changes for 2008 lighting standards
Download
Skip this Video
Download Presentation
Changes for “2008” Lighting Standards

Loading in 2 Seconds...

play fullscreen
1 / 222

Changes for “2008” Lighting Standards - PowerPoint PPT Presentation


  • 84 Views
  • Uploaded on

Changes for “2008” Lighting Standards. California Energy Commission Modifications made by Jay Salazar. Introduction. This Seminar covers the Residential and Nonresidential 2008 energy Standard Changes to the LIGHTING REQUIREMENTS. There are several units lasting about 40 minutes each.

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about ' Changes for “2008” Lighting Standards' - guido


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
changes for 2008 lighting standards

Changes for “2008” Lighting Standards

California Energy Commission

Modifications made by Jay Salazar

introduction
Introduction
  • This Seminar covers the Residential and Nonresidential 2008 energy Standard Changes to the LIGHTING REQUIREMENTS.
  • There are several units lasting about 40 minutes each.
introduction1
Introduction
  • This seminar requires that
    • Participate in the presentation
    • Work practical problems
  • Questions on the slides are welcome at any time. This is not a class of interpretation or general energy.
introduction2
Introduction
  • By the end of this seminar you will
    • Be introduced to the energy website
    • Know when the new 2008 standards go into effect.
    • Recite verbally the major Lighting sections that are changed with the new 2008 Energy Standards
    • Identify the new Residential and Nonresidential 2008 Energy forms for Plan Check and Inspection forms
introduction3
Know how to apply the new Residential 2008 Energy Lighting forms

Know How to apply the new Non-Residential 2008 energy Forms

Know what sections in the Energy Standards change with respect to lighting

Know the new sign requirements

Know the new outdoor lighting requirements

Review new definitions

Introduction
how can i participate
How Can I Participate?

www.energy.ca.gov

List Servers Sign-Up

Click on Links-

http://www.energy.ca.gov/listservers/index.html

Enter your name & e-mail address

Then click on subscribe and click the box for the list(s) you wish to subscribe to. EFFICIENCY LISTS include:

Appliance Efficiency Standards

Blueprint - Title 24 Newsletter

Energy Efficiency Building Standards (Title 24)

where are the standards and the res and nonres manuals
Where are the Standards And the Res and Nonres Manuals

http://www.energy.ca.gov/title24/2008standards/index.html

slide10

Title 24 - 2008

General Information

slide11
Major Changes to the Lighting Energy Standards:

When they go into effect

All new lighting Forms

CHANGES TO SOME DEFINITIONS

Changes to LTGC and LTGA FORMS-NONRES

Changes to the CF6R Form-RES

Illuminated Signs have a separate energy review.

Outdoor Lighting Plan Review has been Changed.

2008 Title 24 Energy Standards

2008 title 24 energy standards
2008 Title 24 Energy Standards

The Forms are tied directly to the MAJORITY OF changes

  • If you understand the forms you will understand those changes that affect Permit Technician , Plan Review and Inspector activities.
  • The forms are for the Permit Tech, Plan reviewer and Inspector.
  • Energy Staff have worked and will continue to work on providing simplified forms.
slide14
Adopted

April 23, 2008 by the State

Effective

August 1, 2009

For building permit applications submitted on or after August 1, 2009

2008 Title 24 Energy Standards

slide15

Lighting -RES

  • Where stuff is for low rise Residential Lighting:
    • 2008 Energy Standards
      • Section 150(k) Mandatory
      • Section 151(a,f/a-e) Pers/Perfrom pg 144
      • Section 152 Add/Alts
      • Section 119 controls,bal,lum
slide16

Lighting -RES

  • You know its low rise residential if it is section 150, 151, or 152 in the 2008 Standards add 119 for controls, ballasts Luminaries.
  • Definitions related to the Standards are in Section 101
slide19

The New CF-6R-LTG-01 to the Form-RES

  • Has 8 Sections that act like a check list and declaration the applicant must check off and turn in to the Inspector prior to the final inspection.
  • The CF6R-LTG-01 is intended as a declaration by the installer BUT
  • Permit Techs and counter staff should go over the form at the time of application submittal with Owner/Builder applicants or residential remodel contractors.
slide20

