Master Examination Practice Drill #5 2011. Ted “ Smitty ” Smith. Given: a 150 kVA service transformer has a 480Y/277 volt, 3-phase secondary. What is the approximate full-load ampere rating of the primary of the transformer? 180 amperes 312 amperes 542 amperes 416 amperes . 1. A 180.32 A.

etoile
Download Presentation

Master Examination Practice Drill #5 2011

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Master Examination Practice Drill #5 2011 Ted “Smitty” Smith

  2. Given: a 150 kVA service transformer has a 480Y/277 volt, 3-phase secondary. What is the approximate full-load ampere rating of the primary of the transformer? • 180 amperes • 312 amperes • 542 amperes • 416 amperes

  3. 1. A • 180.32 A

  4. Where a conductor is marked RHW-2 on the insulation what does the -2 represent? • The cable has 2 conductors • The conductor is double insulated • The conductor has a nylon outer jacket • The conductor has a maximum operating temperature of 90°C.

  5. 2. D Table 310.104(A)

  6. For a grounded electrical system, the equipment grounding conductor shall be sized in accordance with ___________? • The undergrounded circuit conductors • The overcurrent protective device • The service entrance conductors • The grounding electrode

  7. 3. B • 250.32(B)(1) • Table 250.122

  8. Determine the allowable ampacity of a size kcmil THW aluminum conductor installed in a raceway with four (4) other current-carrying conductors when the expected ambient temperature is 44 deg. C. • 151 amperes • 164 amperes • 210 amperes • 146 amperes

  9. 4. B • Tbl. 310.15(B)(16) • Tbl. 310.15(B)(2)(a) • Tbl. 310.15(B)(3)(a)

  10. Determine the MAXIMUM number of 120-volt, general-purpose duplex receptacles the NEC® permits to be protected by a 20-ampere, 120-volt single-pole circuit breaker in a commercial building. • 18 • 15 • 13 • 10

  11. 5. C • 120 volts x 20 amperes= 2400 VA • 2400 VA / 180 VA= 13 receptacles

  12. For4 lighting systems operating at 30 volts or less, the output circuits of the power supply are to be rated for NOT more than ___________? • 15 amperes • 20 amperes • 25 amperes • 30 amperes

  13. 6. C • 411.2

  14. Where there are tenant spaces in a retail shopping mall, each occupant shall have access to the main disconnecting means, EXCEPT: • Where the service and maintenance are provided by the building management. • Where there are more than six disconnecting means provided. • Where the primary feeder transformer does not exceed 600 volts. • Where the secondary of the service transformer does not exceed 240 volts to ground.

  15. 7. A • 240.24(B)(1)(1)

  16. Determine the conductor allowable ampacity given the following related information: • Ambient temperature of 44°C • 250 kcmil THWN copper conductors • Four (4) current-carrying conductors in the raceway • Length of raceway is 50 feet. • 160 amperes • 167 amperes • 200 amperes • 209 amperes

  17. 8. B • Tble. 310.15(B)(16) • Tbl. 310.15(B)(2)(a) • Tbl. 310.15(B)(3)(a) • 250 kcmil THWN copper ampacity 255 A • 255 A x .82 temp correction x .8 adj factor

  18. In general, the grounded conductor and the grounding conductor must be bonded together in _____________? • I. Panelboards used as service equipment • All sub-panels • I only • II only • Both I and II • Neither I not II

  19. 9. A • 250.24(A) • 250.24(A)(5) • 408.3(C)

  20. Using the standard method of calculation, what is the demand, in kW, on the undergrounded service-entrance conductors of an apartment complex that has thirty-five (35) electric ranges rated at 11.5 kW each? • 403 kW • 15 kW • 280 kW • 50 kW

  21. 10. D • Tbl 220.55, Col. C

  22. A grounding ring consisting of a size 2 AWG bare copper wire encircling a building, buried 36 in. deep, in direct contact with the earth, is required to have a MINIMUM length of ____________? • 15 feet • 20 feet • 25 feet • 50 feet

  23. 11. B • 250.52(A)(4)

  24. Where applying the optional method of calculation for one-family dwelling, what is the demand load for the heating and cooling, in kW, on the ungrounded service-entrance conductors for a residence that has the following? • One blower motor rated 1.2 kW, interlocked with both space heating and AC equipment. • One central electric space-heating unit rated 25 kW • One air-conditioning unit rated 6.5 kW • 32.75 kW • 25.00 kW • 17.03 kW • 26.20 kW

