An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Reduced-order Modeling Framework for Improving Spatial Resolution of Data Center Transient Air Temperatures Levente Klein, Hendrik Hamann IBM TJ Watson Research Center 1101 Kitchawan Road Yorktown Heights, NY 10598 kleinl@us.ibm.com hendrikh@us.ibm.com Rajat Ghosh, Yogendra Joshi Georgia Institute of Technology 801 Ferst Drive Atlanta, GA 30332-0405 rajat.ghosh@gatech.edu yogendra.joshi@me.gatech.edu SEMI-THERM 29 March 21, 2013

  2. Dynamic Events in Data Centers • Fluctuating IT load • Power Outage Liu et al., Phil. Trans. R. Soc. A 2012 370 Microsoft Live Messenger Courtesy Junwei Li, CERCS, GT

  3. Dynamic Resource Allocation Over-Provisioning Loss of cooling resources ( Lower CRAC set points than required) Need for real-time datacenter thermal characterization for better capacity planning Armbrust et al., 2009, Report UCB/EECS-2009-28

  4. Outline • Problem Statement. • Methodology. • Case Study. • Conclusion.

  5. Optimization Problem • Efficient CRAC control system • Return/ supply air temperature control based on air temperature field. • Requirement • Rapid dynamic characterization of DC air temperature field. • Highly-resolved air temperature prediction in time and space. Time scale:10 s 10 kW IT rack 800 W/ ft3 heat load Length scale: 1” / 2.5 cm

  6. Potential Solution • Computational Modeling • CFD/ HT-based solution. • Discretization of the domain into grid points. • Iterative solution of discretized conservation equations. • Experiment • Deployment of sensor network. • Data acquisition. • Measurement-based Modeling • Using sensor data as input to statistical modeling framework. • Data compression techniques: • Proper orthogonal decomposition (POD). • Multivariate interpolation.

  7. Example Problem A 2 ft. x 2 ft. x 6ft. 10 kW Rack • Computational simulation • 1.4 grid points. • 8 hr. (Quad-core processor and 12 GB RAM) for convergence. • Experiment • 6” resolution. • Difficulty in sensor deployment in largely space-constraint facility. • Measurement-based Modeling • A platform for improving granularity of sensor data. • 2 decades of length scale faster than CFD modeling.

  8. Interpolation Vs. POD • Data Matrix: m x n • Interpolation: • Computation ~ O(m) • POD: • Computation ~ log(k) : k<m. • POD Coefficient determination: • Column wise interpolation with a k x n base matrix. • Base matrix elements smaller than data • Smaller error due to interpolation. • Advantages of POD: • Computationally more efficient. • Better accuracy.

  9. Modeling Algorithm • Independent Variable • Time. • Row-wise compilation in ensemble . • Parameter • Spatial location. • Column-wise compilation in ensemble. • POD Modes • Optimal basis. • POD Coefficients • Spatial dependency of interrogation. • Principal Component • Cut-off Criteria. • Useful tool for analyzing time signals • of high dimensionality.

  10. Ensemble Compilation Interrogation Points • Two-point method • Two transient temperature data (vector) constitutes the ensemble. • Least data acquisition cost. • Two near most sensors are reasonable choice. • 1-D spatial prediction. Class-1: - Two nearest sensors lying in opposite direction. Class-2: - Two nearest sensors lying in same direction.

  11. Experimental Facility 2013 W 2 ft. X2 ft. X 6 ft. 1 3 2 5.85 m3/s (12400 cfm) 5.85 m3/s (12400 cfm) 2075 W 2 ft. X1.8 ft. X 6 ft. 2753 W 2 ft. X2.5 ft. X 6 ft. Grey blocks: IT rack. Blue blocks: ACUs. Yellow blocks: PDU. Red block: Storage.

  12. Temperature Measurement x • 10 K-type thermocouples placed on a pole, located at the server outlets. • Measurement period: 1.5 s. • Measurement uncertainty:

  13. Experimental Condition Photograph Courtesy to Dr. Levente Klein, IBM For this case study, the block/ unblocking period is 30 min. Simulated dynamic temperature field: Periodic blocking and unblocking of rack airflow intake.

  14. Data h h h h h h h h h Significant phase shift due to boundary effect (cold air mixing) In-phase with blocking/ unblocking In-phase with blocking/ unblocking In-phase with blocking/ unblocking In-phase with blocking/ unblocking Boundary Effect Appears Boundary Effect Appears In-phase with blocking/ unblocking Boundary effect dominant

  15. Data Comparison • No particular temperature trend is observed • Maximum at 3.3 ft. • Minimum at 7.5 ft.

  16. POD-based Prediction • For Validation purpose, POD-based predictions are computed at points coincident with the sensors. • Two point ensemble compilation method used: Interrogation Point Class-2 Ensemble sensor data Class-1 Ensemble sensor data Interrogation Point

  17. POD-based Modeling • Eigen Space • Prediction • Interrogation Point: 3.3 ft. (1006 mm). • Ensemble Sensor: (5,7). Data Matrix: 4425 x 2 • Computational prediction time for a new temperature data ~ 1 s • (2.66 GHz Core2Duo processor, 4 GB RAM). • k=1: only 2 interpolations required. 1st POD mode captures dominant characteristics.

  18. Comparison

  19. Error Distribution Large error due boundary effect Time Sample Size=4425.

  20. Space-time Mapping Large Error at h=0 due the Boundary Effect Increase in Temperature due to Blocking Decrease in Temperature due to Unblocking

  21. Conclusion • A modeling framework is developed for improving the spatial resolution of experimentally-acquired transient temperature data. • The framework is applied on a representative case study with dynamic temperature evolution. • The framework predicts the temperature evolution with reasonable accuracy.

  22. Thank You!!