The New CF-6R-LTG-01 to the Form-RES-8 Sections

  • Kitchen Lighting
  • Lighting Internal to Cabinets
  • Installed Devices and Components Have Been Certified to the Energy Commission
  • Lighting Controls
  • Luminaires (Lighting Fixtures)
  • Indoor Lighting (any indoor room that is not a kitchen)
  • Outdoor Lighting
  • Common areas of low-rise residential buildings
slide23

Changes to the CF6R Form-RES

  • Start with Kitchen Lighting
    • Permit Technicians or Plan Reviewers make sure the applicable boxes are checked Off.
slide27

Changes to the CF6R Form-RES

  • Start with Kitchen Lighting must comply with options (a),(b),or (c)
slide28

Changes to the CF6R Form-RES

  • Start with Kitchen Lighting
    • Permit Technicians or Plan Reviewers make sure the applicable boxes are checked Off when dealing with Owner/Builders or Remodel contractors but let Architects and energy consultants have the installer declare. .
slide29

Changes to the CF6R Form-RES-What happens if less than 50%

  • Permit Tech and Plan Reviewers use option (c)
  • Remember if you use ( c) then
    • Additional kitchen low efficacy lighting (50 watts or 100 watts ) is available only if all of the following are true:
    • 􀂆 Yes. All low efficacy luminaires in the kitchen are controlled by a vacancy sensor, dimmer, energy management control system (EMCS), or a multi-scene programmable control system.
    • 􀂆 Yes. Permanently installed luminaires in garages, laundry rooms and utility rooms are high efficacy luminaires AND are controlled by a vacancy sensor
high efficacy luminaires 150 k

High Efficacy Luminaires § 150(k)

  • T24 requires ALL luminaires installed in RESIDENTIAL applications must be classified as high efficacy or low efficacy
  • T24 does not require luminaires installed in nonresidential applications to be classified as high efficacy or low efficacy
slide35

Changes to the CF6R Form-RES

  • Always High Efficacy
    • Fluorescent (no screws) ( 13W or over needs electronic ballast)
    • Metal Halide
    • High Pressure Sodium
  • Always Low Efficacy
    • Incandescent
    • Mercury Vapor
  • LED’s must be considered low Efficacy unless they are Certified by CEC
slide38

HID Luminaires (typically metal halide or high pressure sodium)

UL listed by the manufacturer as HID luminaires

Must be manufactured with an HID ballast integral to the luminaire

May have HID rated screw-based sockets which are not incandescent sockets

this is a medium screw base socket
This is a medium screw base socket

LOW EFFICACY

LOW EFFICACY

slide45

The New CF-6R-LTG-01 to the Form-RES-8 Sections

  • Kitchen Lighting
  • Lighting Internal to Cabinets
  • Installed Devices and Components Have Been Certified to the Energy Commission
  • Lighting Controls
  • Luminaires (Lighting Fixtures)
  • Indoor Lighting (any indoor room that is not a kitchen)
  • Outdoor Lighting
  • Common areas of low-rise residential buildings
slide46

Changes to the CF6R Form-RES section 2

  • Cabinets with internal illumination
internally illuminated cabinets

Internally Illuminated Cabinets

You may use either the width of the cabinet section or the height of the glazing per cabinet section, regardless of the number of shelves or doors on the cabinet. 

slide49

The New CF-6R-LTG-01 to the Form-RES-8 Sections

  • Kitchen Lighting
  • Lighting Internal to Cabinets
  • Installed Devices and Components Have Been Certified to the Energy Commission
  • Lighting Controls
  • Luminaires (Lighting Fixtures)
  • Indoor Lighting (any indoor room that is not a kitchen)
  • Outdoor Lighting
  • Common areas of low-rise residential buildings
slide50

Changes to the CF6R Form-RES Section 3

  • Must be certified at
  • http://www.energy.ca.gov/appliances/database/excel_based_files/Lighting/
slide51

The New CF-6R-LTG-01 to the Form-RES-8 Sections

  • Kitchen Lighting
  • Lighting Internal to Cabinets
  • Installed Devices and Components Have Been Certified to the Energy Commission
  • Lighting Controls
  • Luminaires (Lighting Fixtures)
  • Indoor Lighting (any indoor room that is not a kitchen)
  • Outdoor Lighting
  • Common areas of low-rise residential buildings
slide54

Changes to the CF6R Form-RES Section 4 Lighting Controls

4. Lighting Controls Complete section 4

􀂆 Yes 􀂆 NA §150(k)7A: Permanently installed low efficacy luminaires are controlled by switches separate from those controlling high efficacy luminaires.

