CFE EM-BT301 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL CFE EM-BT302 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

Download Presentation

ESPECIFICACIONES DE MEDICION PARA ACOMETIDAS TRIFASICAS

An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -

Presentation Transcript


Especificaciones de medicion para acometidas trifasicas

CFE EM-BT301 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL

CFE EM-BT302 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

CFE EM-BT303 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL

CFE EM-BT304 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

CFE EM-BT305 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANADA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, CON BARDA FRONTAL

CFE EM-BT306 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

CFE EM-BT307 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED SUBTERRANEA, CON BARDA FRONTAL

CFE EM-BT308 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

CFE EM-BT309 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANADA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, EN ZONAS DE ARQUITECTURA COLONIAL

CFE EM-BT310 ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, EN ZONAS DE ARQUITECTURA COLONIAL

CFE EM-BT3

ESPECIFICACIONES DE MEDICION PARA ACOMETIDAS TRIFASICAS


Especificaciones de medicion para acometidas trifasicas

1

3

7

ACOTACIONES EN mm

SIN ESCALA

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL

CFE EM-BT301

HOJA 1 DE 2

#310

VISTA DE CONJUNTO

F1

F1

2

F2

F2

F3

F3

N

N

500 mm DELONGITUD

#310

6

5

4800

12

C F E

13

4

1800

PARA CONEXIONES ENLA BASE ENCHUFEVER DETALLE

8

9

10

11

VISTA LATERAL

VISTA FRONTAL


Especificaciones de medicion para acometidas trifasicas

5

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL

CFE EM-BT301

HOJA 2 DE 2

ESPECIFICACIONES DE MATERIALES Y EQUIPO

DE LA ACOMETIDA

F3F2F1

N

A CARGO DEL USUARIO

2

1 MUFA INTEMPERIE DE 38 mm (1 1/2") DE DIAMETRO

2 TUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 38 FFFmm (1 1/2")DE DIAMETRO Y CON 3000 mm DE LONGITUD3 CABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE A CALIBRES Y DEMANDAS, DESDE LA MUFA HASTA EL . INTERRUPTOR,EL FORRO DEL CONDUCTOR NEUTRO DE . COLOR BLANCO Y LOSDE LAS FASES DIFERENTES AL BLANCO4 BASE ENCHUFE DE 7 TERMINALES, 100 AMPERES TIPO AEREA A A A CON TAPA 5 INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS,100 FFFAMPERES A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIE 6 MONITOR Y CONTRATUERCA DE 38 mm (1 1/2")7 REDUCCION DE 38 mm (1 1/2") A 12,7 mm (1/2")8 TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETRO9 ALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMO 10 CONECTOR PARA VARILLA DE TIERRA 11 VARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS

4

A INSTALACIONINTERIOR

6

A VARILLADE TIERRA

DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR

INSTALADO POR C.F.E.

MEDIDOR TIPO ENCHUFE DE 15(100) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (FD21)SELLO DE PLASTICO

1213

AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBE SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y LA TAPA

NOTAS :

TAPA DE LA BASE

A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR

COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA

EL SERVICIO

B EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A

LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION

( FUSIBLE O TERMOMAGNETICO )

C LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL

LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA

D EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O

CONSTRUCCION

E LA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE

4800 mm

F EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm

DEL MEDIDOR

G MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE

MURO

DETALLE DE EMPOTRADO DE BASE

4

PROPIEDADDEL USUARIO

VIAPUBLICA

MEDIDOR

VISTA DE PLANTA

ACOTACIONES EN mm SIN ESCALA


Especificaciones de medicion para acometidas trifasicas

ACOTACIONES EN mm

SIN ESCALA

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

CFE EM-BT302

HOJA 1 DE 2

VISTA DE CONJUNTO

3

1

F1

F2

N

F1

F3

N

F2

F3

500 mm DELONGITUD

2

220

MINIMO

300

MINIMO

MURETEDECONCRETO

MURETE

ARMADO DE

CONCRETO Y

VARILLA

12

4800

4

13

13

C F E

2800

MINIMO

14

5

1800

7

8

A INSTALACIONINTERIOR

10

9

A INSTALACIONINTERIOR

CIMIENTO DE PIEDRA

CON CEMENTO Y ARENA

11

VISTA LATERAL

VISTA FRONTAL


Especificaciones de medicion para acometidas trifasicas

5

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

CFE EM-BT302

HOJA 2 DE 2

ESPECIFICACIONES DE MATERIALES Y EQUIPO

DE LA ACOMETIDA

F3F2F1

N

A CARGO DEL USUARIO

2

1 MUFA INTEMPERIE DE 38 mm (1 1/2") DE DIAMETRO

2 TUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 38 FFFmm (1 1/2")DE DIAMETRO Y CON 3000 mm DE LONGITUD 3 CABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE CALIBRES . Y DEMANDAS DESDE LA BASE HASTA EL INTERRUPTOR, EL . FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS DE . LAS FASES DIFERENTES AL BLANCO 5 INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS,100 FFFAMPERES A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIE 6 MONITOR Y CONTRATUERCA DE 38 mm ( 1 1/2”) 7 REDUCCION DE 38 mm (1 1/2") A 12,7 mm (1/2")8 TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETRO9 ALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMO 10 CONECTOR PARA VARILLA DE TIERRA 11 VARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS 12 MURETE DE ACUERDO A LO INDICADO

4

A INSTALACIONINTERIOR

6

A VARILLADE TIERRA

DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR

INSTALADO POR C.F.E.

AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y LA TAPA

MEDIDOR TIPO ENCHUFE DE 15(100) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (FD21)SELLO DE PLASTICO

1314

NOTAS :

BASE ENCHUFE

A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR

COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA

EL SERVICIO

B EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A

LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION

( FUSIBLE O TERMOMAGNETICO )

C LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL

LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA

D EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O

CONSTRUCCION

E LA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE

4800 mm

F EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm

DEL MEDIDOR

G MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE

TAPA DE LA BASE

MURO DECONCRETO

DETALLE DE EMPOTRADO DE LA BASE

PROPIEDADDEL USUARIO

VIAPUBLICA

MEDIDOR

VISTA DE PLANTA

ACOTACIONES EN mm SIN ESCALA


Especificaciones de medicion para acometidas trifasicas

1

3

7

ACOTACIONES EN mm

SIN ESCALA

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL

CFE EM-BT303

HOJA 1 DE 2

#310

VISTA DE CONJUNTO

F1

F1

2

F2

F2

F3

F3

N

N

500 mm DELONGITUD

#310

6

5

4800

12

C F E

13

4

1800

PARA CONEXIONES ENLA BASE ENCHUFEVER DETALLE

8

9

10

11

VISTA LATERAL

VISTA FRONTAL


Especificaciones de medicion para acometidas trifasicas

5

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED AEREA, CON BARDA FRONTAL

CFE EM-BT303

HOJA 2 DE 2

ESPECIFICACIONES DE MATERIALES Y EQUIPO

DE LA ACOMETIDA

F3F2F1

N

A CARGO DEL USUARIO

2

1 MUFA INTEMPERIE DE 63.5 mm (2 1/2") DE DIAMETRO

2 TUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE63.5 . mm (2 1/2")DE DIAMETRO Y CON 3000 mm DE LONGITUD3 CABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE .CALIBRES Y DEMANDAS, DESDE LA MUFA HASTA EL INTERRUPTOR, . EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS .DE LAS FASES DIFERENTES AL BLANCO4 BASE ENCHUFE DE 7 TERMINALES, 200 AMPERES TIPO AEREA A A A CON TAPA 5 INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 200 FF AMPERES A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIE 6 MONITOR Y CONTRATUERCA DE 63.5 mm (2 1/2")7 REDUCCION DE 63.5 mm (2 1/2") A 12,7 mm (1/2")8 TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETRO9 ALAMBRE O CABLE DE COBRE DE CALIBRE SEGÚN LA TABLA DE

CALIBRES Y DEMANDAS

10 CONECTOR PARA VARILLA DE TIERRA 11 VARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS

4

A INSTALACIONINTERIOR

6

A VARILLADE TIERRA

DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR

INSTALADO POR C.F.E.

