1 / 54

Dust Explosion Hazard Assessment and Control An Overview

Dust Explosion Hazard Assessment and Control An Overview. Vahid Ebadat, Ph.D. Chilworth Technology, Inc. 250 Plainsboro Road, Building 7 Plainsboro, NJ 08536 TEL: 609 799 4449 FAX: 609 799 5559 email: vebadat@chilworth.com http://www.chilworth.com Presentation at

aradia
Download Presentation

Dust Explosion Hazard Assessment and Control An Overview

An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Dust Explosion Hazard Assessment and Control An Overview Vahid Ebadat, Ph.D. Chilworth Technology, Inc. 250 Plainsboro Road, Building 7 Plainsboro, NJ 08536 TEL: 609 799 4449 FAX: 609 799 5559 email: vebadat@chilworth.com http://www.chilworth.com Presentation at American Industrial Hygiene Conference & Exposition - Pharmaceutical Forum June 3rd, 2009, Toronto, Canada

  2. Dust Explosion Hazard Assessment and Control An Overview • Presentation Outline • Conditions for a Dust Cloud Explosion • Management of Dust Cloud Explosion Hazards • Explosion Characteristics of Dust Clouds • Control of the Spread of Combustible Dust Atmospheres • Elimination/Control of Potential Ignition Sources • Application of Explosion Safeguards

  3. FUEL OXIDANT IGNITION SOURCE Fire Triangle • FUEL - Liquid (vapor or mist), gas, or solid capable of being oxidized. Combustion always occurs in the vapor phase; liquids are volatized and solids are decomposed into vapor prior to combustion • OXIDANT - A substance which supports combustion – Usually oxygen in air • IGNITION SOURCE - An energy source capable of initiating a combustion reaction

  4. Conditions Required for Dust Cloud Explosions to Occur • A number of conditions must exist simultaneously for a dust explosion to occur: • Dust must be explosible (combustible, Flammable) • Dust must be airborne • Dust concentrations must be within explosible range • Dust must have particle size distribution capable of propagating a flame • The atmosphere in which the dust cloud is present must be capable of supporting combustion • An ignition source with sufficient energy to initiate flame propagation must be present

  5. Explosibility Screening Use a Hartmann Bomb, 20L sphere, or 1m3 sphere test vessel to determine whether the dust cloud is explosible at the dust handling/processing conditions Modified Hartmann Apparatus • Dusts which ignite and propagate away from the source of ignition are considered “explosible” • Dusts which do not propagate flame away from the ignition source are considered “non-explosible”

  6. Conditions Required for Dust Cloud Explosions to Occur • A number of conditions must exist simultaneously for a dust explosion to occur: • Dust must be explosible (combustible, Flammable) • Dust must be airborne • Dust concentrations must be within explosible range • Dust must have particle size distribution capable of propagating a flame • The atmosphere in which the dust cloud is present must be capable of supporting combustion • An ignition source with sufficient energy to initiate flame propagation must be present 6

  7. Management of Dust Cloud Explosion Hazards • Site Audit: • Understand process operations and review of all available information (drawings, specifications, process/operation descriptions) • Identification of locations where combustible dust cloud atmospheres are or could be present during normal and abnormal operating conditions • Identification of potential ignition sources that could be present under normal and abnormal conditions • On-site electrostatic measurements (electrical field, electrical continuity measurements, etc.), where applicable • Understanding of the explosion characteristics of the dust(s) • Proper process and facility design to prevent and/or minimize the occurrence of dust explosions and protect people and facilities against their consequences • Regular inspection and maintenance of equipment to minimize ignition sources and dust releases

  8. Laboratory Testing to Understand Explosion Characteristics of Dusts • How easily will the dust cloud ignite? • Minimum Ignition Energy (dust cloud) • Minimum Ignition Temperature (dust cloud and dust layer) • Thermal Instability • Electrostatic Properties • Electrostatic Chargeability • Resistivity / Conductivity • What will happen if the dust cloud does ignite? (Consequences of Ignition) • Maximum Explosion Pressure • Maximum Rate of Pressure Rise • Ensuring Safety by Avoiding/Controlling Flammable Atmospheres? • Minimum Explosible Concentration • Limiting Oxygen Concentration