􀂆 Yes 􀂆 NA §150(k)7B: Exhaust fans with integral lighting systems are switched separately from lighting systems, OR have a lighting system that can be manually turned on and off while allowing the fan to continue to operate for an extended period of time.

slide55

Changes to the CF6R Form-RES Section 4 Lighting Controls

􀂆 Yes 􀂆 NA §150(k)7C: All permanently installed luminaires are switched with readily accessible controls that permit the luminaires to be manually switched on and off.

􀂆 Yes 􀂆 NA §150(k)7D: All lighting controls have been installed in accordance with the manufacturer’s instructions.

􀂆 Yes 􀂆 NA §150(k)7E: All lighting circuits that are controlled by more than one switch, where a dimmer or vacancy sensor has been installed to comply with §150(k), no controls bypass the dimmer or vacancy sensor functions.

slide56

The New CF-6R-LTG-01 to the Form-RES-8 Sections

  • Kitchen Lighting
  • Lighting Internal to Cabinets
  • Installed Devices and Components Have Been Certified to the Energy Commission
  • Lighting Controls
  • Luminaires (Lighting Fixtures)
  • Indoor Lighting (any indoor room that is not a kitchen)
  • Outdoor Lighting
  • Common areas of low-rise residential buildings
slide60

Changes to the CF6R Form-RESSection 5 Luminaires

  • Any electrical box finished with a blank cover or where no electrical equipment has been installed, and where the electrical box can be used for a luminaire or a surface mounted ceiling fan, has been treated as low efficacy luminaires for compliance with §150(k).
slide61

Changes to the CF6R Form-RES Section 5 Recessed luminaires

  • To qualify as high efficacy recessed must be certified
  • http://www.energy.ca.gov/appliances/database/excel_based_files/Lighting/
slide65

The New CF-6R-LTG-01 to the Form-RES-8 Sections

  • Kitchen Lighting
  • Lighting Internal to Cabinets
  • Installed Devices and Components Have Been Certified to the Energy Commission
  • Lighting Controls
  • Luminaires (Lighting Fixtures)
  • Indoor Lighting (any indoor room that is not a kitchen)
  • Outdoor Lighting
  • Common areas of low-rise residential buildings
the new cf 6r ltg 01 to the form res section 6 indoor lighting1
The New CF-6R-LTG-01 to the Form-RES Section 6 Indoor lighting

Does the project include permanently installed luminaires in any room that is not a kitchen?

Yes, complete section 6 􀂆 No, go on to section 7

Yes 􀂆 NA §150(k)10: Permanently installed luminaires in bathrooms, garages, laundry rooms, closets > 70 ft2, and utility rooms are high efficacy luminaires OR are controlled by a vacancy sensor.

Yes 􀂆 NA §150(k)11: Permanently installed luminaires located in rooms or areas other than in kitchens, bathrooms, garages, laundry rooms, closets, and utility rooms are high efficacy luminaires, OR are controlled by a dimmer switch OR are controlled by a vacancy sensor.

slide74

The New CF-6R-LTG-01 to the Form-RES-8 Sections

  • Kitchen Lighting
  • Lighting Internal to Cabinets
  • Installed Devices and Components Have Been Certified to the Energy Commission
  • Lighting Controls
  • Luminaires (Lighting Fixtures)
  • Indoor Lighting (any indoor room that is not a kitchen)
  • Outdoor Lighting
  • Common areas of low-rise residential buildings
slide79

The New CF-6R-LTG-01 to the Form-RES-8 Sections

  • Kitchen Lighting
  • Lighting Internal to Cabinets
  • Installed Devices and Components Have Been Certified to the Energy Commission
  • Lighting Controls
  • Luminaires (Lighting Fixtures)
  • Indoor Lighting (any indoor room that is not a kitchen)
  • Outdoor Lighting
  • Common areas of low-rise residential buildings
slide83