MEDIDOR TIPO ENCHUFE DE 30(200) AMPERES, 3 FASES, 4 HILOS, 120 - 480 VOLTS (KL28)SELLO DE PLASTICO

1213

AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBE SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y LA TAPA

NOTAS :

TAPA DE LA BASE

A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR

COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA

EL SERVICIO

B EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A

LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION

( FUSIBLE O TERMOMAGNETICO )

C LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL

LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA

D EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O

CONSTRUCCION

E LA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE

4800 mm

F EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm

DEL MEDIDOR

G MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE

13

MURO

DETALLE DE EMPOTRADO DE BASE

4

PROPIEDADDEL USUARIO

VIAPUBLICA

MEDIDOR

VISTA DE PLANTA

ACOTACIONES EN mm SIN ESCALA


Especificaciones de medicion para acometidas trifasicas

ACOTACIONES EN mm

SIN ESCALA

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

CFE EM-BT304

HOJA 1 DE 2

#305

VISTA DE CONJUNTO

3

1

F1

F2

N

F1

F3

N

F2

F3

500 mm DELONGITUD

2

220

MINIMO

300

MINIMO

MURETEDECONCRETO

MURETE

ARMADO DE

CONCRETO Y

VARILLA

12

4800

4

13

13

C F E

2800

MINIMO

14

5

1800

7

8

A INSTALACIONINTERIOR

10

9

A INSTALACIONINTERIOR

CIMIENTO DE PIEDRA

CON CEMENTO Y ARENA

11

VISTA LATERAL

VISTA FRONTAL


Especificaciones de medicion para acometidas trifasicas

5

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED AEREA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

CFE EM-BT304

HOJA 2 DE 2

ESPECIFICACIONES DE MATERIALES Y EQUIPO

DE LA ACOMETIDA

F3F2F1

A CARGO DEL USUARIO

N

2

1 MUFA INTEMPERIE DE 63.5 mm (2 1/2") DE DIAMETRO

2 TUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE

63.5 mm (2 1/2")DE DIAMETRO Y CON 3000 mm DE LONGITUD3 CABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE A CALIBRES Y DEMANDAS, DESDE LA MUFA HASTA EL . INTERRUPTOR, A EL FORRO DEL CONDUCTOR NEUTRO DE . COLOR BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCO4 BASE ENCHUFE DE 7 TERMINALES, 200 AMPERES TIPO AEREA A A A CON TAPA 5 INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 200 FFFAMPERES A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIE 6 MONITOR Y CONTRATUERCA DE 63.5 mm ( 2 1/2”)7 REDUCCION DE 63.5 mm (2 1/2") A 12,7 mm (1/2")

8 TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETRO9 ALAMBRE O CABLE DE COBRE CALIBRE SEGÚN LA TABLA DE . CALIBRES Y DEMANDAS 10 CONECTOR PARA VARILLA DE TIERRA 11 VARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS 12 MURETE DE ACUERDO A LO INDICADO

4

A INSTALACIONINTERIOR

6

A VARILLADE TIERRA

DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR

INSTALADO POR C.F.E.

AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y LA TAPA

MEDIDOR TIPO ENCHUFE DE 30(200) AMPERES, 3 FASES, 4 HILOS, 120 - 480 VOLTS (KL28)SELLO DE PLASTICO

1314

NOTAS :

BASE ENCHUFE

A LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR

COMO MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA

EL SERVICIO

B EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A

LA CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION

( FUSIBLE O TERMOMAGNETICO )

C LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL

LIMITE DE PROPIEDAD, EMPOTRADA O SOBREPUESTA

D EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O

CONSTRUCCION

E LA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA ES DE

4800 mm

F EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm

DEL MEDIDOR

G MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE

TAPA DE LA BASE

MURO DECONCRETO

DETALLE DE EMPOTRADO DE LA BASE

PROPIEDADDEL USUARIO

VIAPUBLICA

MEDIDOR

VISTA DE PLANTA

ACOTACIONES EN mm SIN ESCALA


Especificaciones de medicion para acometidas trifasicas

ACOTACIONES EN mm

SIN ESCALA

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANADA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, CON BARDA FRONTAL

CFE EM-BT305

HOJA 1 DE 2

#411

C F E

DUCTO RED B.T.

DUCTO RED B.T.

REGISTRO DE ACOMETIDAEN B.T.

VISTA DE CONJUNTO

4

11

C F E

5

12

6

1800

1800

7

2

13

VER DETALLE "A"

8

1

9

10

SECUNDARIO DE LA RED

VISTA FRONTAL

VISTA LATERAL


Especificaciones de medicion para acometidas trifasicas

5

DISPONIBLES

15

14

ACOMETIDA

SECUNDARIODE LA RED

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANADA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, CON BARDA FRONTAL

CFE EM-BT305

HOJA 2 DE 2

ESPECIFICACIONES DE MATERIALES Y EQUIPO

A CARGO DEL USUARIO

3

1

CODO DE PVC 38 mm ( 1 1/2” ) DE DIAMETROTUBO RIGIDO DE PVC 38 mm ( 1 1/2” ) DE DIAMETROCABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDAS DESDE LA BASE HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCOBASE ENCHUFE DE 7 TERMINALES, 100 AMPERES INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 100 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE PVC 38 mm (1 1/2") A 12,7 mm (1/2")TUBO RIGIDO PVC DE 12.7 mm ( 1/2” ) DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMOCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS

2

3

4

A INSTALACIONINTERIOR

4

5

A VARILLADE TIERRA

2

DEL

REGISTRO

6

7

8

9

10

DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR

INSTALADO POR C.F.E.

AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y LA TAPA

11

MEDIDOR TIPO ENCHUFE DE 15(100) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (FD21)

SELLO DE PLASTICO

CABLE DE ALUMINIO XLP A LA BASE ENCHUFE

CONECTOR EMPALME A COMPRESION TENSION MINIMA

TIPO ZAPATA

MANGA TERMOCONTRACTIL O REMOVIBLE

12

13

14

BASE ENCHUFE

15

TAPA DE LA BASE

NOTAS :

MURO DECONCRETO

A. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO

MAXIMO A 35 METROS DEL REGISTRO.

B. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA

CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION

( FUSIBLE O TERMOMAGNETICO )

C. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL

LIMITE DE LA PROPIEDAD EMPOTRADA D. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONE. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR

F. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE

DETALLE DE EMPOTRADO DE LA BASE

DETALLE “A”

PROPIEDADDEL USUARIO

VIAPUBLICA

MEDIDOR

VISTA DE PLANTA

ACOTACIONES EN mm SIN ESCALA


Especificaciones de medicion para acometidas trifasicas

ACOTACIONES EN mm

SIN ESCALA

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

CFE EM-BT306

HOJA 1 DE 2

#435

DUCTO

RED DE

BAJA TENSION

VISTA DE CONJUNTO

220

300

5

13

11

2

2000

1800

14

8

VISTA FRONTAL

VISTA LATERAL


Especificaciones de medicion para acometidas trifasicas

5

DISPONIBLES

16

15

ACOMETIDA

SECUNDARIODE LA RED

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

CFE EM-BT306

HOJA 2 DE 2

ESPECIFICACIONES DE MATERIALES Y EQUIPO

A CARGO DEL USUARIO

3

CODO DE PVC 38 mm ( 1 1/2” ) DE DIAMETROTUBO RIGIDO DE PVC 38 mm ( 1 1/2” ) DE DIAMETROCABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDAS DESDE LA BASE HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCOBASE ENCHUFE DE 7 TERMINALES, 100 AMPERES INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 100 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE PVC 38 mm (1 1/2") A 12,7 mm (1/2")TUBO RIGIDO PVC DE 12.7 mm ( 1/2” ) DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMO

CONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS MURETE DE ACUERDO A LO INDICADO

1

2

3

4

A INSTALACIONINTERIOR

4

5

A VARILLADE TIERRA

2

DEL

REGISTRO

6

7

8

9

10

DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR

11

INSTALADO POR C.F.E.

AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 10mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO

12

MEDIDOR TIPO ENCHUFE DE 15(100) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (FD21)

SELLO DE PLASTICO

CABLE DE ALUMINIO XLP A LA BASE ENCHUFE

CONECTOR EMPALME A COMPRESION TENSION MINIMA

TIPO ZAPATA

MANGA TERMOCONTRACTIL O REMOVIBLE

13

14

15

BASE ENCHUFE

16

TAPA DE LA BASE

NOTAS :

MURO DECONCRETO

A. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO

MAXIMO A 35 METROS DEL REGISTRO.

B. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA

CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION

( FUSIBLE O TERMOMAGNETICO )

C. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL

LIMITE DE LA PROPIEDAD EMPOTRADA D. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONE. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR

F. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE

DETALLE DE EMPOTRADO DE LA BASE

DETALLE “A”

PROPIEDADDEL USUARIO

VIAPUBLICA

MEDIDOR

VISTA DE PLANTA

ACOTACIONES EN mm SIN ESCALA


Especificaciones de medicion para acometidas trifasicas

ACOTACIONES EN mm

SIN ESCALA

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED SUBTERRANEA, CON BARDA FRONTAL

CFE EM-BT307

HOJA 1 DE 2

#411

C F E

DUCTO RED B.T.

DUCTO RED B.T.

REGISTRO DE ACOMETIDAEN B.T.

VISTA DE CONJUNTO

4

11

C F E

5

12

6

1800

1800

7

2

13

VER DETALLE "A"

8

1

9

10

SECUNDARIO DE LA RED

VISTA FRONTAL

VISTA LATERAL


Especificaciones de medicion para acometidas trifasicas

5

DISPONIBLES

15

14

ACOMETIDA

SECUNDARIODE LA RED

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED SUBTERRANEA, CON BARDA FRONTAL

CFE EM-BT307

HOJA 2 DE 2

ESPECIFICACIONES DE MATERIALES Y EQUIPO

A CARGO DEL USUARIO

3

1

CODO DE PVC 63.5 mm ( 2 1/2” ) DE DIAMETROTUBO RIGIDO DE PVC 63.5 mm ( 2 1/2” ) DE DIAMETROCABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDAS DESDE LA BASE HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCOBASE ENCHUFE DE 7 TERMINALES, 200 AMPERES INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 200 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE PVC 32 mm (1 1/4") A 12,7 mm (1/2")TUBO RIGIDO PVC DE 63.5 mm ( 2 1/2” ) A 12.7 mm ( 1/2” ) DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE SEGÚN TABLA DE CALIBRES Y DEMANDASCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS

2

3

4

A INSTALACIONINTERIOR

4

5

A VARILLADE TIERRA

2

DEL

REGISTRO

6

7

8

DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR

9

10

INSTALADO POR C.F.E.

AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO

11

MEDIDOR TIPO ENCHUFE DE 30(200) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (KL28)

SELLO DE PLASTICO

CABLE DE ALUMINIO XLP A LA BASE ENCHUFE

CONECTOR EMPALME A COMPRESION TENSION MINIMA

TIPO ZAPATA

MANGA TERMOCONTRACTIL O REMOVIBLE

12

13

14

BASE ENCHUFE

15

TAPA DE LA BASE

NOTAS :

MURO DECONCRETO

A. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO

MAXIMO A 35 METROS DEL REGISTRO.

B. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA

CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION

( FUSIBLE O TERMOMAGNETICO )

C. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL

LIMITE DE LA PROPIEDAD EMPOTRADA D. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONE. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR

F. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE

DETALLE DE EMPOTRADO DE LA BASE

DETALLE “A”

PROPIEDADDEL USUARIO

VIAPUBLICA

MEDIDOR

VISTA DE PLANTA

ACOTACIONES EN mm SIN ESCALA


Especificaciones de medicion para acometidas trifasicas

ACOTACIONES EN mm

SIN ESCALA

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

CFE EM-BT308

HOJA 1 DE 2

#590

DUCTO

RED DE

BAJA TENSION

VISTA DE CONJUNTO

220

300

5

13

11

2

2000

1800

14

8

VISTA FRONTAL

VISTA LATERAL


Especificaciones de medicion para acometidas trifasicas

5

DISPONIBLES

16

15

ACOMETIDA

SECUNDARIODE LA RED

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA DE 26 kW A 50 kW EN BAJA TENSION, RED SUBTERRANEA, CONSTRUCCION AL FONDO DE LA PROPIEDAD

CFE EM-BT308

HOJA 2 DE 2

ESPECIFICACIONES DE MATERIALES Y EQUIPO

A CARGO DEL USUARIO

3

1

CODO DE PVC 63.5 mm ( 2 1/2” ) DE DIAMETROTUBO RIGIDO DE PVC 63.5 mm ( 2 1/2” ) DE DIAMETROCABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDAS DESDE LA BASE HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCOBASE ENCHUFE DE 7 TERMINALES, 200 AMPERES INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 200 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE PVC 63.5 mm (2 1/2") A 12,7 mm (1/2")TUBO RIGIDO PVC DE 12.7 mm ( 1/2” ) DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDASCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS MURETE DE ACUERDO A LO INDICADO

2

3

4

A INSTALACIONINTERIOR

4

5

A VARILLADE TIERRA

2

DEL

REGISTRO

6

7

8

9

DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR

10

11

INSTALADO POR C.F.E.

AL EMPOTRAR LA BASE ENCHUFE, ESTA DEBERA SALIR COMO MINIMO 10 mm DEL MURO PARA COLOCAR EL MEDIDOR Y EL ARO

12

MEDIDOR TIPO ENCHUFE DE 30(200) AMPERES, 3 FASES, 4 HILOS, 120 - 480 VOLTS (KL28)

SELLO DE PLASTICO

CABLE MONOPOLAR XLP A LA BASE ENCHUFE

CONECTOR EMPALME A COMPRESION TENSION MINIMA

TIPO ZAPATA

MANGA TERMOCONTRACTIL O REMOVIBLE

13

14

15

BASE ENCHUFE

16

TAPA DE LA BASE

NOTAS :

MURO DECONCRETO

A. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO

MAXIMO A 35 METROS DEL REGISTRO.

B. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA

CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION

( FUSIBLE O TERMOMAGNETICO )

C. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL

LIMITE DE LA PROPIEDAD EMPOTRADA D. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONE. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR

F. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE

DETALLE DE EMPOTRADO DE LA BASE

DETALLE “A”

PROPIEDADDEL USUARIO

VIAPUBLICA

MEDIDOR

VISTA DE PLANTA

ACOTACIONES EN mm SIN ESCALA


Especificaciones de medicion para acometidas trifasicas

7

ACOTACIONES EN mm

SIN ESCALA

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANADA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, EN ZONAS DE ARQUITECTURA COLONIAL

