Discovery Communications. Headquarters. Silver Springs, MD. Josh Woolcock Structural Option. Architectural Engineering Pennsylvania State University. Outline. Building Information Existing Conditions Structural Analysis Cost Analysis Schedule Analysis Office Lighting Design

loader
I am the owner, or an agent authorized to act on behalf of the owner, of the copyrighted work described.
capcha
Download Presentation

PowerPoint Slideshow about 'Discovery Communications Headquarters' - deiondre


An Image/Link below is provided (as is) to download presentation

Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author.While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server.


- - - - - - - - - - - - - - - - - - - - - - - - - - E N D - - - - - - - - - - - - - - - - - - - - - - - - - -
Presentation Transcript
Slide1 l.jpg

Discovery Communications

Headquarters

Silver Springs, MD

Josh Woolcock

Structural Option

Architectural Engineering

Pennsylvania State University


Outline l.jpg
Outline

  • Building Information

  • Existing Conditions

  • Structural Analysis

  • Cost Analysis

  • Schedule Analysis

  • Office Lighting Design

  • Conclusions

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide3 l.jpg

Project Team

Owner

Discovery

Communications Inc.

Architect

SmithGroup Inc.

General Contractor

Clark Construction

Engineers

Structural – KTLH Engineering

Civil – VIKA Inc.

MEP – Flack & Kurtz

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide4 l.jpg

Building Overview

Layout & Function

- Multipurpose Office Facility

- two independent towers, of 7 and 10-stories

- 3 levels of underground parking

- 550,000 sqft. of open office space

- $52 Million overall cost

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide5 l.jpg

Existing ConditionsMechanical

  • Individual air-handling units on each floor

  • Duct work for tenant build-out

  • - 3 centrifugal water chillers and roof cooling towers

  • - 3 gas-fired furnaces

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide6 l.jpg

Existing ConditionsLighting / Electrical

- Three 4,000A three-phase feeders for three switchboards, totaling 12,000A

- Lighting in office space reserved for tenant build-out

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide7 l.jpg

Existing ConditionsStructural

  • - CIP Concrete Structural System

  • - Two structurally independent towers

  • - 2-way cambered 9” structural slab with drop panels

  • 30’ x 30’ column grid

  • Column sizes up to 36” x 48”

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide8 l.jpg

Structural Analysis

Focus

North Tower: 10 Office Floors & Penthouse

Purpose

To reduce the size of the columns within the office spaces to reduce concrete volume, increase floor space and promote aesthetics.

Reasons for Initial Size

- Act as both lateral and gravity system

- Building sway constraints

- Large dead Loads

Possible Solutions

- Separation of Lateral and Gravity Systems

- Reduction of Gravity Loads

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide9 l.jpg

Structural AnalysisInitial Considerations

  • Loads calculated from IBC2000

  • Deflection Requirements

    • H/400 for service wind loads

    • H/50 for service seismic loads

    • Respect to other tower: Contact at 8th Floor

  • Building Geometry

    • Much longer than it is wide

  • -Secondary Considerations

    • -Building Floor Plan and Impact

    • Impact on other building systems

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide10 l.jpg

Structural AnalysisFloor Slab Reduction

  • ADOSS was used: Equivalent Frame Method

  • Floor slab construction switched from 4000psi to 5000psi concrete

  • Slab thickness reduced from 9” to 8”

  • Drop panels remain 7.5”

  • Slab Reinforcement increased from an average of 4.46psf to 4.89psf

  • Maximum D+L deflection is 0.759”

