An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. WATER SOUCE SYSTEM

  2. Content • Introduction to Water Source System • General Benefit of Water Source System • Product Lineup • Product (WH, 5WSS, WSS) • Features • Handset • PCB • Control Algorithm • Selft Diagnosis & Troubleshooting • Installation

  3. INTRODUCTION to Water Source System

  4. 4 Way Valve Water inlet Water-to-refrigerant heat exchanger Water outlet Compressor Finned-tube heat exchanger Expansion device Introduction: What is Water Source Heat Pump?

  5. Water Source System Categories 1. Water Loop Heat Pump System 2. Ground Water Heat Pump System 3. Surface Water Heat Pump System 4. Ground Coupled Heat Pump System

  6. Water Source System Categories Water Loop Heat Pump • Most common configuration • Re-circulating water loop • Cooling tower & boiler

  7. Water Source System Categories Ground Water Heat Pump • Ground water from well • Drained back to well, drain, stream or lake • Stable throughout the year • Limited by availability of water table and aquifers in the ground

  8. Water Source System Categories Surface Water Heat Pump • Open or close loop • Open – water being returned back to source or drain • Closed – water being re-circulated in the closed loop • Stable throughout the year

  9. Water Source System Categories Ground Coupled Water Heat Pump • HE is buried into the earth • Installation cost is high • Massive & stable thermal capacity

  10. Water Loop Heat Pump System

  11. air separator expansion tank cooling tower pumps plate-and-frame heat exchanger water distribution loop boiler heat pumps Water Loop Heat Pump System

  12. cooling tower ON 32ºC [90ºF] boiler off heat pumps in cooling mode Water Loop Heat Pump System Summer Operation

  13. cooling tower OFF 16ºC [60ºF] boiler on heat pumps in heating mode Water Loop Heat Pump System Winter Operation

  14. Water Loop Heat Pump System Spring and Fall Operation cooling tower OFF boiler off heat pumps in heating mode heat pumps in cooling mode

  15. General Benefits of a Water Source System • Heat recovery offers energy savings • Individual space control • Performs both cooling and heating • Flexibility – additional of heat pump - Individual tenant metering • Small amount of floor space required • Unit failure does not affect the rest of the system

  16. Product Lineup & Features

  17. Product Lineup Package Type • Horizontal WSHP, WH-B/BR series • Vertical WSHP, WV-A/AR series Split Type • WSS & 5WSS series + Various Indoor

  18. R410A Water Source Split, 5WSS-AR

  19. R410A Water Source Split 5CKWS 20/25/30/40/50 AR 5CKWS 10/15/20 CR 5WMWS 10/15/20/25 GR 5CCWS 10/15/20/25/30/40/50/60 CR 5WSS – AR Series

  20. 1. Features 1.1 Product Information 1.2 Wide Range of Indoor 1.3 Compact & Low Height Profile 1.4 Less Vibration Design 1.5 Zero ODP Refrigerant 1.6 Part Loading Capability – Tandem Type 1.7 Centralize Control & Networking

  21. R410A Water Source Split 1.1 Product Introduction - Heat pump Only - Split Type - Capacity: 2.37kW – 15.77kW - 8,100 Btu/hr to 53,800 Btu/hr

  22. R410A Water Source Split Product Name Btu/hr x 103 0 10 20 30 40 50 60 0 2.93 5.86 8.79 11.72 14.65 17.59 kW 5WSS 07/10/15/16/20/25/30/40/50/60 AR

  23. 1. Features 1.2 Wide Range of Indoor Option • Wall Mounted : 1 hp to 2.5 hp • Ceiling Cassette - A : 2 hp to 5 hp • Ceiling Cassette - C : 1 hp to 2 hp • Ceiling Concealed : 1 hp to 6 hp

  24. 1. Features 1.3 Compact & Low Height Profile ~ 30% volume metric reduction

  25. 1. Features 1.4 Less Vibration Design • Double isolation Panel • Reduce noise and vibration transmission Compressor Upper Panel Grommet Lower Panel

  26. 1. Features 1.5 Zero ODP Refrigerant - In line with Montreal Protocol. 1.6 Part Loading Capability - Compared to 5WSS series, 5WST series is having the part loading capability during the low load condition, which resulting in good SEER, Seasonal EER.

  27. 1. Features 1.7 Centralize Control by Using NIMPC or Smart Manager/ HydroIntel

  28. 2. Handset & PCB 2.1 Handset WM : G11/G12 CK : G7/G8 CC : SLM3

  29. 3. Control Algorithm 3.1 System & Mode Selection 3.2 Features 3.3 Operating Mode 3.4 Protection

  30. 3. Control Algorithm 3.1 System Selection – 5WMWS Modes can be selected via the value of resistor RFAN through slide switch.