  9. Management of Dust Cloud Explosion Hazards • Control of the spread of combustible dust atmospheres: • Proper plant design • Use of local exhaust ventilation • Management of dust deposits • Elimination/control of potential ignition sources including: • Electrostatic discharges • Mechanical friction and sparks • Hot surfaces and equipment • Thermal decomposition • Electrical arcs (sparks) • Application of explosion safeguards: • Explosion protection (containment, relief venting, explosion suppression) • Explosion isolation • Inert Gas Blanketing

  10. Explosible Dust Cloud Concentration 10 Explosion Violence 5 0 0 250 500 750 1000 Dust Concentration (g/m3) Minimum Explosible Concentration (ASTM E 1515) • When concentration of dispersed dust cloud in air is below the Minimum Explosible Concentration, an explosion can not propagate • Explosion violence of the cloud increases as the dust concentration increases until an optimum concentration is reached giving the highest explosion violence

  11. (b) (a) (c) 1mm layer of dust of bulk density 500kg/m3 500 g/m3 100 g/m3 5m 1m C = Pbulk * h / H Control of the Spread of Combustible Dust Atmospheres Illustration of the potential hazard of even thin dust layers. A 1mm layer of a dust of bulk density 500Kg/m3 will generate a cloud of average concentration 100g/m3 if dispersed in a room of 5m height. Partial dispersion up to only 1m gives 500g/m3(Eckhoff) C is dust cloud concentration Pbulk is powder bulk density h is dust layer thickness H is dust cloud height in the room

  12. Control of the Spread of Combustible Dust Atmospheres • Equipment should be maintained and operated in a manner that minimizes the escape of dust • Continuous local exhaust ventilation should be provided for processes where combustible dust is liberated in normal operation so as to minimize the escape of dust. The dust should be conveyed to dust collectors • Regular cleaning frequencies should be established for floors and horizontal surfaces, such as ducts, pipes, hoods, ledges, and beams, to minimize dust accumulations within operating areas of the facility

  13. Management of Dust Cloud Explosion Hazards • Control of the spread of combustible dust atmospheres: • Proper plant design • Use of local exhaust ventilation • Management of dust deposits • Elimination/control of potential ignition sources including: • Electrostatic discharges • Mechanical friction and sparks • Hot surfaces and equipment • Thermal decomposition • Electrical arcs (sparks) • Application of explosion safeguards: • Explosion protection (containment, relief venting, explosion suppression) • Explosion isolation • Inert Gas Blanketing

  14. Minimum Ignition Energy Apparatus Minimum Ignition Energy (MIE), (ASTM E 2019) MIE of a flammable material is the smallest electrostaticspark energy needed to ignite an optimum concentration of the material using a capacitive spark Ignition Chamber Current Limiting Resistor Switch D.C. Voltage Source Capacitor Decoupling Resistor Electrostatic Voltmeter

  15. 10 5 0 Minimum Ignition Energy (mJ) 0 250 500 750 1000 Dust Concentration (g/m3) MIE and the Effect of Dust Cloud Concentration

  16. Factors Affecting Minimum Ignition Energy

  17. Systematic Approach to Electrostatic Hazard Assessment Schematic of a Typical Chemical Processing Plant Tank farm Reactor Centrifuge Mill Vacuum Dryer

  18. Electrostatic Discharges and Their Control Several types of electrostatic discharges are distinguished depending on resistivity and the geometric arrangement of the charged object and the geometry of the discharge initiating electrode: • Spark Discharge - Spark from ungrounded conductor Stored (Spark) Energy = ½ C V2 • Resistance to ground should be checked. If R > 10 ohm, direct ground connection is required • Propagating brush Discharge - Discharge from the surface of an insulator backed by a conductor (e.g. plastic or glass-lined metal pipes and vessels) and from the surfaces of plastic pipes and hoses used for pneumatic conveying of powders Maximum discharge energy of 1,000mJ to 2,000mJ • Avoid the use of plastic pipes and hoses for pneumatic conveying of powders • Avoid plastic containers/liners for powders with high charge densities