  • Slab weight was reduced by 11% or 11.25kip per column per floor

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide11 l.jpg

Structural AnalysisShear Walls

  • 4 preliminary locations for shear walls

  • Locations do no hinder original floor plan

  • Tests were performed to determine their lateral performance

  • Use of 4 walls resulted in excess torsion

  • 2 shear walls were implemented and located to reduce torsion in building

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide12 l.jpg

Structural AnalysisShear Wall Design

  • Walls Start at floor 1 and continue to main roof

  • Walls span column-to-column

  • Design changes at floors 1,3,5 & 7

  • Maximum loads – Wind w/ Torsion & Factored

    • 765.3 kip Shear

    • 57269.81ft-kip Bending

    • 1909 kip Axial

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide13 l.jpg

Structural AnalysisShear Wall Design

  • 24” x 36” columns at ends

  • Concrete strength

    • 10000psi at Floor 1

    • 8000psi at Floor 3

    • 4000psi at floor 5

  • Wall Reinforcement

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide14 l.jpg

Structural AnalysisShear Transfer

  • Shear Walls stop at first floor

  • Columns continue down to foundation

    • No Bending in Slab

  • - Shear transferred from walls to floor slab then to retaining walls

  • - Lateral earth pressure resists shear and locks floor 1 in place

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide15 l.jpg

Structural AnalysisColumn Reduction

  • All Columns within office spaces are 24” x 24”

  • 4 different column designs

  • Concrete Strengths

    • 8000psi Floor 1

    • 6000psi Floor 3

    • 4000psi Floor 5

    • 4000psi Floor 7

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide16 l.jpg

Structural AnalysisFinal Lateral System

  • North-South Direction

    • Combination of Shear walls and Moment Frames

    • Contribution via stiffness analysis

      • 66.8% Shear walls at floor 10

      • 90.1% Shear walls at floor 5

      • 96.3% Shear walls at Floor 1

  • East-West Direction

    • Moment Frames

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide17 l.jpg

Structural AnalysisLateral System Performance

  • North-South Direction

Notes:

Max Wind = 2.66”

Max Seismic = 2.54”

  • East-West Direction

Notes:

Max Wind = 2.32”

Max Seismic = 4.44”

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide18 l.jpg

Structural AnalysisConclusions

  • Reduction in floor slab produced a 11% decrease in slab dead load on columns

  • Implementation of Shear Walls reduced bending stresses in columns due to lateral forces

  • Column size was reduced to 24”x24” throughout the office spaces

  • - Placement of Shear Walls did not adversely affect building floor plan or mechanical and fire protection services

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide19 l.jpg

Cost AnalysisInitial Considerations

Purpose

Determine cost implications of new structural systems

- Detailed Estimate performed on both original and new structural systems

- Costs Estimated using RSMeans 2001

- Bare Costs : Overhead and Profit not included

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide20 l.jpg

Cost AnalysisColumns

Notes:

- 43.8% Reduction in volume (1210cy)

- 25% Reduction in formwork (28000sqft)

- 14.3% increase in reinforcement

- Cost Savings of $157,017.74

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide21 l.jpg

Cost AnalysisFloor Slab

Notes:

- 1” reduction in slab thickness

- 11.1% Reduction in volume (1260cy)

- 7.2% increase in reinforcement

- Increased Cost of $5,493.33

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide22 l.jpg

Cost AnalysisShear Walls

  • Notes:

  • 291.33cy of additional concrete

  • 14,683.2 sqft of formwork

  • 12.6 ton of additional reinforcement

  • Approximately $81,700 in additional cost

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide23 l.jpg

Cost AnalysisConclusions

  • Notes:

  • 2178.67 cy reduction in concrete

  • 14,366 sqft reduction in formwork

  • 106.66 ton increase in reinforcement

  • Cost savings of nearly $70,000.00

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide24 l.jpg

Schedule AnalysisInitial Considerations

Purpose

Analyze construction time and sequencing of new structural system via floor to floor erection time

  • Possible construction sequence for the original and new system

  • Based on a 2 week floor to floor construction time

  • Production number calculated from 2001 edition of RSMeans

  • Slab pours would be made every 2 days to facilitate construction of both towers simultaneously

