1 / 17

Voltage Support Service (VSS) for CREZ Region

Voltage Support Service (VSS) for CREZ Region. Advanced Network Applications ERCOT. Voltage Control Challenges in CREZ. Maintain voltages within operational limits Weak grid in the panhandle with no large synchronous generators to provide stability

audra-lyons
Download Presentation

Voltage Support Service (VSS) for CREZ Region

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Voltage Support Service (VSS) for CREZ Region Advanced Network Applications ERCOT

  2. Voltage Control Challenges in CREZ • Maintain voltages within operational limits • Weak grid in the panhandle with no large synchronous generators to provide stability • Long, highly compensated 345KV transmission lines to load centers in the north • Extreme variability of wind power outputs and transfers • Coordination between different Transmission Service Providers and the ERCOT Control room • Minimize continuous variation and switching of control equipment

  3. VOLTAGE SUPPORT SERVICES (VSS) • VSS is a tool built into the Alstom EMS Application • VSS application is designed to resolve voltage violations by solving an optimization problem • Uses following controls • Shunt Capacitors/reactors • Generators • Transformers • Solves for both base case and post-contingency conditions. • Runs every five minutes along with State Estimator and Contingency Analysis • VSS application will be used to manage voltage violations in CREZ

  4. VSS Results For TSPs • VSS results will be made available to all the TSPs using the SOTE application • TSPs will see the same displays available to ERCOT operators in the control room thus helping in communications between ERCOT and TSPs • Dashboard and Overview displays provided to improve CREZ TSPs’ situational awareness and system overview • Tabular displays to provide detailed information about the neighboring TSPs’ reactive device statuses and outputs, voltages and suggested control actions

  5. Access SOTE and VSS Applications • Login to SOTE • Login into ERCOT Citrix using https://gateway.ercot.com/ • Click on the SOTEEMS icon to open the SOTE system • Once the SOTE application is open, click on the “VSS” icon in the toolbar on top of the window.

  6. CREZ Dashboard Display

  7. CREZ Dashboard Display (Continued) • Graph – Shows the PU voltages for all buses in the CREZ stations • Hover mouse on the dots to display the Station name and Bus PU voltage • Tabular display – Shows Owner, Station, Voltage PU, Voltage KV etc.. • Highlights voltages above and below the limits

  8. Application runtimes • SE, CA and VSS timestamps show the last successful runtime for these applications • Helps in identifying upstream application issues during failures ERCOT Public

  9. Activate violations to VSS - Basecase • Click on the “Basecase Voltage Violations” button to view the violations activated to VSS for resolution • ERCOT Operator has the option to activate / deactivate violations to the VSS application ERCOT Public

  10. Activate violations to VSS – Contingency Analysis • Click on the “Contingency Voltage Violations” button to view the Contingency violations activated to VSS for resolution • ERCOT Operator has the option to activate / deactivate violations to the VSS application ERCOT Public

  11. CREZ Overview Displays • Click “CREZ Region” button • Shows 5 regions that the CREZ stations have been divided into

  12. CREZ Overview Displays (Continued) • Click on any of the regions – Example “WEST” • Shows the stations in the zone and the connectivity between the stations

  13. CREZ Overview Displays (Continued) • Click on any of the stations – Example “BITTER” • Shows the station online for the selected station • Same displays used by the ERCOT control room

  14. CREZ Capacitor / Reactor status – Example Capacitors • Click on “Capacitors in service” button • Shows the CREZ region Capacitors that are switched in • Click on “Capacitors Available” button • Shows the CREZ region Capacitors that are switched off but available to turn on

  15. VSS Results • Click on “VSS Results” button • Shows the violations activated to VSS by the ERCOT Operator • Shows the Control Actions suggested by VSS

  16. VSS Controls • Click on “VSS Controls” button • Shows all reactive devices that can provide voltage control in the CREZ region

  17. Initial List of Stations Identified As CREZ Related

More Related