An Image/Link below is provided (as is) to download presentation Download Policy: Content on the Website is provided to you AS IS for your information and personal use and may not be sold / licensed / shared on other websites without getting consent from its author. Content is provided to you AS IS for your information and personal use only. Download presentation by click this link. While downloading, if for some reason you are not able to download a presentation, the publisher may have deleted the file from their server. During download, if you can't get a presentation, the file might be deleted by the publisher.

E N D

Presentation Transcript


  1. Energy Efficient Refrigeration Jane Gartshore, Cool Concerns Ltd

  2. Outline • Revision - the basics • Component operation • Factors effecting efficiency • load reduction • operating conditions • The low hanging fruit

  3. Revision • Common principles • How a system works • Importance of operating conditions: • evaporating temperature • condensing temperature • superheat • subcooling

  4. A Simple System

  5. A Simple System COSP = capacity / total power input

  6. COSP • What do you expect the COSP to be?

  7. COSP • What do you expect the COSP to be? Typically … • LT ~ 0.5 to 1.5 • HT ~ 2 to 4 • AC ~ 4 to 6

  8. Superheated gas high pressure Superheated gas low pressure Subcooled liquid high pressure Saturated liquid high pressure Saturated mixture low pressure A Simple System Saturated mixture high pressure

  9. How Many Times Round the Circuit?

  10. How Many Times Round the Circuit? 20,000

  11. Compressor Most efficient if: • compression ratio low • suction superheat low • cooling adequate

  12. Evaporator Evaporator effectiveness depends on ... • evaporating temperature / pressure • size / condition of evaporator • temperature of cooled space / fluid • degree of useful superheat • degree of subcooling

  13. Condenser Condenser effectiveness depends on ... • condensing temperature / pressure • size / condition of condenser • cooling medium • temperature of cooling medium • head pressure control

  14. Superheat Useful superheat • in evaporator • aim for ~ 5K Non useful superheat • in suction line • minimise Refrigerant arriving at compressor must be superheated (but not too much!)

  15. Subcooling • 10K subcooling ~ 7% capacity increase • natural cooling or by subcooler • insulate liquid line when using a subcooler • No subcooling ~ ??% capacity reduction • condensing temperature too low • liquid line passes through hot area • loss of refrigerant

  16. Expansion Valve • Subcooled liquid at entry • Useful superheat setting important • TEV, minimum 6 bar pressure drop • EEV, minimum 4 bar pressure drop

  17. Central Plant Systems • Several smaller compressors for better capacity matching to load • Can be unevenly sized • Controlled on suction pressure

  18. Central Plant Systems

  19. Central Plant Control EV EV EV EV S S S S

  20. Evaporator Temperatures -8 -12 -8 -6 EV EV EV EV S S S S

  21. An Efficient System ... • has minimum load • has minimum temperature lift • uses an efficient combination of components • is well controlled

  22. Keeping the Load Low

  23. Load - Door Management Open door: Freezer, £6/h Chiller, £3/h

  24. Load - Product Loading

  25. Load - Defrost • Does the defrost work? • Is it controlled correctly • Defrost on demand can improve efficiency

  26. Load - Auxiliaries Switching off fans can save up to 14%

  27. Load - Sec. Ref. Pumps • Contribute twice to energy use • direct electricity consumption • heat into secondary fluid • Variable Speed Drive • will reduce pump power, e.g. by 25% • will reduce heat load

  28. Load - Insulation Cold store / cabinet insulation Secondary fluid pipe work insulation • ensure in good condition • ensure sufficient thickness • ensure well joined / sealed Suction line Liquid line

  29. Temperature Lift • Evaporating temperature • Condensing temperature • Control 1°C = 2% to 4%

  30. Evaporating Temperature • Cooled space / fluid temperature - as high as possible e.g. increasing frozen food store temperature from -25°C to -20°C saves over 10% (and reduces breakdown)

  31. Evaporating Temperature

  32. Evaporating Temperature • Ensure evaporator is clean • Ensure evaporator is clear of frost

  33. Evaporating Temperature • Refrigerant charge is critical • leak test • repair • re-charge

  34. Reduce Leak Potential • Brazed joints • Minimum charge • Minimum pressures • Charge monitoring • Effective leak testing

  35. Condensing Temperature • Ensure condensers are clean

  36. Condensing Temperature What’s the problem here?

  37. Condensing Temperature

  38. Condensing Temperature

  39. Condensing Temperature • Recommend replacement • take opportunity to fit larger condenser

  40. Condensing Temperature Non condensable gases increase condensing temperature • Purge air / nitrogen • use an automatic (refrigerated) air purger • portable versions available

  41. Control • Highest possible evaporating temperature • thermostat / controller (LP) setting • Lowest possible condensing temperature • minimum head pressure control • Appropriate useful superheat • TEV / EEV adjustment • Optimum compressor strategy

  42. Low Hanging Fruit • Cold store air change load reduction • Auxiliary load reduction • Reducing refrigerant leaks • System control • Re commissioning • Maintenance £££'s

  43. Air Change Reduction • Heat and moisture • Door management • Strip curtains / air lock • Try dehumidification • e.g. 8% reduction

  44. Aux Load Reduction Double impact / saving • Evaporator fan motors • E.g. 14% reduction on HT area • Process fluid pump control

  45. PPM 300 250 200 150 100 50 0 3 6 9 12 15 18 21 3 6 9 12 15 18 21 3 6 9 12 15 18 21 3 6 9 12 15 18 21 Tuesday Wednesday Thursday Friday 05/02/2002 06/02/2002 07/02/2002 08/02/2002 Leak Reduction 15% leakage doubles power input • Maintenance • Leak test method • Regime • Fixed leak detection • Charge monitoring

  46. Control • Suction and discharge pressure optimisation • ~10% savings • Defrost on demand • ~2.5% savings • Floating head pressure • ~ 7% savings

  47. Re Commissioning Re set suction & discharge set points Example savings: • 21.2% on HT pack • 13.6% saving on LT pack • 6.9% on total site energy

  48. Maintenance is Vital Ensure there is a maintenance regime which at least … • cleans condensers and evaporators • checks for leaks (and repairs them!) • does an eyes & ears system check