Lighting –NON RES

Where stuff is for Non Res, High Rise Re, and Hotel and motel Lighting:

  • 2008 Energy Standards
  • 4 major sections to Non res
    • Indoor Lighting conditioned space
    • Indoor lighting unconditioned space
    • Outdoor lighting
    • Indoor and outdoor Signs
slide84

Lighting –NON RES-CON

1. Indoor Lighting Controls

  • Where stuff is for Non Res, High Rise Re, and Hotel and motel Lighting:
    • 2008 Energy Standards

1. Indoor lighting conditioned, process spaces

Sections 119,130,131,134 Mandatory

Section 143 (c ) 146 Prescriptive

Section 141 Performance

Section 149 Additions Alterations

slide85

Lighting –NON RES UNCON

2. Indoor Lighting Controls

  • Where stuff is for Non Res, High Rise Re, and Hotel and motel Lighting:
    • 2008 Energy Standards

2. Indoor lighting unconditioned spaces

Sections 119,130,131,134 Mandatory

Section 143(c ) , 146 Prescriptive

N/A Performance

Section 149 Additions Alterations

slide86

Lighting –NON RES

3. Outdoor Lighting

Where stuff is for Non Res, High Rise Re, and Hotel and motel Lighting:

  • 2008 Energy Standards

3. Outdoor Lighting

Sections 119,130,132,134 Mandatory

Section 147 Prescriptive

N/A Performance

Section 149 Additions Alterations

slide87

Lighting –NON RES

4. Indoor/Outdoor Signs

Where stuff is for Non Res, High Rise Re, and Hotel and motel Lighting:

  • 2008 Energy Standards

4. Indoor /outdoor Signs

Sections 130,133 Mandatory

Section 148 Prescriptive

N/A Performance

Section 149 Additions Alterations

lighting non res changes to the forms
Lighting –NON RES Changes to the Forms
  • Forms are found in the Nonresidential Manual, Appendix A Compliance Forms and Worksheets.
  • ENV-1A, LTG-1A, OTLG -1A, MECH-1A, are no longer used and have been deleted.
  • 2005 - 16 Forms 2008 – 14 Forms
slide91

Non Res Forms Inspectors

Inspection Staff

Use the Following

  • LTG-1-C Inspection checklist
  • FIELD INSPECTION ENERGY CHECKLIST

Verify the following:

  • LGT-INST Indoor lighting Installation certificate
  • OTLG-INST Outdoor Lighting Installation Certificate
  • SLTG-INST Sign Installation Certificate
  • LTG-2-A Lighting Control Acceptance Doc
  • OLTG-2-A Outdoor Lighting Control Acceptance Doc
ltg 1 c form
LTG-1-C Form
  • Page 2 of 4 Indoor lighting Schedule.
  • Page 2 of 4 also serves as a Field Inspection Energy Checklist, which is to be utilized by the enforcement agency.
  • The Field Inspector verifies at the end of installation that the LTG-1-INST and the appropriate Certificates of Acceptance have been completed.
  • The Field Inspector also verifies that lighting schedule describes what was installed and checks the appropriate box in column H.
slide95

Non Res Forms Plan Review

Plan Review

LTG-1C Pages 1 through 4 Certificate of Compliance. All Pages required on plans for all submittals.

LTG-2C Lighting Controls Credit Worksheet

LTG-3C Indoor Lighting Power Allowance

LTG-4C Pages 1 through 4 Tailored Method Worksheet

LTG-5C Pages 1 and 2 Line Voltage Track Lighting Worksheet

slide96

Non Res FormsPlan Reviewers

  • LTG-1-C Form
    • Step 1 -Check that the form is filled out.
non res forms plan reviewers
Non Res FormsPlan Reviewers
  • Separate forms required for conditioned and unconditioned spaces.
  • Additions are when the new conditioned space is created.
slide98

Lighting –NON RES

2008 Energy Standards

  • 4 major sections to Non res
    • Indoor Lighting conditioned space
    • Indoor lighting unconditioned space
    • Outdoor lighting
    • Indoor and outdoor Signs

ALL 4 ARE AFFECTED BY THE LIGHTING CONTROLS SECTIONS 119, 130 and 131

lighting control devices
Lighting Control Devices
  • MUST BE CERTIFIED

http://www.energy.ca.gov/appliances/database/excel_based_files/Lighting/

Or

who you gonna call?