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide25 l.jpg

Schedule AnalysisProduction

  • Production capacity

    • 1 crew can erect 3 columns / day

    • 1 crew can erect 1 shear wall / 2 days

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide26 l.jpg

Schedule AnalysisOriginal System

  • 70 Columns in 10 days

    • 2.3 crews needed

  • Columns

    • 2 Form crews

    • 1 Rebar crew

    • 1 Concrete crew

  • Elevated Slab

    • 4 Form Crews

    • 3 Rebar Crews

    • 2 Concrete Crews

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide27 l.jpg

Schedule AnalysisNew System

  • 70 Columns & 2 Shear Walls in 10 days

  • Equivalent to 82 Columns

    • 2.73 crews needed

  • Columns / Shear Wall

    • 3 Form crews

    • 1 Rebar crew

    • 1 Concrete crew

  • Elevated Slab

    • 4 Form Crews

    • 3 Rebar Crews

    • 2 Concrete Crews

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide28 l.jpg

Schedule AnalysisConclusions

  • Both systems require same crews for elevated slab work

  • New structural system requires 1 additional crew for columns / shear walls

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide29 l.jpg

Office LightingInitial Considerations

Purpose

Design a general lighting system for the open office spaces

  • Ceiling height is approximately 11’-8”

  • No finished ceiling

    • Exposed underside of concrete slab

    • Exposed Mechanical 18” Deep

  • Spaces used primarily used for office work

  • Requires Approximately 50fc or 500lx on the work plane

  • Best choice for these requirements is an indirect lighting system

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide30 l.jpg

Office LightingDesign

  • Due to exposed mechanical systems and no finished ceiling, indirect lighting would not work well

  • Decision to incorporate reflector panels was made

    • Provide ideal surface for reflected light

    • Hang 24” from ceiling

    • Able to provide access to exposed mechanical and fire protection services

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide31 l.jpg

Office LightingResults

  • Model was created using Lightscape

  • Peerless LDX030452 was selected

    • Uses (3) 32W T8 lamps

    • Input Wattage of 113W

  • Produced approximately 510lx on work plane

  • Power density of 0.715 W/sqft

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide32 l.jpg

Office LightingRenderings

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide33 l.jpg

Conclusions & Recommendations

  • Floor slabs were reduced from 9” to 8” resulting in an 11% reduction in dead load

  • Implementation of shear walls reduced bending stresses in columns

  • Column size reduced to 24”x24”

    • 43.8% reduction in volume

    • 2200 sqft of additional floor space

  • New design results in a savings of $70,000

  • No change in floor cycle time

  • Lighting design provides an efficient and aesthetic pleasing system for the general office spaces

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide34 l.jpg

Acknowledgements

Thank You to the following….

- Discovery Communications Inc.

- Clark Construction Inc. with special consideration to

Ray Sowers

George Conard

Ken Alexander

- The entire AE Faculty with special consideration to

Dr. Lewis Geschwindner

Dr. Thomas Boothby

Dr. Linda Hanagan

- My Family

- My Friends in and out of Architectural Engineering

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide35 l.jpg

Questions

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Location l.jpg
Location

  • Silver Springs, MD

  • Intersections of Georgia Avenue and Colesville Road

  • Approximately 8 miles from downtown Washington D.C.

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide37 l.jpg

Building Overview

Layout & Function

- Multipurpose Office Facility

- two independent towers, of 7 and 10-stories

- 3 levels of underground parking

- 550,000 sqft. of open office space

- $52 Million overall cost

Architecture

- Aluminum and Glass curtain wall system

-12-story glass atrium connects the two building

- Rooftop Terrace and Garden

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide38 l.jpg

Structural AnalysisShear Walls

  • No impact on existing mechanical and Fire Protection Services

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide39 l.jpg

Structural Analysis3D Analysis

Pennsylvania State University

Architectural Engineering

Josh Woolcock

Structural Option


Slide40 l.jpg

Breadth Aspects

Lateral System Cost Analysis

Determine cost implications of new structural systems

Lateral System Schedule Analysis

Analyze construction time and sequencing of new structural system via floor to floor erection time

Office Lighting Design