  19. Electrostatic Discharges and Their Control Several types of electrostatic discharges are distinguished depending on resistivity and the geometric arrangement of the charged object and the geometry of the discharge initiating electrode: • Discharges from Human Body • Maximum energy of about 25mJ to 30mJ • Personnel should be grounded so that their • resistance-to-ground <1x108 ohm • Static dissipative footwear may be used • Resistance of the floor/surface on which the • operator is standing should also be <1x108 ohm

  20. Electrostatic Discharges and Their Control Several types of electrostatic discharges are distinguished depending on resistivity and the geometric arrangement of the charged object and the geometry of the discharge initiating electrode: • “Bulk”/”Cone” Discharge - Discharges on the surface of the powder during filling of vessels/bins/containers • Maximum discharge energy about 25mJ (depending on powder Volume Resistivity, Electrostatic Chargeability, particle size, and vessel dimensions)

  21. Volume Resistivity - General Accordance with ASTM D 257 • The ability of a material (powder) to retain/dissipate electrostatic charges • Volume Resistivity is a property of the material itself, regardless of the dimensions of the sample • Volume resistivity of material, is related to the resistance, R, measured when a voltage is applied across it, by the following equation • Volume Resistivity, pv= R A/d • A is the sample area and d its length • The units of Volume Resistivity are Ohm meters (Ω.m)

  22. Measurement of Volume Resistivity of Powders Electrodes Guard Ring Powder Current meter Insulating Cell High Voltage Power supply Volume Resistivity can be influenced by the moisture content of powder

  23. Classification of Materials by their Volume Resistivity

  24. Electrostatic Chargeability - General Accordance with ASTM D 257 • The concept of chargeability refers to the propensity of a material to become charged when flowing through conveyances or when handled in containers • Chargeability is measured by flowing the test sample through tubes of uniform length and made from different materials -- specifically stainless steel, plastic, and glass -- and measuring the resultant electrostatic charge • The test provides data that can be used to develop appropriate materials handling guidelines Powder Chargeability Testing

  25. Control of Electrostatic Hazards - Discharges from Powders • Static charge can build up on powders with Volume Resistivity >109 ohm.m or if powder is in insulating or ungrounded conductive vessels • Control measures depend on Minimum Ignition Energy of the dust cloud and Volume Resistivity of the powder : • Volume Resistivity < 109 Ohm.m • No electrostatic charge accumulation if powder is handled in grounded conductive plant • Volume Resistivity > 109 Ohm.m and Minimum Ignition Energy >25mJ • No electrostatic ignition hazard in grounded conductive plant

  26. Control of Electrostatic Hazards - Powders • Volume resistivity > 109 Ohm.mand Minimum Ignition Energy <25mJ • If the Electrostatic Chargeability test results show that the quantity of electrostatic charge on the particles is sufficient to cause discharges from the surface of the bulking powder one of the following measures is suggested: • Installation of inert gas blanketing, or • Installation of explosion protection

  27. Air Sample Temperature Minimum Ignition Temperature - Dust Cloud, (ASTM E 1491) • Minimum Ignition Temperature of a dust cloud is a measure of its sensitivity to ignition by heated environments • Minimum Ignition temperature is NOT a fundamental property of the dust. Factors affecting MIT include particle size, moisture content, and test apparatus Godbert Greenwald (GG) Furnace

  28. Minimum Ignition Temperature - Dust Layer, (ASTM E 2021) • MIT of dust layer is the lowest temperature of a heated free-standing surface capable of igniting a dust layer (12.7mm thick) • With thicker layers, smoldering / glowing may start at a lower temperature • Test applicable only for materials which will not melt or evaporate before reaching the ignition temperature

  29. Minimum Ignition Temperature • Minimum Ignition Temperature tests provide information on: • Sensitivity to ignition by: • hot environments and surfaces of some processing equipment and plant • hot surfaces caused by overheating of bearings and other mechanical parts due to mechanical failure • frictional sparks • Maximum exposure temperature (Temperature Rating) for electrical equipment