slide116

Lighting –NON RES

2008 Energy Standards

  • 4 major sections to Non res
    • Indoor Lighting conditioned space
    • Indoor lighting unconditioned space
    • Outdoor lighting
    • Indoor and outdoor Signs
slide128

Nonresidential Indoor Lighting §146

Complete Building Method

  • Added: may be used for tenant space where one type of use makes up 90 percent of the space
  • Retail and wholesale stores, hotel/motel, and high-rise residential buildings shall not use this method.
  • May be used for combined building where there is a Parking Garage + another complete building category
    • Parking garage portion and remaining portion shall each separately qualify for and use categories from Table
slide129

Nonresidential Indoor Lighting §146

Tailored Method

  • Displays installed against a wall shall not qualify for the floor display lighting power allowances.
  • Floor displays shall not qualify for the wall display allowances.
  • Permanent full height partitions shall extend from the floor to within 2 feet of the ceiling or are taller than 10 feet, and are permanently anchored to the floor.
    • Commercial and industrial storage stacks are not classified as permanent full height partitions.
slide130

Nonresidential Indoor Lighting §146

Tailored Method

  • Qualifying wall lighting systems shall be mounted within sixten feet of wall
  • Qualifying floor display lighting systems shall be mounted no closer than sixtwo feet to a wall and
  • In retail merchandise sales, museum, and religious worship, the lighting power for very valuable displays cases
    • Removed from Tailored Method table and inserted into text

Smallest of:

    • Area of space times 1.0 W/ft2, or
    • Area display case times 16 W/ft2, or
    • Actual power
slide134

Day lighting BIG Changes –NON RES

  • NO MORE 15 FOOT DEPTH
  • Basically the Daylit Depth is the height of the window
  • Depth is determined by the height of the window, or distance to the nearest 5 foot high vertical obstruction.
  • Introduction of a Secondary Daylit area
  • Daylit areas must be shown on the plans
definition primary and secondary sidelit area still 250 sf or more auto controls at 2500 sf
DefinitionPrimary and Secondary Sidelit AreaStill 250 SF OR MORE Auto controls at 2500 SF

h

Primary

Secondary

1 X h

2 X h

slide136

Daylighting –NON RES

AB switching No credit

Controls get credits in the Secondary area

alterations skylights 149 b no daylighting control when you add skylight for alterations

Alterations – Skylights §149(b)No daylighting control when you add skylight for alterations

  • Adding skylights to existing buildings:
  • When §131(c)2 triggered by addition of skylights to existing building
  • And lighting system is not re-circuited
  • Daylighting control need not meet multi-level requirements in Section 131(c)2A.
slide140

Lighting –NON RES

2008 Energy Standards

  • 4 major sections to Non res
    • Indoor Lighting conditioned space
    • Indoor lighting unconditioned space
    • Outdoor lighting
    • Indoor and outdoor Signs
four outdoor lighting zones
Four Outdoor Lighting Zones
  • The Energy Commission sets statewide default Lighting Zones

http://www.energy.ca.gov/title24/2005standards/outdoor_lighting/

  • However, the jurisdictions (usually a city or county), may change the zones to accommodate local conditions.
  • Follow a formal public process
  • File changes with Energy Commission
outdoor lighting zones
Outdoor Lighting Zones

LZ1 Darkest

  • Government designated parks, recreation areas, and wildlife preserves

LZ2 Low

  • Rural areas, as defined by the most recent US Census

LZ3 Mid

  • Urban areas, as defined by the most recent US Census

LZ4 Highest

as of today
AS OF TODAY…

There are still

NO OLZ 4’s

in California

outdoor luminaire cutoff requirement 132
Outdoor Luminaire Cutoff Requirement (132)
  • Hardscape Areas
    • Parking lots
    • Building entrances
    • Canopies
    • Outdoor sales areas
  • > 175 Watts
  • Must be IESNA Cutoff (full cutoff also complies)
    • Must take into account mounting at a tilt
lighting devices
Lighting Devices
  • MUST BE CERTIFIED

http://www.energy.ca.gov/appliances/database/excel_based_files/Lighting/

Or

who you gonna call?

slide148

< 2.5 %

Plumb line

Full Cutoff

Cutoff

< 5 %

≥ 5 %

Semi-Cutoff

Non-Cutoff

slide149

> 2.5 % ?

