Intelligent Distribution Substation improves power quality. Irina Melnik – the Netherlands – Session S2 – 0665. MV. MV. Fluctuating loads Distributed generation. LV. LV. Changes in power flows Larger voltage variations. Load. Load. Power. Power. MV. MV. Power. Power.

Download Presentation

Irina Melnik – the Netherlands – Session S2 – 0665

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Intelligent Distribution Substation improves power quality Irina Melnik – the Netherlands – Session S2 – 0665

  2. MV MV • Fluctuating loads • Distributed generation LV LV • Changes in power flows • Larger voltage variations Load Load Power Power MV MV Power Power • Uncertainty for planning • Complex grid operation Load Load Generation Generation Micro Micro Micro PV PV CHP CHP CHP LV LV Micro Micro Micro • Monitoring and control • New technologies PV PV CHP CHP CHP Micro Micro Micro CHP CHP CHP Need for new technologies

  3. Intelligent distribution substation (IntDS) • Developed by a consortium of Dutch industries Additional functions of the IntDS: • Monitoring • Control • Improving Power Quality • Installed and tested in the grid of DSO Alliander

  4. Smart Transformer Electricity storage systemwith bidirectional inverter Measurement system “Intelligent” components of IntDS

  5. IntDS implementation District with large amount ofmicro Combined Heat Powerat customers

  6. Test program • Voltage control • Reduction of harmonic distortion • Reduction of flicker • Mitigation of voltage dips Power Quality improvement by the IntDS:

  7. Voltage control Performed by Smart Transformer: • Electronic tap changer ensuresa constant voltage level on the LV rail of the IntDS. • The voltage control set-pointhas to be determined to achievethe optimal voltage level on PCC’sof all LV customers. Smart Transformer

  8. Voltage control – test results LV bus-bar U avg U max U min control no control LV customer no control control 2 1 3 2 1 3

  9. Harmonic distortion reduction Performed by ESI(Electricity storage inverter) : • Resistive harmonic damping • Passive harmonic dampingThe filter capacitors of the ESI take part in the filtering of harmonics. Electricity storage systemwith bidirectional inverter

  10. Harmonic distortion reduction – test results LV bus-bar H03 max H05 max H07 max THD max no control control no LV customer no control control no

  11. Voltage dips mitigation • Can be performed by:the Smart Transformerthe ESI (Electricity storage inverter) • Voltage dips occur only a few times per yearon an LV bus-bar of Dutch distribution substations.That’s why this functionality is not actively tested.

  12. Flicker reduction (LV side) Performed by: • The electronic tap changer of the Smart Transformer • The flicker reduction control of the bidirectional inverter (ESI) of the storage system.

  13. Flicker reduction – test results LV bus-bar no control LV customer Plt avg Pst avg Plt max Pst max no control

  14. Conclusions • The Intelligent substation has proved to be safe in operation. • The first field test results demonstrate a significant reduction of voltage variations, harmonic and THD levels both at the LV bus-bar of the IntDS and at the LV customers. • Further metering and test programs will be performed to set optimal set-points for control equipments. • The proved principles can be used for area’s with high levels of PQ distortions. Irina Melnik – the Netherlands – Session S2 – 0665