ApplicationsLibrary Note: The descriptions that follow offer links allowing access to the corresponding application. IfZelioSoft2softwareisinstalled,aclickonthelinkwillopentheprogram.Youmaythenselectsimulationmode (1)andstartthemodule(RUN)(2). (1) (2) Floatingpop-upsareavailabletochangeandviewtheinput-outputstatus.Toviewthemormaskthem,usethe iconbarat thebottomofthescreen: 1ApplicationsinLadderlanguage 1.1GREENHOUSEAUTOMATIC VENTILATION PANECONTROL Specifications: Theownerofagreenhousewouldliketoacquireaninstallationtomanagetheopening andclosingoftheventilationwindowpaneslocatedonthegreenhouseroof. The greenhouse has two window panes toprovide ventilation.The opening ofthesewindowpanesiscontrolledbyamotorand2sensorsthatindicatewhether the window panesareopenorclosed: Duringtheday,thewindowpanesopentoventilatethestructurefrom12:00to15:00,atthe time ofday when, in principle,the temperature is the highest.However,ifthetemperatureislessthan10°C,thewindowpanesdonotopen,orwhentheyarealready open,theyclose. Inaddition,thewindowpanesopenduringthedaywhenthetemperaturereaches25°C.Ifthetemperaturefalls below25°C,thewindowpanesmustcloseagain. Finally,atnight,thewindowpanesremainclosedregardless ofthetemperature. Powerbyhttp://www.hackspedia.com
Summarydiagram: Description of the inputs/ouputs: Thetemperatureis suppliedbyasensorwithoutputvoltageof 0to10V. Model Required: ZelioLogic withclockandanaloginputs. SR2B121BD (24VDC)ouSR2B121JD (12VDC)parexemple. Program Description: 3timerangesareused: -Range 1:Night,from21:00 to07:00 -Range 2:Daytime,from7:00to12:00a.m.andfrom3:00to9:00p.m. -Range 3:Noon,from12:00to15:00 Powerbyhttp://www.hackspedia.com