  30. Thermal Instability (Self-Heating) • Ignition of bulk powders can occur by a process of self-heating • Ignition occurs when the temperature of the powder is raised to a level at which the heat liberated by the exothermic reaction is sufficient to exceed the heat losses and to produce runaway increase in temperature • The minimum ambient temperature for self-ignition of a powder depends mainly on the nature of the powder and on its dimensions

  31. Thermal Instability Hazards EXPOSURE TIME SCALE (THICKNESS + SHAPE) AIR AVAILABILITY CONTAINMENTS LABORATORY TESTING AIR OVER LAYER TEST Simulate powder deposits on dryer surfaces or walls BASKET TEST Simulate large scale storage or transport conditions BULK POWDER TEST Simulate bulk powder in IBC, Bags, bottom of hopper AERATED POWDER TEST Simulate fluidized bed drying • Is difference between onset and drying temperature < 50°C? • Is drying cycle longer than screening test period? • Is onset temperature < 200°C? ISOTHERMAL TEST Temperature: 50°C above drying temp. Duration: longer than drying or storage time

  32. Thermal Instability (Self-Heating)

  33. Control of Heat Sources and Frictional Sparks • Preventing overloading of processing plant (grinders, conveyors, etc.) • Isolation or shielding of hot surfaces • Prevention/removal of dust accumulations on hot surfaces • Use of approved electrical equipment (correct temperature rating) • Prevent overheating due to misalignment, loose objects, belt-slip/rubbing etc. by regular inspection and maintenance of plant • Prevent foreign material from entering the system when such foreign material presents an ignition hazard. Consider use of screens, electromagnets, pneumatic separators, etc. • Hot work operations should be controlled by a hot work permit system in accordance with NFPA 51B, Standard for Fire Prevention During Welding, Cutting and Other Hot Work

  34. Elimination/Control of Potential Ignition Sources – Electrical Equipment • Incorrectly specified electrical equipment is a potent ignition source for flammable gases, vapors and dusts • Sparks • Hot surfaces • In facilities handling flammable materials the electrical equipment used must be suitable for the environment in which it is to be used • In order to determine the type of equipment it is necessary to define hazardous (classified) locations

  35. Electrical Area Classification • Electrical area classifications defined under Article 500 of the National Electrical Code (NFPA 70) • The intent of Article 500 is to prevent electrical equipment from providing a means of ignition for an ignitable atmosphere • Two classes of hazardous locations: • Class I Flammable gases or vapors (NFPA 497) • Class II Combustible dusts (NFPA 499) • Two divisions of hazardous locations: • Division 1 Normally or frequently present • Division 2 Not normally present, but possible

  36. Extent of Class II Locations • Dust-tight equipment and good maintenance reduces the extent of classified areas • Effective dust removal (ventilated hoods and pickup points) and excellent housekeeping reduces the extent of a classified area • Where there are walls that limit the travel of the dust particles, area classifications do not extend beyond the walls

  37. Selection of Electrical Apparatus

  38. Management of Dust Cloud Explosion Hazards • Control of the spread of combustible dust atmospheres: • Proper plant design • Use of local exhaust ventilation • Management of dust deposits • Elimination/control of potential ignition sources including: • Electrostatic discharges • Mechanical friction and sparks • Hot surfaces and equipment • Thermal decomposition • Electrical arcs (sparks) • Application of explosion safeguards: • Explosion protection (containment, relief venting, explosion suppression) • Explosion isolation • Inert Gas Blanketing

  39. Explosion Severity of Dust Cloud, Kst (ASTM E 1226) • An indication of the severity of dust cloud explosion • Data produced: • Maximum developed pressure, Pmax • Maximum rate of pressure rise, (dP/dt)max • Deflagration index (explosion severity) Kst • Kst = (dP/dtmax) . V1/3 [bar.m/s] • Where V is the volume of the test vessel (m3) • Used for the design of deflagration protection (venting, suppression, Containment) 20-Liter Sphere Apparatus

  40. Explosion Severity - Dust Explosion Hazard Classification • Note: • Any explosion can cause burn injuries • Any explosion can cause structural damage if the structure is not strong enough