Plumb line

Non-Compliant Full Cutoff

132 outdoor lighting controls
§ 132 Outdoor Lighting Controls

Existing exceptions to outdoor luminaire cutoff:

  • Building facades, public monuments, statues, and vertical surfaces of bridges
  • Required by health or life safety statue, ordinance, or regulations
  • Temporary outdoor lighting
  • Used around water subject to Article 680 of CEC
132 outdoor lighting controls1
§ 132 Outdoor Lighting Controls

New exception to outdoor luminaire cutoff:

  • Replacement of existing pole mounted luminaires in hardscape areas meeting all of the following conditions:
    • Existing luminaire not cutoff; and
    • Spacing between existing poles is greater than six times the mounting height of the existing luminaires; and
    • No additional poles added to the site; and
    • No new wiring to the luminaires; and
    • Connected lighting power wattage not increased
motion sensors on inefficient lighting technologies
Motion Sensors on inefficient lighting technologies

If luminaire rated for over 100 watt lamp, shall have either:

  • Lamp efficacy of 60 lumens per watt
  • Or controlled by motion sensor
    • Do not want Mercury Vapor
    • Use metal halide. High pressure sodium or flourescent.
132 outdoor lighting controls2
§ 132 Outdoor Lighting Controls

Exceptions to motion sensors

  • Required by health or life safety statue, ordinance, or regulations
  • Used around water subject to Article 680 of CEC
  • Searchlights
  • Theme lighting used in theme parks
  • For film and live performances
  • Temporary
  • LED, light emitting capacitors, neon, cold cathode
  • Sign
multi level switching
Multi-Level Switching
  • Give owner ability to automatically turn off ≥50% to ≤ 80%
    • Building facades
    • Parking lots
    • Garages
    • Canopies
    • Outdoor Sales Areas
    • Student pick-up/drop-off zones
134 nonresidential lighting controls acceptance
§ 134 Nonresidential Lighting Controls Acceptance
  • In 2005, Lighting Control Acceptance only applied to nonresidential indoor lighting controls
  • In 2008, added: Certified that outdoor lighting controls shall meet the requirements of §119 and 132.
slide157

Non Res FormsPlan Reviewers

  • 3 areas or layers to check out door power density
  • LAYERS
    • Illuminated Hardscape Wattage per SF
    • Linear Wattage per LF
    • Initial Wattage
147 outdoor lighting
§ 147 Outdoor Lighting

Illuminated hardscape means:

  • Square pattern ten times the luminaire mounting height with the luminaire in the middle of the pattern
  • Shall not go beyond hardscape border or into buildings
  • No double counting of any areas
  • Hardscape areas which are not illuminated shall not be included in total square feet of site hardscape
  • Solar powered lighting, or other “off the grid” lighting is not exempt from Title 24, Part 6
slide159

117 ft

108 ft

25 ft high

luminaires

illuminated area
Illuminated Area

30 feet

150 feet

150 feet

Not to Scale

illuminated area1
Illuminated Area

16 feet

30 feet

150 feet

80 feet

80 feet

150 feet

Not to Scale

illuminated area2
Illuminated Area

16 feet

30 feet

Area NOT

illuminated

150 feet

80 feet

150 feet

Not to Scale

illuminated area4
Illuminated Area

Parking

Lot

This area is not illuminated

illuminated area5
Illuminated Area

Do not count area within square pattern that is beyond the paved area

This area is not illuminated

147 outdoor lighting exceptions
§ 147 Outdoor Lighting Exceptions

EXCEPTIONS to Section 147: When ≥ 50% light from luminaire falls on one or more of the following applications, the lighting power for that luminaire shall be exempt from Section 147(b):

