui = 6.8 kV

Consumed energy during discharge:

question 3
Question 3
  • The system in question 2 has 50 Hz alternating voltage of 6 kVRMS. Pressure in the cavity is 1013 mbar. Breakdown voltage in the cavity obeys Paschen’s law and the extinction voltage is 0.5 kV. Draw the voltage waveform and calculate the steady state partial discharge frequency.
slide12

Applied voltage

where U = 6 kV

Voltageovercavity:

Inceptionvoltage:

Extinctionvoltage:

slide13

8

u(t)

uc(t)

6

+uci

4

2

+uce

0

-uce

-2

-uci

-4

-6

Number of discharges per period · 50 Hz

Discharge frequency

= 4 · 50 Hz = 200 Hz

=

-8

question 4
Question 4

1

2

  • The figure shows a bushing (feed-through insulator). Cylinder 1 is the bushing conductor. Insulation layers 2, 3, and 4 have thin metal sheets between them to improve dielectric strength. Design lengths l2 and l3 so that maximum field strength in both sheets is of the same magnitude. What is this maximum field strength value?

3

4

l

l

l

l

l

l

4

4

3

3

2

2

D

1

D

2

D1 = 20 mm D2 = 34 mm

D3 = 48 mm D4 = 62 mm

L4 = 140 mm U14 = 30 kV

D

3

D

4

slide15

Electric field for a cylinder:

l

Design lengths l2 and l3 so that maximum field strength in both sheets is of the same magnitude

2

1

3

4

l

l

l

l

l

l

4

4

3

3

2

2

r

r

U

U

D1

1

R

D

2

l4 and D1…4 are given:

D

3

D

4

slide16

Voltage:

2

1

3

4

l

l

l

l

l

l

4

4

3

3

2

2

D1

1

D

2

D

3

D

4

ad