  31. 3. Control Algorithm 3.1 MODE Selection – 5WMWS Modes can be selected via the value of resistor RMODE

  32. 3. Control Algorithm 3.1 System Selection – 5CCWS & 5CKWS Modes can be selected via the value of resistor ROPT2

  33. 3. Control Algorithm 3.1 MODE Selection – 5CCWS, 5CKWS Modes can be selected via the value of resistor RMODE

  34. 3.2 Features 3.2.1 Auto Random Restart • Auto random restart at the last state memory setting • Shorted at J_LST jumper at main board • Remove the jumper to have non-auto restart

  35. 3.2 Features Auto Random Restart J_LST

  36. 3.2 Features Power Up Settings Power Up J_LST Shorted J_LST Opened User Set Mode Mode = COOL User Set Temperature Set Temperature = 24˚C User Set Fan Speed Fan Speed = HIGH SWING OFF

  37. 3.2 Features 3.2.2 Unit ON / OFF • 3 ways to turn on / off the system: • (a) On/Off Triggering • Emergency On/Off Button • - System mode setting will rotate in the following • sequence • Heat pump …….>COOL>HEAT>OFF>….. • Cooling …….>COOL>OFF>……. • On/Off button on handsets

  38. 3.2 Features 3.2.2 Unit ON / OFF • (b) Delay timer • Pressing the On/Off will reset the timer to 0 hour • (c) Real time On/Off Timer • Based on internal real time clock • The timer settings are kept so that similar switches can occur 24 hours later. • If emergency ON/OFF switch being press, then the timer will be reset.

  39. 3.2 Features 3.2.3 Sleep Function • Only available for COOL, HEAT & AUTO mode • This function will increase (cooling mode) or decrease (Heating mode) the set temperature with time

  40. 01/212 Hours Ts + 2 Ts + 1 Ts + 1/2 Ts SLEEP set on SLEEP set off 3.2 Features 3.2.3 Sleep Function (Cool Mode)

  41. 3.2 Features 3.2.3 Sleep Function (Heat Mode) SLEEP set on SLEEP set off Ts Ts - 1 Ts - 2 Ts - 3 01/212 Hours

  42. 3.2 Features 3.2.4 Indoor Fan Control • Indoor fan speeds are LOW, MEDIUM, HIGH or AUTO FAN in COOL, HEAT and AUTO modes. • In FAN mode, only HIGH, MEDIUM and LOW speeds are allowed.

  43. 3.2 Features 3.2.5 IONIZER Control • The IONIZER can be turned ON when indoor fan is ON. • The IONIZER will OFF when indoor fan is OFF. Capacitor Ionizer

  44. 20min 30min Set Temperature TURBO Function Conventional Time 3.2 Features 3.2.6 TURBO Function • Available in COOL, HEAT and DRY modes only. • When TURBO function is set, indoor fan will force to HIGH for 20 minutes and working temperature for - Cooling Cycle is Ts – 2˚C - Heating Cycle is Ts + 2˚C • If TURBO & Sleep function activated, Sleep function timer will reset until TURBO function is clear.

  45. 3.3. Operating Mode 3.3.1 Cool Mode 3.3.2 Heat Mode 3.3.3 Auto Fan 3.3.4 AUTO Mode 3.3.5 Defrost Function 3.3.6 Dry Mode

  46. 3.3 Operating Modes 3.3.1 Cool Mode • Compressor will cut in if Tr – Ts > 0.5˚C • Compressor will cut out if Tr < Ts – 1.0˚C Note: Tr = Room Temperature Ts = Set Temperature 23C 26C 24C 22C 25C 24.5C 23C OFF ON

  47. 3.3 Operating Modes 3.3.2 Heat Mode • Compressor will cut in if Tr – Ts < 1.0˚C • Compressor will cut out if Tr –Ts > 3.5˚C Note: Tr = Room Temperature Ts = Set Temperature 3.3.2.1 Heat Pump Model 23C 27C 26C 24C 22C 25C 27.5C 23C ON OFF

  48. 3.3 Operating Modes 3.3.2 Heat Mode • The indoor fan speed modulate according to the Tin coil: - If Tin coil > 40˚C, indoor fan run at user set speed - If Tin coil < 18˚C, indoor fan stop - If Tin coil crosses 30˚C, indoor fan change to low speed Note : Tin coil = Indoor Coil Temperature 3.3.2.2 Hot Start

  49. 3.3 Operating Modes 3.3.2 Heat Mode • 2 selection available at the slide switch – ON/OFF • Factory Preset at OFF option 3.3.2.3 Hot Keep

  50. 3.3 Operating Modes 3.3.2 Heat Mode When compressor cuts out, the indoor fan will runs according to hot keep options. There are 2 options of Hot Keep: (a) Fan On Option (b) Fan Off Option 3.3.2.3 Hot Keep