GAIA-series 5-11KVA Introduction. Apr. 2009. Online GAIA Series 5-7KVA. Main Features: Models: 5KVA/3.5KW, 7KVA/4.9KW Rating Voltage : 200/208/220/230/240Vac, Single Phase Smart Rack/Tower In 2U Height Parallel Redundancy And Common Battery Application Multi-Language LCD Display

Download Presentation

Apr. 2009

An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -

Presentation Transcript


Apr 2009

GAIA-series 5-11KVA

Introduction

Apr. 2009


Apr 2009

Online GAIA Series 5-7KVA

Main Features:

Models: 5KVA/3.5KW, 7KVA/4.9KW

Rating Voltage : 200/208/220/230/240Vac, Single Phase

Smart Rack/Tower In 2U Height

Parallel Redundancy And Common Battery Application

Multi-Language LCD Display

Input PF >0.99, iTHD < 5%

Wide Input Voltage Range : 100~280 Vac (100~155Vac is linearly based on the loading).

Capable Of Bearing Input Voltage Transient Up To 330Vac Without Failure

Charger Capacity: 4A (Internal) + Optional 4Amp 2nd Charger

Two Smart Slots For Mission Critical Application

Optional Maintenance Box For Parallel Redundancy and Manual Bypass Switch.

Remote Emergency Power Off

Battery Start and AC Start Capability

Battery Cabinet – 2U


Apr 2009

Online Gaia Series 11KVA

Main Features:

Models: 11KVA / 7.7KW, Rating Voltage : 200/208/220/230/240Vac,

Single Phase

Smart Rack/Tower in 3U Height

Parallel Redundancy And Common Battery Application

Multi-Language LCD Display

Input PF >0.99, iTHD < 5%

Wide Input Voltage Range : 100~280 Vac (100~155Vac is linearly based on the loading).

Capable Of Bearing Input Voltage Transient Up To 330Vac Without Failure

Charger Capacity: 4A (Internal) + Optional 4Amp 2nd Charger

Two mart Slots For Mission Critical Application

Optional Maintenance Box For Parallel Redundancy and Manual Bypass Switch.

Remote Emergency Power Off

Battery Start and AC Start Capability

Battery Cabinet – 3U


Apr 2009

Outlook - Front

11KVA : 3U Height

5-7KVA : 2U Height


Apr 2009

Outlook - Rear

Rear Panel:

1. Input Terminal

2. Output Terminal

3. Input Circuit Breaker

4. External Battery Connector

5. Smart Slot

6. Fan Grid

7. Parallel port

8. RS232 Port

9. SNMP Slot

10. REPO Port (RJ11)


Apr 2009

GAIA-series Key Benefit

Parallel Redundancy :

1+1 (Only) for capacity expansion or redundancy purpose

Common Battery Application:

Two UPS can use the same battery pack to save the cost of installation. But of course, the runtime would be shorter.

It depends on the application of site.

High Efficiency And Low iTHD :

pf > 0.99 and iTHD < 5%.

High efficiency will save the operation cost (Energy Saving).

Low iTHD will not pollute the upstream power.

Wide Input Voltage Range 100~280Vac,

High Voltage Protection Up To 330Vac:

(For 100~155Vac, it depends on the loading condition).

It makes UPS can withstand severe power condition. Therefore reducing the chance of battery discharging caused by power fluctuation or transient. Thus extend the lifecycle of battery.


Apr 2009

New R-series Key Benefit (continue )

Standard Charger(4A) And Optional Charger(4A) :

High charging ability and extra charger can be implemented

and built-in UPS (Total 8A) for the application of particular runtime.

Smart Interfaces :

There are two smart interfaces : SNMP and Smart slots

Delta provides different smart cards with powerful function makes UPS become a value-added power protection for customer:

For SNMP Slot : SNMP Card, Modbus Card, Relay I/O Card, Environmental Box, SNMP With 5 Ports Hub

For Smart Slot : Mini SNMP, Mini Relay I/O, Mini USB, TVSS cards.

High Power Density:

5 or 7 KVA capacity in only 2U height. 11KVA in 3U height.

Less space needed and therefore save the precious space of server cabinet.

Optional Battery Pack :

For longer runtime application. 5-7KVA: 2U, 11KVA: 3U


Apr 2009

Comparison - J vs. New R

Capacity 7KVA / 4.9KW 7KVA / 4.9KW

I/P Voltage 156~276Vac 100~300Vac

(Can withstand 330V!)

iTHD <5% < 5%

Parallel Redundancy

Dimension 3U2U

Common Battery

Optional Charger(Can be Built-in)


Apr 2009

Comparison - J vs. New R (continue)

REPO

Battery Pack 3U (12V * 20 pcs) 2U (12V * 16pcs)

Delta Standard CableDelta Standard Cable

Overload <102% : Continue <105% : Continue

102~125% : 1 minute 106~110% : 10 minutes

125~150% : 30 seconds 111~125% : 5 minute

>150% : immediately 126~150% : 30 seconds

>150% : immediately

Interface RS232, SNMP Slot, REPO RS232, SNMP Slot, REPO

Dry Contact Smart Slot

Manual BypassStandard Optional Maintenance Box


Apr 2009

Comparison - J vs. New R

Capacity 11KVA / 7.7KW 11KVA / 7.7KW

I/P Voltage 156~276Vac 100~280Vac

(Can withstand 330V!)

iTHD <5% < 5%

Parallel Redundancy

Dimension 3U (445 x 131 x 563) 3U (440 x 131 x 559)

Common Battery

Optional Charger(Can be Built-in)


Apr 2009

Comparison - J vs. New R (continue)

REPO

Battery Pack 3U (12V * 20 pcs) 3U (12V * 20pcs)

Delta Standard Cable Delta Standard Cable

Overload <102% : Continue <105% : Continue

102~125% : 1 minute 106~110% : 10 minutes

125~150% : 30 seconds 111~125% : 5 minute

>150% : immediately 126~150% : 30 seconds

>150% : immediately

Interface RS232, SNMP Slot, REPO RS232, SNMP Slot, REPO

Dry Contact Smart Slot

Manual Bypass Standard Optional Maintenance Box


Apr 2009

Maintenance Bypass Box

For GAIA Series


Apr 2009

Maintenance Bypass Box - Models

MBB-S: For 5~11 kVA

Maintenance bypass when single UPS is installed.

MBB-P: For 5~11 kVA

Maintenance bypass when two UPSs are in parallel link.


Apr 2009

MBB-S Outlook

  • Dimension (WxDxH): 440 x 135 x 88 mm

  • 2U height.

  • Bypass transfer switch.

Top View

Rear View


Apr 2009

MBB-P Outlook

  • Dimension (WxDxH): 440 x 195 x 131 mm

  • 3U height.

  • Use breaker to be the switch.

Top View

Rear View


Apr 2009

MBB Fixing

MBB-P

MBB-S


Apr 2009

Fixing on Rack


Apr 2009

MBB-S Connection(1)

UPS cable connection

MBB cable connection


Apr 2009

MBB-S Connection(2)

Connect to Line & Load


Apr 2009

MBB-P Connection(1)

UPS Input & Output


Apr 2009

MBB-P Connection(2)

Connect to Line & Load


Apr 2009

MBB-P Connection(3)

Example of Complete Installation

Battery

Cabinets

Battery

Cabinets

UPS2

UPS1

MBB-P


Apr 2009

Why we change MBB types ?

  • Too many models for old MBB accessory (3 types).

  • Old solution for parallel function:

  • cabinet is the same depth as UPS.

  • Waste space and cost.

  • TUV certificated for new models.


Apr 2009