1 / 24

Ex isolating spark gaps Examples of use

Ex isolating spark gaps Examples of use. Ex isolating spark gap EXFS 100; Part No. 923 100 Application environment. Isolating spark gaps or protective spark gaps are supposed to establish a galvanic isolation of electric parts of the installation, which are not connected with

cara
Download Presentation

Ex isolating spark gaps Examples of use

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Ex isolating spark gaps Examples of use

  2. Ex isolating spark gap EXFS 100; Part No. 923 100Application environment • Isolating spark gaps or protective spark gaps are supposed to establish a galvanic isolation of electric parts of the installation, which are not connected with • each other under normal operating conditions. • - Specific applications: • for establishing a galvanic isolation of insulatingflanges and insulated couplings (e.g. fuel pipes) • Cathodic corrosion protection of tanks • Cathodic corrosion protection of pipelines • Lightning equipotential bonding of gas pressure regulation stations • Assembly: • Isolating spark gaps can be mounted between the parts of the installation to be bridged by means of brackets or connectors. When mounting isolating sparks, the shortest possible cable length should be used as long cables increase the danger of inductive voltages putting unnecessary stress on the isolation. EXFS 100 14.01.08 / 5242e

  3. Ex isolating spark gap EXFS 100; Part No. 923 100Application EXFS 100 14.01.08 / 5238e

  4. Cathodic corrosion protection of tank installatins EXFS 100 building earth – ~ + EXFS 100 14.01.08 / 5300e

  5. Insulating flange of fuel or product pipelines EXFS 100 insulating flange building earth EXFS 100 14.01.08 / 5301e

  6. Insulating flange of fuel or product pipelines EXFS 100 insulating flange EXFS 100 – ~ insulating flange + EXFS 100 14.01.08 / 5302e

  7. Insulating flange of fuel or product pipelines EXFS 100 insulating flange EXFS 100 gas pressure regulator insulating flange EXFS 100 14.01.08 / 5303e

  8. Installation of EXFS 100 EXFS 100 EXFS 100 minimum distance 2 cm pipeline pipeline EXFS 100 14.01.08 / 5304e

  9. Installation of EXFS 100 electric actuator, e.g. MOV (motor operated valve) cathodic corrosion protection 16 mm² Cu Insulating flange ground earth-termination system EXFS 100 14.01.08 / 5305e_a

  10. Installation of EXFS 100 detail electric actuator, e.g. MOV (motor operated valve) EXFS 100 cathodic corrosion protection 16 mm² Cu Insulating flange ground earth-termination system EXFS 100 14.01.08 / 5305e_b

  11. Installation of EXFS 100 cathodic corrosion protection detail electric actuator, e.g. MOV (motor operated valve) EXFS 100 16 mm² Cu Insulating flange ground earth-termination system EXFS 100 14.01.08 / 5305e_c

  12. Installation of EXFS 100 < 300 mm arrangement as required CCP - side loop loop Reference: Eon Ruhrgas EXFS 100 14.01.08 / 5306e

  13. Installation of EXFS 100 Type A Installation of EXFS 100 if several pipelines are run closely in parallel and insulating units installed directly side by side. Type B loop If possible the isolating spark gaps shall be installed symmetrically between the pipelines. Reference: Eon Ruhrgas EXFS 100 14.01.08 / 5307e

  14. Installation of EXFS 100 Type C EXFS 100 14.01.08 / 5308e

  15. Ex isolating spark gaps EXFS 100 (KU)Application Reference: Schwelm Anlagentechnik GmbH, Austria EXFS 100 14.01.08 / 5317e_a

  16. Ex isolating spark gaps EXFS 100 (KU)Application Reference: Schwelm Anlagentechnik GmbH, Austria EXFS 100 14.01.08 / 5317e_b

  17. Ex isolating spark gaps EXFS 100 (KU)Application Reference: Schwelm Anlagentechnik GmbH, Austria EXFS 100 14.01.08 / 5317e_c

  18. Ex isolating spark gaps EXFS 100 (KU)Application Reference: Schwelm Anlagentechnik GmbH, Austria EXFS 100 14.01.08 / 5317e_d

  19. Ex isolating spark gaps EXFS 100 (KU)Application Reference: Schwelm Anlagentechnik GmbH, Austria EXFS 100 14.01.08 / 5317e_e

  20. Ex isolating spark gaps EXFS 100 (KU)Application Reference: Schwelm Anlagentechnik GmbH, Austria EXFS 100 14.01.08 / 5317e_f

  21. Ex isolating spark gaps EXFS 100 (KU)Application Reference: Schwelm Anlagentechnik GmbH, Austria EXFS 100 14.01.08 / 5317e_g

  22. Ex isolating spark gaps EXFS 100 (KU)Application Reference: Schwelm Anlagentechnik GmbH, Austria EXFS 100 14.01.08 / 5317e_h

  23. Ex isolating spark gaps EXFS 100 (KU)Application Reference: Schwelm Anlagentechnik GmbH, Austria EXFS 100 14.01.08 / 5317e_i

  24. Ex isolating spark gaps EXFS 100 (KU)Application Reference: Schwelm Anlagentechnik GmbH, Austria EXFS 100 14.01.08 / 5317e_j