CFE EM-BT309

HOJA 1 DE 2

72

74

76

VISTA DE CONJUNTO

3

1

F1

2

F2

N

F3

500 mm DELONGITUD

F3

N

F2

F1

350

12

4

4800

500

C F E

5

1800

13

MURODEADOBE

8

9

INTERIOR

BANQUETA

10

11

VISTA FRONTAL

VISTA LATERAL


Especificaciones de medicion para acometidas trifasicas

5

DISPONIBLES

15

14

ACOMETIDA

SECUNDARIODE LA RED

PROPIEDADDEL USUARIO

MEDIDOR

VIAPUBLICA

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANADA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED AEREA, EN ZONAS DE ARQUITECTURA COLONIAL

CFE EM-BT309

HOJA 2 DE 2

DE LA ACOMETIDA

F3F2F1

ESPECIFICACIONES DE MATERIALES Y EQUIPO

N

2

A CARGO DEL USUARIO

1 MUFA INTEMPERIE DE 38 mm (1 1/2") DE DIAMETRO 2 TUBO CONDUIT DE FIERRO GALVANIZADO PARED GRUESA DE 38 FFFmm (1 1/2")DE DIAMETRO Y CON 3000 mm DE LONGITUD3 CABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE A CALIBRES Y DEMANDAS, DESDE LA MUFA HASTA EL . INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR . BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCO4 BASE ENCHUFE DE 7 TERMINALES, 100 AMPERES TIPO AEREA A A A CON TAPA 5 INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS,100 FFFAMPERES A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIE 6 MONITOR Y CONTRATUERCA DE 38 mm (1 1/2”) 7 REDUCCION DE 38 mm (1 1/2") A 12,7 mm (1/2")8 TUBO CONDUIT PARED DELGADA DE 12,7 mm (1/2") DE DIAMETRO9 ALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMO 10 CONECTOR PARA VARILLA DE TIERRA 11 VARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS

A INSTALACIONINTERIOR

4

6

A VARILLADE TIERRA

7

DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR

INSTALADO POR C.F.E.

12

MEDIDOR TIPO ENCHUFE DE 15(100) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (FD21)

400

13

SELLO DE PLASTICO

14

CONECTOR EMPALME A COMPRESIÓN A TENSION MINIMATIPO ZAPATA

MANGA TERMOCONTRACTIL O REMOVIBLE

15

NOTAS :

500

A. EL NICHO PARA MEDIDOR SERA DE CONCRETO ARMADO DE

500 X 400 X 350 mm

B. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO

MAXIMO A 35 METROS DEL POSTE DESDE EL CUAL SE DARA EL SERVICIO.

C. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA

CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION

( FUSIBLE O TERMOMAGNETICO )

D. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL

LIMITE DE LA PROPIEDAD EMPOTRADA E. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONF. LA ALTURA DE LA MUFA PARA RECIBIR LA ACOMETIDA SERA DE 4800 mm

G. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR

H. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE

MALLAMETALICA

PUERTA DEL NICHOCON APLANADO IDENTICOAL MATERIAL DE LA FACHADA

DETALLE PUERTA DEL NICHO

DETALLE “A”

VISTA DE PLANTA

ACOTACIONES EN mm SIN ESCALA


Especificaciones de medicion para acometidas trifasicas

6

ACOTACIONES EN mm

SIN ESCALA

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, EN ZONAS DE ARQUITECTURA COLONIAL

CFE EM-BT310

HOJA 1 DE 2

72

74

76

REGISTRO DE

ACOMETIDA BAJA TENSION

DUCTO RED BAJA TENSION

DUCTO RED

BAJA TENSION

VISTA DE CONJUNTO

4

350

400

11

500

500

C F E

5

1800

12

MURODEADOBE

7

2

8

VER

DEATLLE “A”