  25. 12. C • 220.82(C) and (C)(4) • Note: Use the large of the A/C or heating load

  26. Apply the general method of calculation for dwelling units and determine the Minimum demand load, in VA, where a one-family residence has the following fastened in place appliances. • Microwave oven – 1,250 VA • Trash compacter – 960VA • Dishwasher – 1,400 VA • Garage door opener – 960 VA • 3,428 VA • 3,656 VA • C. 4,570 • 4,883 VA

  27. 13. A 220.53 • Microwave Oven: 1250 VA • Trash Compactor: 960 VA • Dish Washer: 1400 VA • Garage Door Opener: 900 Va • Total: 4570 VA x .75= 3428 VA

  28. Where a service riser is installed in a wet location and contains THWN insulated conductors, the wiring method used ________________. • Is permitted to be Type AC cable • Shall be rigid metal conduit (RMC) • Is permitted to be electrical metallic tubing (EMT) • Shall be liquidtight flexible metal conduit (LFMC)

  29. 14. C 230.43(5)

  30. What is the MAXIMUM distance between supports for straight horizontal runs of trade size 1 ½ in. threaded rigid metal conduit (RMC)? • 10 feet • 12 feet • 14 feet • 16 feet

  31. 15. C • Tbl 344.30(B)(2)

  32. At least one receptacle outlet shall be installed directly above a show window of a department store for each __________ linear feet of show window area. • Six • Eight • Ten • Twelve

  33. 16. D • 210.62

  34. A thermal barrier shall be required if the space between the resistors and reactors, of 600 volts or less, and combustible material is Less than __________________? • 12 inches • 18 inches • 10 inches • 6 inches

  35. 17. A • 470.3

  36. In movie theaters, all switches for controlling the emergency lighting systems shall be located __________. • On the stage • In the lobby • In the manger’s office • In the project booth

  37. 18. B • 700.21

  38. Where a 90 ampere, 240-volt, single-phase load is located 225 feet from a panelboard and is supplied with size 3 AWG copper conductors, determine the approximate voltage drop on the conductors. (K=12.9) • 6 volts • 4 volts • 8 volts • 10 volts

  39. 19. D • VD= 2KDI/CM • 2x12.9x225x90/52620= 9.92

  40. A one-family residence is served with insulated 120/240 colt service-drop conductors, supported with a grounded messenger wire from the utility company. This service-drop crosses the swimming pool; the pool has a diving board that is 5 feet above the water level. The NEC® requires the conductors to be a Minimum height of ______ above the pool water level. • 25 feet • 14 ¼ feet • 22 ½ feet • 19 ½ feet

  41. 20. C • Fig. 580.8 • Tbl. 680.8

  42. Given: A trade size 2 in. electrical metallic tubing (EMT) containing four (4) size 2/0 AWG THWN copper conductors is to be installed in a pull box for a straight pull of the conductors. What is the MINIMUM required length of the pull box? • 4 inches • 12 inches • 16 inches • 24 inches

  43. 21. C • 314.28 • 2x8= 16

  44. In a commercial garage work area, which of the following receptacles, if any, are required to have GFCI protection? • I. 15 ampere general-purpose receptacles for hand tools and portable lights. • II. 20 ampere receptacles serving electrical diagnostic equipment only. • I only • II only • Both I and II • Neither I and II

  45. 22. C • 210.8(B)(8) • 511.12

  46. Conductors tapped from a feeder and supplying the primary of a transformer need not have overcurrent protection, if the length of the tap conductors are not over 25 feet and have an ampacity of at LEAST ______ of the rating of the overcurrent device protecting the feeder conductors. • One-third • One-half • 80 percent • 75 percent

  47. 23. A • 240.21(B)(3)(1)

  48. Where conductors carrying alternating current are installed in ferrous metal raceways, ________. • All phase conductors, the grounded conductor and equipment grounding conductors shall be grouped together • The phase conductors shall not be grouped with the grounded conductor • The equipment grounding conductor is not permitted to be in the same raceway with the grounded and ungrounded conductors • The equipment grounding conductors are not permitted to be installed in a common raceway with the grounded conductors.

  49. 24. A • 300.20(A)

  50. When connecting utilization equipment to a 20-ampere rated branch-circuit that also serves luminaires (lighting fixtures), the utilization equipment shall have an ampere rating of NOT more than _______. • 10 amperes • 15 amperes • 16 amperes • 12 amperes