  • Lighting specifically for Automated Teller Machine as required by California Financial Code Section 13040, or required by law through a local ordinance
  • Lighting of tunnels, bridges, stairs, wheelchair elevator lifts for American with Disabilities Act (ADA) compliance, and ramps that are other than parking garage ramps.
  • In theme parks: outdoor lighting for themes and special effects
  • Lighting for outdoor theatrical and other outdoor live performances, provided additions to area lighting systems and controlled by a multiscene or theatrical cross-fade control station accessible only to authorized operators
  • Outdoor lighting systems for qualified historic buildings if they consist solely of historic lighting components or replicas of historic lighting components
147 outdoor lighting exceptions continued
§ 147 Outdoor Lighting Exceptions (continued)
  • Temporary
  • Required FAA and Coast Guard
  • Public Streets, roadways, highways, traffic signage
  • Sports, athletic fields, children’s playgrounds
  • Industrial sites (rail yards, maritime shipyards and docks, piers and marinas, chemical and petroleum processing plants, aviation facilities)
  • Public monuments
  • Around swimming pools & water features (CEC 680)
  • Landscape
147 outdoor lighting1
§ 147 Outdoor Lighting

New “Layered Method”

  • Outdoor lighting language rewritten for clarity
  • Repackaged for simplification of compliance forms and enforcement
  • No longer break site into many puzzle pieces
147 outdoor lighting2
§ 147 Outdoor Lighting

New “Layered Method”

  • First layer = illuminated hardscape lighting power allowance for entire site
    • May trade off hardscape allowance within the site– provided entire hardscape remains illuminated
    • Must reduce total square feet of site hardscape if luminaires removed
147 outdoor lighting3
§ 147 Outdoor Lighting

New “Layered Method”

  • Other Specific Application “layers” available where appropriate
    • Each additional lighting power allowance is layered on the appropriate portion of site
147 outdoor lighting4
§ 147 Outdoor Lighting

The general hardscape area of a site includes:

  • Parking lots, roadways, driveways, sidewalks, walkways, bikeways, plazas, and other improved areas that are illuminated
  • No longer differentiate between pedestrian and automotive hardscape
  • No longer have methods ‘i’ and ‘ii’
147 outdoor lighting5
§ 147 Outdoor Lighting

TABLE 147-A GENERAL HARDSCAPE LIGHTING POWER ALLOWANCE

slide173

Grey = hardscape

Blue = building

Green = grass

Red = linear wattage allowance

147 outdoor lighting6
§ 147 Outdoor Lighting
  • Additional Lighting Power Allowance for Specific Applications:
  • Shall be the smaller of:
  • Additional lighting power allowances for specific applications
    • Determined from Table 147-B
    • For appropriate lighting zone
  • Or the actual installed lighting power meeting the requirements for the allowance.
147 outdoor lighting7
§ 147 Outdoor Lighting

Hardscape security exception for local ordinance

  • For hardscape including parking lots, site roadways, driveways, sidewalks, walkways or bikeways
  • When specific light levels are required by law through a local ordinance
    • Provided local ordinance has followed public process allowing formal public notification, review, and comment about the proposed change in accordance with §10-114
  • The smaller of the following additional layer may be added:
    • Actual additional wattage, or
    • LPD specified in TABLE 147-C
147 outdoor lighting8
§ 147 Outdoor Lighting

Hardscape security exception for local ordinance

10 114 outdoor lighting zones
§ 10-114 Outdoor Lighting Zones
  • Public process required when adopting ordinances for minimum light levels
outdoor lighting power
Outdoor Lighting Power

Trading off lighting power allowances with

any indoor areas not permitted

slide195

Appliance Efficiency Regulations (Title 20)

Table U-2 Standards for Power Supplies

101 definitions
§ 101 Definitions

Many new definitions added

Clarifications made to existing definitions

Many T24 inquires are answered by taking folks to the definition section

luminaire efficacy and wattage is not based on the initial lamp installed

Luminaire Efficacy and Wattage isNOT based on the initial lamp installed

  • Luminaire input wattage is based upon the type and rating of the luminaire (Socket-not the light bulb), not the type of lamp initially installed in a luminaire
  • A high efficacy lamp screwed into a low efficacy luminaire is still be considered to be a low efficacy lighting system for Title 24 projects
slide220
An LED source system with a standardized base is an LED lamp.

For purposes of Title 24, an LED bulb which is a drop-in replacement for an incandescent bulb is not an LED light engine with integral heat sink

Residential Compliance Manual Chapter 6.2.10

ad