  41. Explosion Protection Techniques – Explosion Containment • Relies on “explosion resistant construction” to withstand the maximum deflagration pressure of the material being handled • The following points should be considered; • Advantage: Low maintenance, Passive • Disadvantages: High initial cost, Heavy • Equipment is designed either to prevent permanent deformation or to prevent rupture, with some permanent deformation allowable • All interconnected pipe work, flanges, manhole cover etc., should withstand the design explosion pressure • Containment is always necessary when using other protection measures • If an explosion resistant vessel fails, the pressure effects will be more severe than if an extremely weak vessel tears open

  42. 2. Detection - 0.020 Seconds 3. Control - 0.025 Seconds 1. Ignition - 0.000 Seconds 4. Suppression - 0.060 Seconds Explosion Protection Techniques – Explosion Suppression • Relies on early detection of an explosion and rapid injection of suppressant. Typically at moment of detection, explosion pressure is 35 to 100 m bar g. Suppressant extinguishes the flame within approximately 50msec. • To achieve explosion suppression, the following are required; • Explosion Detector • Control Unit • Suppressor • Suppressant

  43. Explosion Protection Techniques – Venting • Relies on rapid opening of panel(s) or door(s) hence allowing the release of hot gases and unburnt product from within a process component or room • Advantages and disadvantages • Relatively low cost • Simple to install in most cases • Not suitable for toxic materials • Venting to inside of buildings is usually unacceptable

  44. Explosion Protection Techniques - Isolation • An explosion, initiated in one plant item should be prevented from propagating along pipes, chutes, conveyors etc. and starting a subsequent explosion in other plant items. • The simplest isolation method is avoidance of unnecessary connections. If this is not possible, special measures should be taken to create barriers to avoid propagation of an explosion. • Mechanical Isolation (Barriers) • Chemical Isolation (Barriers)

  45. Inert Gas Blanketing Techniques - NFPA 69 • An explosion (or fire) can be prevented by reducing the oxidant concentration below a level that will no longer support combustion through the addition of an inert gas to the vessel where the flammable/combustible atmosphere exists. • There are 3 commonly used inerting techniques: • Pressure Purging Vessel is pressurized with an inert gas, then relieved to the outside. This procedure is repeated until the desired oxygen concentration is reached. • Vacuum Purging Vessel is evacuated and then pressure is increased to atmospheric using an inert gas. • Flow-Through Purging Vessel is purged with a continuous flow of inert gas.

  46. Limiting Oxidant Concentration (ISO 6184/1) • The concentration of oxidant below which a deflagration cannot occur is referred to as the Limiting Oxidant Concentration (LOC) • Limiting Oxidant Concentration (LOC) for combustion is dependent on the type of fuel and the inert gas used • Nitrogen gas is the most commonly used inert gas. • Carbon dioxide and argon are also used

  47. Dust Explosion Hazard Assessment and Control An Overview Vahid Ebadat, Ph.D. Chilworth Technology, Inc. 250 Plainsboro Road, Building 7 Plainsboro, NJ 08536 TEL: 609 799 4449 FAX: 609 799 5559 email: vebadat@chilworth.com http://www.chilworth.com Presentation at American Industrial Hygiene Conference & Exposition - Pharmaceutical Forum June 3rd, 2009, Toronto, Canada 58

  48. About Chilworth Technology

  49. Chilworth Technology, Inc. Our History • Chilworth Technology was first established in the UK in 1986 • Since then we have expanded and are now providing process safety and flammability services through our facilities in: • United Kingdom – Chilworth Technology Ltd • United States of America: • Chilworth Technology, Inc – New Jersey • Safety Consulting Engineers - Chicago • Chilworth Pacific Fire Laboratories – Kelso, Washington • Italy – Chilworth Vassallo Srl • France – Chilworth SARL • India – Chilworth Safety and Risk Management Ltd • Spain – Chilworth Amalthea SL

  50. Chilworth Technology, Inc. Our Business • We provide services to business and industry to help identify, characterize, prevent, and mitigate potential fire, explosion, and thermal instability (runaway reaction) hazards in their processes • We achieve this by providing the following services: • Process safety consulting and Incident Investigation • Laboratory testing • Training courses

More Related