13

INTERIOR

BANQUETA

1

9

10

VISTA FRONTAL

VISTA LATERAL


Especificaciones de medicion para acometidas trifasicas

5

DISPONIBLES

15

14

ACOMETIDA

PROPIEDADDEL USUARIO

SECUNDARIODE LA RED

MEDIDOR

VIAPUBLICA

ESPECIFICACION PARA SERVICIO TRIFASICO CON DEMANDA CONTRATADA HASTA 25 kW EN BAJA TENSION, RED SUBTERRANEA, EN ZONAS DE ARQUITECTURA COLONIAL

CFE EM-BT310

HOJA 2 DE 2

ESPECIFICACIONES DE MATERIALES Y EQUIPO

A CARGO DEL USUARIO

3

1

CODO DE PVC 38 mm ( 1 1/2” ) DE DIAMETROTUBO RIGIDO DE PVC 38 mm ( 1 1/2” ) DE DIAMETROCABLE DE COBRE THW CALIBRE SEGÚN LA TABLA DE CALIBRES Y DEMANDAS DESDE LA BASE HASTA EL INTERRUPTOR, EL FORRO DEL CONDUCTOR NEUTRO DE COLOR BLANCO Y LOS DE LAS FASES DIFERENTES AL BLANCOBASE ENCHUFE DE 7 TERMINALES, 100 AMPERES INTERRUPTOR TERMOMAGNETICO (PREFERENTEMENTE) O DE CARTUCHO FUSIBLE DE 3 POLOS, 1 TIRO, 250 VOLTS, 100 AMPERES, A PRUEBA DE AGUA CUANDO QUEDE A LA INTEMPERIEREDUCCION DE PVC 38 mm (1 1/2") A 12,7 mm (1/2")TUBO RIGIDO PVC DE 12.7 mm ( 1/2” ) DE DIAMETROALAMBRE O CABLE DE COBRE CALIBRE 8.367 mm2 (8 AWG) MINIMOCONECTOR PARA VARILLA DE TIERRAVARILLA DE TIERRA PARA UNA RESISTENCIA MAXIMA DE 25 OHMS

2

3

4

A INSTALACIONINTERIOR

4

5

A VARILLADE TIERRA

2

DEL

REGISTRO

6

7

8

9

10

DETALLE DE ALAMBRADO DE LA BASEE INTERRUPTOR

INSTALADO POR C.F.E.

11

MEDIDOR TIPO ENCHUFE DE 15(100) AMPERES, 3 FASES, 4 HILOS, 120 VOLTS (FD21)

400

SELLO DE PLASTICO

CABLE MONOPOLAR XLP A LA BASE ENCHUFE

CONECTOR EMPALME A COMPRESION TENSION MINIMA

TIPO ZAPATA

MANGA TERMOCONTRACTIL O REMOVIBLE

12

13

14

15

500

NOTAS :

A. EL NICHO PARA MEDIDOR SERA DE CONCRETO ARMADO DE

500 X 400 X 350 mm

B. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR COMO

MAXIMO A 35 METROS DEL REGISTRO.

C. EL CONDUCTOR DEL NEUTRO DEBE DE CONECTARSE DIRECTO A LA

CARGA SIN PASAR POR ALGUN MEDIO DE PROTECCION

( FUSIBLE O TERMOMAGNETICO )

D. LA PREPARACION PARA RECIBIR LA ACOMETIDA DEBE ESTAR AL

LIMITE DE LA PROPIEDAD EMPOTRADA E. EVITAR QUE LA ACOMETIDA CRUCE OTRO TERRENO O CONSTRUCCIONF. EL INTERRUPTOR ESTARA A UNA DISTANCIA NO MAYOR A 5000 mm DEL MEDIDOR

G. MARCAR EL NUMERO OFICIAL DEL DOMICILIO EN FORMA PERMANENTE

MALLAMETALICA

PUERTA DEL NICHOCON APLANADO IDENTICOAL MATERIAL DE LA FACHADA

DETALLE PUERTA DEL NICHO

DETALLE “A”

VISTA DE PLANTA

ACOTACIONES EN mm SIN ESCALA