Evolution of Antipumping relay

The new electronic version of the antipumping relay replaces the obsolete electromechanical relay, with the ability to handle multi-voltages. Changes in the electrical diagram and offer structure have been made. Spare parts for different mechanisms are recommended to be replaced simultaneously.

davidmoss
Download Presentation

Evolution of Antipumping relay

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Evolution of Antipumping relay SF, LF, Evolis 24kV, EvolisHP

  2. Anti pumping Relay Description: The anti-pumping relay is built into the mechanism of circuit breakers to ensure that the opening order has priority. This function prohibits re-closing of CB in case of fault tripping. In other words it prevents the possibility of maintaining a permanent closing order inorder to avoid « pumping » of the CB Antipumping relay:

  3. What’s new? • Replacement of Electromechanical antipumping relay by Electronic version due to obsolete component. • Capable of handling multi-voltages, from 24V to 380V • Input: DC/AC, Output: DC only. Associated closing release coil YF to have DC ratings only • New Electrical diagram: Change in assembling closing coil with relay Please see attached file for the updated diagrams.

  4. Ex. of updated Electrical Diagram

  5. Change in the offer structure • Configured full product: • No impact in Elonet configuration. • Additional bridge options of internal electrical connection is not possible anymore. Only standard bridge remains unchanged. • Additional leaflet with new electrical diagram is attached with user manual systematically • Spare part: • Ref MV261200 will be replacing old references for RI mechanism in SF, LF, Evolis 24 and Evolis HP ranges • Ref MV261202 will be replacing old references for GmH mechanism in SF MCset4, SF F400 and SF2 fixed versions. • It is recommended to replace the closing coil and relay at the same time. • Level C adaptation: Separate Mail

  6. Implementation Planning Configured full product: Week 30 Week 23 LF Evolis 24 Evolis HP SF